Louisiana Administrative Code
Title 33 - ENVIRONMENTAL QUALITY
Part XI - Underground Storage Tanks
Chapter 7 - Methods of Release Detection and Release Reporting, Investigation, Confirmation, and Response
Section XI-705 - Release Detection Recordkeeping
Universal Citation: LA Admin Code XI-705
Current through Register Vol. 50, No. 9, September 20, 2024
A. All UST system owners and operators shall maintain records in accordance with LAC 33:XI.509 demonstrating compliance with all applicable requirements of LAC 33:XI.701-703 and LAC 33:XI.803.D. These records shall include the following.
1. All
written performance claims pertaining to any release detection system used and
documentation of the manner in which these claims have been justified or tested
by the equipment manufacturer, installer, or thirdparty independent testing
laboratory must be maintained throughout the operational life of the release
detection system. Beginning no later than September 20, 2021, records of the
site assessments required under LAC 33:XI.701.A.5.b.vi and LAC
33:XI.701.A.5.c.v shall be maintained as long as the methods are used. Records
of site assessments developed after September 20, 2018, shall be signed by a
professional engineer or professional geologist, or equivalent licensed
professional with experience in environmental engineering, hydrogeology, or
other relevant technical discipline acceptable to the department.
a. The department may waive the site
assessment requirement for UST systems that were conducting vapor or
groundwater monitoring prior to September 20, 2018, if the applicable
requirements of LAC 33:XI.701.A.5.a, b, and c were verified during a compliance
evaluation inspection. In these cases, the department will provide a written
waiver to the facility that shall be maintained for as long as the methods are
used.
2. The results of
any sampling, testing, or monitoring shall be maintained for at least three
years, except that the results of tank tightness testing conducted in
accordance with LAC 33:XI.701.A.3 when used in combination with inventory
control and manual tank gauging as a release detection method shall be retained
until the next test is conducted, and shall contain, at a minimum, the
following information.
a. Inventory Control
i. Inventory control records shall include:
(a). the tank identifier;
(b). the month and year of the
report;
(c). the date of the
monthly water check and the measured water level in inches;
(d). the daily start stick inventory in
inches and gallons, gallons delivered, gallons pumped, end stick inventory in
inches and gallons, the over and short measurements, and the initials of the
person conducting the measurements;
(e). the total gallons pumped for the
month;
(f). cumulative over and
short calculation for the month;
(g). the monthly leak check amount;
(h). the monthly leak check amount plus 130;
and
(i). the monthly leak check
result of pass/fail or yes/no.
b. Manual Tank Gauging
i. Manual tank gauging records shall include:
(a). the tank identifier;
(b). the month, day and time of the initial
test;
(c). the first, second and
average initial readings;
(d). the
initial test gallons;
(e). the
month, day and time of the end test;
(f). the first, second and average end
readings;
(g). the end test
gallons;
(h). the change in tank
volume calculated weekly and monthly; and
(i). whether the tank test passes or not
weekly and monthly.
c. Tank Tightness Testing. Tank tightness
test reports shall include the date of the test, the tank identifier, a
qualitative result statement, a calculated leak rate, and any other information
needed to verify compliance with LAC 33:XI.703.A.2.c as applicable to the
equipment and method used. Raw data generated for each tank tightness test
shall be provided to the department upon request.
d. Automatic Tank Gauging (ATG)
i. AT G test reports shall include:
(a). the time, date, or period covered for
the test;
(b). the tank and/or
piping identifier;
(c). a
qualitative result of pass, fail, inconclusive, or alarm code where
applicable;
(d). a quantitative
result with a calculated leak rate; and
(e). any other information needed to verify
compliance with LAC 33:XI.703.A.2.c as applicable to the equipment and method
used.
