Current through Register Vol. 50, No. 9, September 20, 2024
A. Requirements for All UST Systems
1. Owners and operators of all UST systems
shall use a method, or combination of the methods, of release detection
described in LAC 33:XI.701.
2. The
method of release detection used shall also meet the following requirements.
a. The release detection method used shall be
capable of detecting a release from any portion of the tank and the connected
underground piping that routinely contains product.
b. The release detection system shall be
installed and calibrated in accordance with the manufacturer's
instructions.
c. The release
detection system shall meet the performance requirements in LAC 33:XI.701.A, B,
or LAC 33:XI.Chapter 8, as applicable, with any performance claims and their
manner of determination described in writing by the equipment manufacturer or
installer, or in accordance with the third party evaluations, unless otherwise
approved by the department. In addition, methods listed in LAC 33:XI.701.A.2,
3, 4, 7, and 8, LAC 33:XI.701.B.1 and 2, and LAC 33:XI.33.Chapter 8 shall be
capable of detecting the leak rate or quantity specified for that method in the
corresponding Section of LAC 33:XI.701 or LAC 33:XI.Chapter 8 with a
probability of detection of at least 0.95 and a probability of false alarm of
no greater than 0.05.
d. The
release detection system shall be operated and maintained in accordance with
the manufacturers instructions. Beginning September 20, 2021, the release
detection method used shall be operated and maintained, and electronic
components shall be tested for proper operation, in accordance with
manufacturers instructions, a code of practice developed by a nationally
recognized organization or independent testing laboratory listed in LAC
33:XI.599, or requirements developed by the department that are no less
protective of human health and the environment than the two options listed
above.
i. A test of the proper operation shall
be performed at least once every 12 months and, at a minimum, as applicable to
the facility, cover the components and criteria listed in LAC
33:XI.703.A.2.d.ii.(a).-(e).
ii.
The equipment listed below that fails testing shall be repaired or replaced
within 30 days of the failed test date:
(a).
automatic tank gauge and other controllers:
(i). test alarm;
(ii). verify configuration; and
(iii). test battery backup;
(b). probes and sensors:
(i). inspect for residual buildup;
(ii). ensure floats move freely;
(iii). ensure shaft is not damaged;
(iv). ensure cables are free of kinks and
breaks; and
(v). test alarm
operability and communication with the controller;
(c). automatic line leak detector: test
operation to meet criteria in LAC 33:XI.701.B.1;
(d). vacuum pumps and pressure gauges: ensure
proper communication with sensors and controller; and/or
(e). hand-held electronic sampling equipment
associated with groundwater and vapor monitoring: ensure proper
operation.
3. When a release detection method operated
in accordance with the performance standards in LAC 33:XI.701.A, B, or LAC
33:XI.Chapter 8 indicates that a release may have occurred, owners and
operators shall notify the Office of Environmental Assessment in accordance
with LAC 33:XI.707. If more than one method of release detection is conducted
on a UST system, and, if any one of these release detection methods indicates
that the release may have occurred which cannot be overruled by one of the
other methods currently in use, a suspected release shall be reported in
accordance with LAC 33:XI.707.
4.
The release detection method used shall provide a conclusive result at least
once every 30 days. When an inconclusive result is received, the UST owner or
operator shall either run another release detection test, where applicable, or
conduct an alternate method of release detection in order to obtain a
conclusive result for the 30 day monitoring period. If no alternate method of
release detection is available, the UST owner or operator may conduct a tank
and/or line tightness test in accordance with LAC 33:XI.701.A.3 and/or B.2
within seven days of the end of the 30 day monitoring period in order to
satisfy this requirement.
5. Any
UST system that cannot apply a method of release detection that complies with
the requirements of LAC 33:XI.701-705 shall complete the closure procedures in
LAC 33:XI.Chapter 9. For previously deferred UST systems described in LAC
33:XI.101 and LAC 33:XI.Chapter 8, this requirement is applicable after the
effective dates described in LAC 33:XI.101.A.1.b and LAC 33:XI.801.A.
B. Additional Requirements for
Petroleum and Motor Fuel UST Systems. In addition to the requirements specified
in LAC 33:XI.703.A, owners and operators of petroleum and motor fuel UST
systems shall provide release detection for tanks and piping as follows.
