Current through Register Vol. 50, No. 9, September 20, 2024
A.
Tanks. Each method of release detection for tanks used to meet the requirements
of LAC 33:XI.703.B shall be conducted in accordance with the following.
1. Inventory Control. Product inventory
control (or another test of equivalent performance) shall be conducted monthly
in a manner to ensure the detection of any release as small as 1.0 percent of
flow-through plus 130 gallons on a monthly basis in the following manner.
a. Inventory volume measurements for
regulated substance inputs, withdrawals, and the amount still remaining in the
tank shall be recorded each operating day.
b. The equipment used shall be capable of
measuring the level of product over the full range of the tank's height to the
nearest 1/8 of an inch.
c. Inputs
of regulated substances shall be reconciled with delivery receipts measuring
the tank inventory volume before and after delivery.
d. Deliveries shall be made through a drop
tube that extends to within 1 foot of the tank bottom.
e. Product dispensing shall be metered and
recorded within the local standards for meter calibration or an accuracy of 6
cubic inches for every 5 gallons of product withdrawn.
f. Measurements of any water level in the
bottom of the tank shall be made to the nearest 1/8 of an inch at least once a
month.
g. Practices described in
the American Petroleum Institute Publication 1621, "Recommended Practice for
Bulk Liquid Stock Control at Retail Outlets," may be used, where applicable, as
guidance in meeting the requirements of Paragraph A.1 of this
Section.
2. Manual Tank
Gauging. Tanks having a nominal capacity of 550 gallons or less and tanks
having a nominal capacity of 551 to 1,000 gallons that meet the tank diameter
criteria in the table in Subparagraph 2.d of this Subsection may use manual
tank gauging as the sole method of release detection. All other tanks with a
nominal capacity of 551-2,000 gallons may use this method in place of the
manual inventory control described in Paragraph 1 of this Subsection. Tanks
having a nominal capacity of greater than 2,000 gallons may not use this method
to meet the requirements of this Subsection. Manual tank gauging shall meet the
following requirements.
a. Tank liquid levels
shall be measured at the beginning and ending of a period using the appropriate
minimum duration of the test provided in the table in Paragraph 2.d of this
Section, during which no liquid is added to or removed from the tank. For the
purposes of Subparagraph d of this Paragraph, this constitutes one
test.
b. Liquid level measurements
shall be based on an average of two consecutive stick readings at both the
beginning and ending of the period.
c. The equipment used shall be capable of
measuring the level of product over the full range of the tank's height to the
nearest 1/8 of an inch.
d. A leak
shall be suspected and subject to the requirements of LAC 33:XI.707-713 if the
variation between beginning and ending measurements exceeds the weekly or
monthly standards in the following table.
Nominal Tank Capacity
|
Minimum
Duration of
Test
|
Weekly Standard (One Test)
|
Monthly Standard (Average of 4
Tests)
|
550 gallons or less
|
36 hours
|
10 gallons
|
5 gallons
|
551-1000 gallons (when tank diameter is 64
inches)
|
44 hours
|
9 gallons
|
4 gallons
|
551-1000 gallons (when tank diameter is 48
inches)
|
58 hours
|
12 gallons
|
6 gallons
|
551-1000 gallons (also requires periodic tank
tightness testing)
|
36 hours
|
13 gallons
|
7 gallons
|
1001-2000 gallons (also requires periodic tank
tightness testing)
|
36 hours
|
26 gallons
|
13 gallons
|
3. Tank Tightness Testing. Tank tightness
testing (or another test of equivalent performance) shall be capable of
detecting a 0.1-gallon-per-hour leak rate from any portion of the tank that
routinely contains product while accounting for the effects of thermal
expansion or contraction of the product, vapor pockets, tank deformation,
evaporation or condensation, and the location of the water table.
4. Automatic Tank Gauging (ATG)
a. Equipment for automatic tank gauging that
tests for the loss of product and conducts inventory control shall meet the
following requirements:
i. the automatic
product level monitor test shall be capable of detecting a 0.2-gallon-per-hour
leak rate from any portion of the tank that routinely contains
product;
ii. the automatic tank
gauging equipment shall meet the inventory control requirements of
Subparagraphs 1.b and 1.f of this Subsection (or another test of equivalent
performance); and
iii. the test
shall be performed with the system operating in one of the following modes:
(a). in-tank static testing conducted at
least once every 30 days; or
(b).
continuous in-tank leak detection operating on an uninterrupted basis or
operating within a process that allows the system to gather incremental
measurements to determine the leak status at least once every 30
days.
5. External Release Detection Devices
a. General. External release detection
devices (RDDs) consist of slotted (screened) piping installed within the
excavation zone to permit either the testing or monitoring of vapors or the
testing or monitoring for liquids on the water table. All RDDs shall meet the
following requirements.
i. All RDDs shall have
a 4-inch inside diameter and be constructed of either polyvinyl chloride (PVC),
polytetrafluoroethylene (PTFE), or stainless steel, and shall be chemically
compatible with the stored product. The screened interval shall be commercially
fabricated, slotted, or continuously wound. Screen size shall be 0.01 inches.
