D. All new UST systems shall comply with the
following standards.
1. Tanks. Each tank shall
be properly designed and constructed, and any portion underground that
routinely contains product shall be protected from corrosion in accordance with
Subsection A of this Section and as described below:
a. the tank is constructed of
fiberglass-reinforced plastic; or
b. the tank is constructed of metal and
cathodically protected in the following manner:
i. the tank is coated with a suitable
dielectric material;
ii.
field-installed cathodic protection systems are designed by a corrosion
expert;
iii. impressed current
systems are designed to allow determination of current operating status as
required in LAC 33:XI.503.A.3; and
iv. cathodic protection systems are operated
and maintained in accordance with LAC 33:XI.503 or according to guidelines
established by the department; or
c. the tank is constructed of steel and clad
or jacketed with a noncorrodible material; or
d. the tank is constructed of metal without
additional corrosion protection measures, provided that:
i. the tank is installed at a site that a
corrosion expert determines will not be corrosive enough to cause the tank to
have a release due to corrosion during its operating life; and
ii. owners and operators maintain records
that demonstrate compliance with the requirements of Clause D.1.d.i of this
Section for the remaining life of the tank; or
e. the tank construction and corrosion
protection are determined by the department to be designed to prevent the
release or threatened release of any stored regulated substance in a manner
that is no less protective of human health and the environment than the
constructions listed in Subparagraphs D.1.a-d and f of this Section;
and
f. for any UST system that is
installed or replaced after December 20, 2008, along with meeting the
requirements of Subparagraphs D.1.a-e of this Section, the tank employs
secondary containment, as defined in LAC 33:XI.103, as
follows:
i. it is an accepted UST design as
described in Subparagraphs D.1.a-e of this Section, is of double-walled or
jacketed construction in accordance with Subsection A of this Section, is
capable of containing a release from the inner wall of the tank, and is
designed with release detection in accordance with LAC 33:XI.701.A.6.a;
or
ii. it is some other
secondarily-contained tank system approved by the department in writing prior
to installation.
2. Piping. Piping on new UST systems that
routinely contains regulated substances and is in contact with the soil,
backfill, or water shall be properly designed, constructed, and protected from
corrosion in accordance with Subsection A of this Section and as described
below:
a. the piping is constructed of a
noncorrodible material; or
b. the
piping is constructed of metal and cathodically protected in the following
manner:
i. the piping is coated with a
suitable dielectric material;
ii.
field-installed cathodic protection systems are designed by a corrosion
expert;
iii. impressed current
systems are designed to allow determination of current operating status as
required in LAC 33:XI.503.A.3; and
iv. cathodic protection systems are operated
and maintained in accordance with LAC 33:XI.503 or guidelines established by
the department; or
c.
the piping is constructed of metal without additional corrosion protection
measures, provided that:
i. the piping is
installed at a site that a corrosion expert determines is not corrosive enough
to cause the piping to have a release due to corrosion during its operating
life; and
ii. owners and operators
maintain records that demonstrate compliance with the requirements of Clause
D.2.c.i of this Section for the remaining life of the piping; or
d. the piping construction and
corrosion protection are determined by the department to be designed to prevent
the release or threatened release of any stored regulated substance in a manner
that is no less protective of human health and the environment than the
requirements in Subparagraphs D.2.a-c, e, and f of this Section; or
e. the piping is of double-walled
non-metallic flexible or semi-rigid construction;
f. if piping connected to a UST is installed
or replaced after December 20, 2008, along with meeting the requirements of
Subparagraphs D.2.a-e of this Section, the piping employs
secondary
containment, as defined in LAC 33:XI.103, as follows:
i. any of the accepted piping designs listed
in Subparagraphs D.2.a-e of this Section shall be fabricated with double-walled
or jacketed construction in accordance with Subsection A of this Section, shall
be capable of containing a release from the inner wall of the piping, and shall
be designed with release detection in accordance with LAC 33:XI.701.B.4;
or
ii. the piping system shall have
some other form of secondary containment system approved by the department in
writing prior to installation; and
g. if 25 percent or more of the piping to any
one UST is replaced after December 20, 2008, the entire piping run shall comply
with Clause D.2.f.i or ii of this Section;
h. if a new dispenser is installed at an
existing UST facility and new piping is added to the UST system to connect the
new dispenser to the existing system after December 20, 2008, then the new
piping shall comply with Clause D.2.f.i or ii of this Section;
i. suction piping that meets the requirements
of LAC 33:XI.703.B.2.a.ii.(a)(e) and suction piping that manifolds two or more
tanks together are not required to meet the secondary containment requirements
of LAC 33:XI.303.D.2.f; and
j.
reuse of existing single-walled piping is prohibited when replacement
underground storage tanks are installed.
3. Spill and Overfill Prevention Equipment
a. Except as provided in Subparagraphs b and
c of this Paragraph, to prevent spilling and overfilling associated with
product transfer to the UST system, owners and operators shall use:
i. spill prevention equipment that will
prevent release of product to the environment when the transfer hose is
detached from the fill pipe (for example, a spill bucket). Spill buckets shall
have liquid-tight sides and bottoms and be maintained free of liquid and
debris; and
ii. overfill prevention
equipment that will:
(a). automatically shut
off flow into the tank when the tank is no more than 95 percent full;
(b). alert the transfer operator when the
tank is no more than 90 percent full by restricting the flow into the tank or
triggering a high-level alarm; or
(c). restrict flow 30 minutes prior to
overfilling, or alert the transfer operator with a high-level alarm one minute
before overfilling, or automatically shut off flow into the tank so that none
of the fittings on top of the tank are exposed to product because of
overfilling.
b. Owners and operators are not required to
use the spill and overfill prevention equipment specified in Subparagraph D.3.a
of this Section if:
i. alternative equipment
is used that the department determines is no less protective of human health
and the environment than the equipment specified in Clause D.3.a.i or ii of
this Section; or
ii. the UST system
is filled by transfers of no more than 25 gallons at one time.
c. Flow restrictors used in vent
lines shall not be used to comply with LAC 33:XI.303.D.3.a.ii when overfill
prevention is installed or replaced after September 20, 2018. If removal is
required, the entire ball float assembly shall be removed from the
tank.
d. Spill and overfill
prevention equipment shall be periodically tested or inspected in accordance
with LAC 33:XI.511.
