Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XI - Office of Conservation-Pipeline Division
Subpart 4 - Carbon Dioxide
Chapter 45 - Construction Requirements for Carbon Dioxide Pipelines
Section XI-4555 - Valves: Location (Formerly section 1555)
Universal Citation: LA Admin Code XI-4555
Current through Register Vol. 50, No. 9, September 20, 2024
A. A valve must be installed at each of the following locations:
1. on the suction end and the discharge end
of a compressor station in a manner that permits isolation of the station
equipment in the event of an emergency;
2. on each mainline at locations along the
pipeline system that will minimize damage from accidental carbon dioxide
discharge, as appropriate for the terrain in open country, for offshore areas,
or for populated areas;
3. on each
lateral takeoff from a trunk line in a manner that permits shutting off the
lateral without interrupting the flow in the trunk line;
4. on each side of a reservoir holding water
for human consumption.
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:4(C)(17) and R.S. 30:1104(A).
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.