No solvents, glues, epoxies, thermal processes, or rivets shall be
used.
ii. The screened interval
shall extend from 1 foot beneath the ground surface through the entire
excavation zone.
iii. Each RDD
shall be sealed from the ground surface to a depth of 1 foot and provided with
a locking cap. Each RDD shall be installed in such a fashion as to preclude the
introduction of surface contaminants into the RDD.
iv. No RDD shall be installed within or
penetrate native soils unless the hydraulic conductivity of the native soil is
no less than 0.01 centimeters per second.
v. If only one UST system is located within
the excavation zone, at least two RDDs shall be installed. For excavation zones
containing between two and four UST systems, at least four RDDs shall be
installed. If more than four UST systems are situated within a common
excavation zone, additional RDDs shall be installed as appropriate to ensure
adequate coverage for release detection. If, prior to the implementation of
these regulations, fewer RDDs than required in this Clause were installed at a
specific location, the owner or operator may request a variance by
demonstrating to the satisfaction of the administrative authority that the
excavation zone in question can be adequately monitored.
vi. A UST owner or operator may request a
variance to the RDD construction requirements outlined above by demonstrating
to the department that the proposed deviations will allow the excavation zone
to be adequately monitored.
b. Vapor Monitoring. Testing or monitoring
for vapors within the soil gas of the excavation zone shall meet the following
requirements.
i. The materials used as
backfill shall be sufficiently porous (e.g., gravel, sand, crushed rock) to
readily allow diffusion of vapors from releases into the excavation
area.
ii. The stored regulated
substance, or a tracer compound placed in the tank system, shall be
sufficiently volatile (e.g., gasoline) to result in a vapor level detectable by
the monitoring devices located in the excavation zone in the event of a release
from the tank.
iii. The measurement
of vapors by the monitoring devices shall not be rendered inoperative by the
groundwater, rainfall, or soil moisture, or other known interferences, so that
a release could go undetected for more than 30 days.
iv. The level of background contamination in
the excavation zone shall not interfere with the method used to detect releases
from the tank.
v. The vapor
monitors shall be designed and operated to detect any significant increase in
concentration above background of the regulated substance stored in the tank
system, a component or components of that substance, or a tracer compound
placed in the tank system.
vi. In
the UST excavation zone, the site shall be assessed to ensure compliance with
the requirements in Clauses A.5.b.i-iv of this Section and to establish the
number and positioning of monitoring wells that will detect releases within the
excavation zone from any portion of the tank that routinely contains
product.
vii. Monitoring wells
shall be clearly marked and secured to avoid unauthorized access and
tampering.
c. Liquid
Monitoring. Testing or monitoring for liquids on the water table shall meet the
following requirements.
i. The regulated
substance stored shall be immiscible in water and have a specific gravity of
less than one.
ii. When an RDD is
installed in the tank hold backfill, there shall be water present in the RDD
during measurement at least once every 30 days in order to use liquid
monitoring. When an RDD is installed in native soil, the distance to the water
table shall never be more than 20 feet from the ground surface and shall be
present in the RDD during measurement at least once every 30 days, and the
hydraulic conductivity of the soil(s) between the UST system and the RDD shall
not be less than 0.01 centimeters per second (e.g., the soil should consist of
gravels, coarse-to-medium sands, coarse silts, or other permeable materials) in
order to use liquid monitoring.
iii. The slotted portion of the RDD shall be
designed to prevent migration of soils or the filter pack into the RDD and to
allow entry of the regulated substance on the water table into the RDD under
both high and low groundwater conditions.
iv. The continuous monitoring devices or
manual methods used shall be capable of detecting the presence of at least 1/8
of an inch of free product on top of the water within the RDD.
v. Within and immediately below the
excavation zone of the UST system, the site shall be assessed to ensure
compliance with the requirements in Clauses A.5.c.i-iii of this Section and to
establish the number and positioning of devices that will detect releases from
any portion of the tank that routinely contains product.
vi. RDD shall be clearly marked and secured
to avoid unauthorized access and tampering.
6. Interstitial Monitoring. Interstitial
monitoring between the UST system and a secondary barrier immediately around or
beneath it may be used, but only if the system is designed, constructed, and
installed to detect a leak from any portion of the tank that routinely contains
product and also meets one of the following requirements.
a. For double-walled UST systems, the
sampling or testing method used shall be capable of detecting a leak through
the inner wall in any portion of the tank that routinely contains product.