1. Tanks. Tanks shall be monitored for
releases as follows.
a. Tanks installed on or
before December 20, 2008, shall be monitored for releases at least once every
30 days using one of the methods listed in LAC 33:XI.701.A.3-8, except for the
following.
i. UST systems that meet the
performance standards in LAC 33:XI.303.D or E, and the monthly inventory
control requirements in LAC 33:XI.701.A.1 or 2, may use tank tightness testing
(conducted in accordance with LAC 33:XI.701.A.3) at least every 5 years until
10 years after the tank was installed. Inventory control and manual tank
gauging, conducted in accordance with LAC 33:XI.701.A.1 or 2, in conjunction
with tank tightness testing are no longer allowed as release detection methods
after December 20, 2018.
ii. Tanks
with a capacity of 550 gallons or less and tanks with a capacity of 551 to 1000
gallons that meet the tank diameter criteria in LAC 33:XI.701.A.2 may use
manual tank gauging (conducted in accordance with LAC 33:XI.701.A.2).
b. Tanks installed after December
20, 2008, or after the date of the extension granted under LAC 33:XI.303.C.2,
shall be monitored for releases at least once every 30 days in accordance with
LAC 33:XI.701.A.6.
2.
Piping. Underground piping that routinely contains regulated substances shall
be monitored for releases in a manner that meets one of the following
requirements.
a. Piping installed on or before
December 20, 2008, shall meet one of the following.
i. Pressurized Piping. Underground piping
that conveys regulated substances under pressure shall:
(a). be equipped with an automatic line leak
detector in accordance with LAC 33:XI.701.B.1; and
(b). have a line tightness test conducted
every 12 months in accordance with LAC 33:XI.701.B.2, or have monthly
monitoring conducted in accordance with LAC 33:XI.701.B.3.
ii. Suction Piping. Underground piping that
conveys regulated substances under suction shall either have a line tightness
test conducted at least every three years and in accordance with LAC
33:XI.701.B.2, or use a monthly monitoring method conducted in accordance with
LAC 33:XI.701.B.3. No release detection is required for suction piping designed
and constructed to meet the following standards:
(a). the below-grade piping operates at less
than atmospheric pressure;
(b). the
below-grade piping is sloped so that the contents of the pipe will drain back
into the storage tank if the suction is released;
(c). only one check valve is included in each
suction line;
(d). the check valve
is located directly below and as close as practical to the suction pump;
and
(e). a method is used that
allows compliance with Clauses B.2.b.ii-iv of this Section to be readily
determined and verified.
b. Piping installed or replaced after
December 20, 2008, or after the extension granted under LAC 33:XI.303.C.1 and
2, shall meet one of the following.
i.
Pressurized piping shall be monitored for releases at least once every 30 days
in accordance with LAC 33:XI.701.B.4 and be equipped with an automatic line
leak detector in accordance with LAC 33:XI.701.B.1.
ii. Suction piping shall be monitored for
releases at least once every 30 days in accordance with LAC 33:XI.701.B.4. No
release detection is required for suction piping that meets the requirements of
Subclauses a.ii.(a).-(e). of this Paragraph.
C. Additional Requirements for
Hazardous Substance UST Systems. In addition to the requirements of LAC
33:XI.703.A, owners and operators of hazardous substance UST systems shall
provide containment that meets the following requirements and monitor the tanks
for systems using LAC 33:XI.701.A.6 and the piping for systems using 701.B.4 at
least once every 30 days.
1. Secondary
containment systems shall be designed, constructed, and installed in accordance
with LAC 33:V.4437 to:
a. contain regulated
substances leaked from the primary containment until they are detected and
removed;
b. prevent the release of
regulated substances to the environment at any time during the operational life
of the UST system; and
c. be
checked for evidence of a release at least once every 30 days.
2. Double-walled tanks shall be
designed, constructed, and installed to:
a.
contain a release from any portion of the inner tank within the outer wall;
and
b. detect the failure of the
inner wall.
3. External
liners (including vaults) shall be designed, constructed, and installed to:
a. contain 100 percent of the capacity of the
largest tank within the boundary of the external liner;
b. prevent precipitation or groundwater
intrusion from interfering with the ability to contain or detect a release of
regulated substances; and
c.
surround the tank completely (i.e., the liner shall be capable of preventing
lateral as well as vertical migration of regulated substances).
4. Underground piping shall be
equipped with secondary containment that satisfies the requirements of this
Section (e.g., trench liners, jacketing of double-walled pipe). In addition,
underground piping that conveys regulated substances under pressure shall be
equipped with an automatic line leak detector, in accordance with LAC
33:XI.701.B.1.
5. For hazardous
substance UST systems installed on or before September 20, 2018, other methods
of release detection may be used if the owners and operators:
a. demonstrate to the department's
satisfaction that the alternate method can detect a release of the stored
substance as effectively as any of the methods allowed in LAC 33:XI.701.A.2-7
can detect a release of petroleum;
b. provide information to the department on
effective corrective action technologies, health risks, and chemical and
physical properties of the stored substance, and the characteristics of the UST
site; and
c. obtain approval from
the Office of Environmental Assessment to use the alternate release detection
method before the installation and operation of the new UST system.
AUTHORITY NOTE:
Promulgated in accordance with
R.S.
30:2001 et
seq.