4.
Under-Dispenser Secondary Containment. After December 20, 2008, under-dispenser
containment:
a. is required under the
following conditions:
i. in any installation
of a new dispenser at a new facility;
ii. in any installation of a new or
replacement dispenser at an existing facility where new piping is added to the
UST system to connect the new dispenser to the existing system;
iii. in any installation of a replacement
dispenser at an existing facility where the piping that connects the dispenser
to the existing piping is replaced, including replacing the metal flexible
connector, riser, or other transitional components that are beneath the
dispenser and the impact shear valve and that connect the dispenser to the
piping. Replacing an existing dispenser where no piping and none of the piping
that connects the dispenser to the existing piping are replaced does not
require the addition of an under-dispenser containment sump;
and
b. shall be
liquid-tight on its sides, bottom, and at any penetrations, and be maintained
free of storm water and debris. Regulated substances spilled into any
under-dispenser containment sump shall be immediately removed upon discovery to
the maximum extent practicable.
5. Submersible Turbine Pump (STP) Secondary
Containment. After December 20, 2008, secondary containment for submersible
pumps:
a. is required under the following
conditions:
i. in any installation of a new
STP at a new facility;
ii. in any
installation of an STP (the entire STP, STP housing, and riser pipe) at an
existing facility where new piping is added to the UST system to connect the
new STP to the existing system;
iii. in any installation of a replacement STP
(the entire STP, STP housing, and riser pipe) at an existing facility where the
piping that connects the STP to the existing piping is replaced. Replacing the
metal flexible connector with a single-walled flexible connector requires the
addition of a containment sump. Replacing the metal flexible connector with a
double-walled flexible connector does not require the addition of a containment
sump as long as the newly-installed STP is secondarily contained, and replacing
an existing STP where no piping is replaced does not require the addition of
STP secondary containment; and
b. can consist of either a built-in secondary
containment system or a STP containment sump. STP containment installed after
December 20, 2008, shall be liquid-tight on its sides, bottom, and at any
penetrations, and be maintained free of storm water and debris. Regulated
substances spilled into any STP containment sump shall be immediately removed
upon discovery to the maximum extent practicable.
6. Installation Procedures
a. Installation. The UST system, spill and
overfill prevention devices, product pumping equipment, and emergency shutoff
valves (e.g., shear or impact valves), shall be installed in accordance with
Subsection A of this Section and in accordance with the manufacturer's
instructions.
b. Certification of
Installation and Verification of Installer Certification
i. From July 20, 1990, through January 20,
1992, UST owners shall have certified installations as follows. All UST owners
shall have ensured that one or more of the following methods of certification,
testing, or inspection was used to demonstrate compliance with Subparagraph
D.6.a of this Section by providing a certification of compliance on the UST
registration form (UST-REG-02) in accordance with LAC 33:XI.301:
(a). the installer was certified by the tank
and piping manufacturers; or
(b).
the installation was inspected and certified by a professional engineer with
education and experience in UST system installation; or
(c). the installation was inspected and
approved by the department; or
(d).
all work listed in the manufacturer's installation checklists was completed;
or
(e). the UST owner complied with
another method for ensuring compliance with Subparagraph a of this Paragraph
that was determined by the department to be no less protective of human health
and the environment.
ii.
Beginning January 20, 1992 through September 20, 2018, all UST owners shall
have ensured that the individual exercising supervisory control over
installation critical-junctures (as defined in LAC 33:XI.1303)
of a UST system is certified in accordance with LAC 33:XI. Chapter 13. To
demonstrate compliance with Subparagraph D.6.a of this Section, all UST owners
shall have provided a certification of compliance on the UST registration of
technical requirements form (UST-REG-02) within 60 days of the introduction of
any regulated substance. Forms shall have been filed with the
department.
iii. After September
20, 2018, all UST owners shall ensure that the individual exercising
supervisory control over installation-critical junctures (as
defined in LAC 33:XI.1303) of a UST system is certified in accordance with LAC
33:XI.Chapter 13. To demonstrate compliance with Subparagraph a of this
Paragraph, all UST owners shall provide a certification of compliance on the
UST-REG form prior to introduction of any regulated substance into the UST
system. Forms shall be submitted to the Office of Management and
Finance.
c. Notification
of Installation. The UST owner shall notify the Office of Environmental
Assessment in writing at least 30 days before beginning installation of a UST
system by:
i. submitting a completed
installation, renovation, repair, and upgrade notification form
(UST-ENF-04);
ii. including in the
notification a statement of the number of active or abandoned water wells
within 50 feet of the UST system and the type of system to be installed;
and
iii. including in the
notification the methods to be used to comply with LAC 33:XI.Chapters 3 and
7.
d. The UST owner
and/or certified worker responsible for the installation-critical junctures
shall notify the appropriate regional office of the Office of Environmental
Assessment by phone, mail, email, fax, or online (when available) seven days
prior to commencing the installation and before commencing any
installation-critical juncture (as defined in LAC
33:XI.1303).