e. Vapor
Monitoring with RDD
i. Vapor monitoring RDD
records shall include:
(a). the date the
analysis was conducted;
(b). the
well identifiers;
(c). the
concentration measured in each well in parts per million;
(d). a statement or signifier if any of the
measured concentrations represents a suspected release (any significant
increase in concentration above background); and
(e). any other information needed to verify
compliance with LAC 33:XI.703.A.2.c as applicable to the equipment and method
used.
f. Liquid
Monitoring with RDD
i. Liquid monitoring RDD
records shall include:
(a). the date the wells
are checked;
(b). the well
identifiers;
(c). the amount of
product measured in each well;
(d).
the depth to the water surface in each well; and
(e). any other information needed to verify
compliance with LAC 33:XI.703.A.2.c as applicable to the equipment and method
used.
g. Tank
Interstitial Monitoring (IM)
i. Tank IM
records shall include:
(a). the date of the
test;
(b). the tank
identifier;
(c). a qualitative
result statement (i.e., pass or fail, liquid, product or water detected, sensor
normal message, dry space, alarm code when applicable, etc.);
(d). a qualitative result (when applicable);
and
(e). any other information
needed to verify compliance with LAC 33:XI.703.A.2.c as applicable to the
equipment and method used.
h. Statistical Inventory Reconciliation (SIR)
i. SIR records shall include:
(a). the month and year of the
test;
(b). the name of the SIR
provider/vendor/software and the name and version of the SIR method used for
analysis;
(c). the name and address
of the facility;
(d). a description
of the UST system;
(e). a
quantitative result of the leak threshold, the minimum detectable leak rate,
and the calculated leak rate for each UST system monitored;
(f). a qualitative statement of pass, fail,
or inconclusive for each UST system monitored; and
(g). any other information needed to verify
compliance with LAC 33:XI.703.A.2.c as applicable to the equipment and method
used. (Monthly raw data shall be provided to the department upon request.)
i. Other
Method. Any specific records required by the department upon approval of the
method, any records needed to demonstrate that the method meets the performance
requirements outlined in ALC 33:XI.701.A.8.a, and any other information needed
to verify compliance with LAC 33:XI.703.A.2.c as applicable to the equipment
and method used.
j. Line Leak
Detector (LLD)
i. LLD test results shall
include:
(a). the date of the test;
(b). the LLD identifier;
(c). a qualitative result
statement;
(d). a calculated leak
rate;
(e). a qualitative statement
regarding whether the submersible turbine pump is running continuously or
not;
(f). any other information
needed to verify compliance with LAC 33:XI.703.A.2.c as applicable to the
equipment and method used; and
(g).
raw data generated for each line LLD test shall be provided to the department
upon request.
k. Line Tightness Test (LTT)
i. LTT results shall include:
(a). the date of the test;
(b). the line identifier;
(c). a qualitative result
statement;
(d). a calculated leak
rate;
(e). any other information
needed to verify compliance with LAC 33:XI.703.A.2.c as applicable to the
equipment and method used; and
(f).
raw data generated for each LTT shall be provided to the department upon
request.
l.
Piping Interstitial Monitoring (IM)
i. Piping
IM records shall include:
(a). the date of the
test;
(b). the line
identifier;
(c). a qualitative
statement (i.e., pass or fail, liquid, product or water detected, sensor normal
message, dry space, alarm code when applicable, etc.);
(d). a qualitative result, when applicable;
and
(e). any other information
needed to verify compliance with LAC 33:XI.703.A.2.c as applicable to the
equipment and method used.
3. Written documentation of all calibration,
maintenance, and repair of release detection equipment used on-site shall be
maintained for at least three years after the servicing work is completed. Any
schedules of required calibration and maintenance provided by the manufacturer
of the release detection equipment shall be retained for five years from the
date of installation.
4. The
results of annual operation tests conducted in accordance with LAC
33:XI.703.A.2.d shall be maintained for at least three years. At a minimum, the
results shall list each component tested, the date each component was tested,
indicate whether each component tested meets the criteria in LAC
33:XI.703.A.2.d or needs to have action taken, and a description of any actions
taken to correct an issue.
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:2001 et seq.
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.