Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XI - Office of Conservation-Pipeline Division
Subpart 1 - Natural Gas and Coal
Chapter 13 - Design Requirements for Carbon Dioxide Pipelines
Section XI-1337 - Sensing Devices
Universal Citation: LA Admin Code XI-1337
Current through Register Vol. 50, No. 9, September 20, 2024
A. Each operator shall determine the appropriate location for and install sensing devices necessary to monitor the operation of components to detect malfunction which could cause a hazardous condition if permitted to continue; and
B. buildings in which potentially hazardous quantities of carbon dioxide may exist must be continuously monitored by carbon dioxide sensing devices set to activate audible and visual alarms in the building and at the control center.
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:4(C)(17).
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.