Louisiana Administrative Code
Title 33 - ENVIRONMENTAL QUALITY
Part XI - Underground Storage Tanks
Chapter 1 - Program Applicability and Definitions
Section XI-101 - Applicability
Universal Citation: LA Admin Code XI-101
Current through Register Vol. 50, No. 9, September 20, 2024
A. General. The requirements of these regulations apply to underground storage tank (UST) systems as defined in LAC 33:XI.103, except as otherwise provided in Subsections B and C of this Section.
1. Previously Deferred UST Systems. Airport
hydrant fuel distribution systems, UST systems with field-constructed tanks,
and UST systems that store fuel solely for use by emergency power generators
shall meet the requirements of LAC 33:XI as follows:
a. airport hydrant fuel distribution systems
and UST systems with field constructed tanks shall meet the requirements of LAC
33:XI.Chapter 8;
b. UST systems
that store fuel solely for use by emergency power generators installed before
August 9, 2009, shall meet the requirements of LAC 33:XI.701-705 on or before
September 20, 2021;
c. UST systems
that store fuel solely for use by emergency power generators installed on or
after August 9, 2009, are subject to all requirements of LAC 33:XI, including
the interstitial monitoring release detection requirements of LAC
33:XI.701-705.
B. Exclusions. The following UST systems are excluded from the requirements of these regulations. The owner or operator shall provide documentation upon request for any exclusion claimed.
1. Any UST system holding hazardous wastes
listed or identified in the Louisiana Department of Environmental Quality's
Hazardous Waste Regulations or a mixture of such hazardous waste and other
regulated substances is excluded from the requirements of these
regulations.
2. Any wastewater
treatment tank system that is part of a wastewater treatment facility regulated
under Section 402 of the Clean Water Act is excluded from the requirements of
these regulations.
3. Equipment or
machinery that contains regulated substances for operational purposes such as
hydraulic lift tanks and electrical equipment tanks is excluded from the
requirements of these regulations.
4. Any UST system whose capacity is 110
gallons or less is excluded from the requirements of these
regulations.
5. Any UST system that
contains or has never contained more than a de minimis
concentration, as determined by the department, of regulated substances is
excluded from the requirements of these regulations.
6. Any emergency spill or overflow
containment UST system that is expeditiously emptied after use is excluded from
the requirements of these regulations.
C. Partial Exclusions
1. The following categories of partially
excluded tanks are exempted from all of the requirements of LAC 33:XI except
for LAC 33:XI.305 and LAC 33:XI.715:
a.
wastewater treatment tank systems not covered under Paragraph B.2 of this
Section;
b. any UST systems
containing radioactive materials that are regulated under the Atomic Energy Act
of 1954 (42 U.S.C.
2011 et seq.);
c. any UST system that is part of an
emergency generator system at nuclear power generation facilities licensed by
the Nuclear Regulatory Commission and subject to Nuclear Regulatory Commission
requirements regarding design and quality criteria, including but not limited
to 10 CFR 50 ; and
d. aboveground
tanks associated with:
i. airport hydrant fuel
distribution systems regulated under LAC 33:XI. Chapter 8; and
ii. UST systems with field-constructed tanks
regulated under LAC 33:XI.Chapter 8.
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:2001 et seq.
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.