Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XI - Office of Conservation-Pipeline Division
Subpart 2 - Underwater Obstructions
Chapter 25 - Compressed Natural Gas
Section XI-2525 - Pressure Gauges

Universal Citation: LA Admin Code XI-2525

Current through Register Vol. 50, No. 9, September 20, 2024

A. Pressure gauges shall be designed for the normal pressure and temperature conditions to which the devices may be subjected with a burst pressure safety factor of at least four.

B. Dials shall be graduated to read 1.2 times the operating pressure of the system to which the gauge is attached.

C. A gauge shall have an opening not to exceed 0.055 inches (Number 54 drill size) at the inlet connection.

AUTHORITY NOTE: Promulgated in accordance with R.S. 30:751 and 752.

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.