Interstitial monitoring of double-walled or jacketed tanks shall be conducted
either continuously by means of an automatic leak sensing device that signals
to the operator the presence of any liquid in the interstitial space, or
manually every 30 days by means of a procedure capable of detecting the
presence of any liquid in the interstitial space.
b. For UST systems with a secondary barrier
within the excavation zone, the sampling or testing method used shall be
capable of detecting a release between the UST system and the secondary
barrier, and the following criteria shall be met.
i. The secondary barrier around or beneath
the UST system consists of artificially constructed material that is
sufficiently thick and impermeable (at least 10-6
centimeters per second for the regulated substance stored) to direct a leak to
the monitoring point and permit its detection.
ii. The barrier is compatible with the
regulated substance stored so that a leak from the UST system will not cause
deterioration of the barrier that would allow a release to pass through
undetected.
iii. For cathodically
protected tanks, the secondary barrier is installed so that it does not
interfere with the proper operation of the cathodic protection
system.
iv. The groundwater, soil
moisture, or rainfall will not render the testing or sampling method used
inoperative so that a release could go undetected for more than 30
days.
v. The site is assessed to
ensure that the secondary barrier is always above the water table and not in a
25-year floodplain, unless the barrier and monitoring designs are for use under
such conditions.
vi. Monitoring
wells are clearly marked and secured to avoid unauthorized access and
tampering.
c. Tanks with
internally fitted liners shall be equipped with an automated device that can
detect a leak between the inner wall of the tank and the liner, and the liner
shall be compatible with the substance stored.
7. Statistical Inventory Reconciliation (SIR)
a. Release detection methods based on the
application of statistical principles to inventory data similar to those
described in LAC 33:XI.701.A.1 shall meet the following requirements:
i. report a quantitative result with a
calculated leak rate;
ii. be
capable of detecting a leak rate of 0.2 gallons per hour or a release of 150
gallons within 30 days; and
iii.
use a threshold that does not exceed one-half the minimum detectable leak
rate.
b. The UST system
owner or operator shall receive a report from the SIR provider/vendor/software
that performs the SIR analysis within the 30day monitoring period for which the
analysis was performed.
8. Other Methods. Any other type of release
detection method, or combination of methods, can be used if it meets the
following requirements.
a. The release
detection method can detect a 0.2-gallon-per-hour leak rate or a release of 150
gallons within 30 days with a probability of detection of at least 0.95 and a
probability of false alarm of no greater than 0.05.
b. The release detection method has been
approved by the Office of Environmental Assessment on the basis of a
demonstration by the owner and operator that the method can detect a release as
effectively as any of the methods allowed in Paragraphs 3-8 of this Subsection.
In comparing methods, the Office of Environmental Assessment shall consider the
size of release that the method can detect and the frequency and reliability
with which it can be detected. If the method is approved, the owner and
operator shall comply with any conditions imposed on its use by the Office of
Environmental Assessment.
B. Piping. Each method of release detection
for piping used to meet the requirements of LAC 33:XI.703.B shall be used in
accordance with the following.
1. Automatic
Line Leak Detectors. Methods that alert the operator to the presence of a leak
by restricting or shutting off the flow of regulated substances through piping
or by triggering an audible or visual alarm may be used only if they detect
leaks of 3 gallons per hour at 10 pounds per square inch line pressure within 1
hour. A test of the operation of the leak detector shall be conducted at least
once every 12 months in accordance with the following:
a. in accordance with the manufacturers
requirements;
b. by simulating a
release in order to determine if the system can detect leaks of 3 gallons per
hour at 10 pounds per square inch line pressure within 1 hour and is fully
operational; and
c. tested to
ensure that the submersible pump does not run continuously during normal
facility operation.
2.
Line Tightness Testing. Periodic testing of piping is acceptable only if such
testing can detect a 0.1 gallons per hour leak rate at 1.5 times normal
operating pressure.
3. Applicable
Tank Methods. Any of the methods in Paragraphs A.4-8 of this Section may be
used if they are designed to detect a release from any portion of the
underground piping that routinely contains regulated substances. Line tightness
testing conducted at normal operating pressure with an ATG and pressurized line
leak detectors, or with statistical inventory reconciliation must meet a 0.08
gallon-per-hour leak rate in order to qualify as an annual line tightness
test.
4. Interstitial Monitoring.
Interstitial monitoring of double-walled or jacketed piping shall be conducted
either continuously by means of an automatic leak sensing device that signals
to the operator the presence of any liquid in the interstitial space or sump,
or manually every 30 days by means of a procedure capable of detecting the
presence of any liquid in the interstitial space or sump.
a. The interstitial space or sump shall be
maintained free of water, debris, or anything that could interfere with leak
detection capabilities.
b.
Subparagraph a of this Paragraph applies only to containment sumps that are
used for interstitial monitoring of piping.
c. Sump sensors that are used for
interstitial monitoring of piping shall be installed at the lowest part of the
containment sump and in a vertical position, unless otherwise specified by the
sensor manufacturer.
AUTHORITY NOTE:
Promulgated in accordance with
R.S.
30:2001 et
seq.