Current through Register Vol. 50, No. 9, September 20, 2024
A. In order to prevent the release of
hazardous waste or hazardous constituents to the environment, secondary
containment that meets the requirements of this Section must be provided
(except as provided in Subsections F and G of this Section):
1. for all new and existing tank systems or
components, prior to their being put into service;
2. for tank systems that store or treat
materials that become hazardous wastes, within two years of the hazardous waste
listing, or when the tank system has reached 15 years of age, whichever comes
later.
B. Secondary
containment systems must be:
1. designed,
installed, and operated to prevent any migration of wastes or accumulated
liquid out of the system to the soil, groundwater, or surface water at any time
during the use of the tank system; and
2. capable of detecting and collecting
releases and accumulated liquids until the collected material is
removed.
C. To meet the
requirements of Subsection B of this Section, secondary containment systems
must be at a minimum:
1. constructed of or
lined with materials that are compatible with the waste to be placed in the
tank systems and must have sufficient strength and thickness to prevent failure
due to pressure gradients (including static head and external hydrological
forces), physical contact with the waste to which they are exposed, climatic
conditions, the stress of installation, and the stress of daily operation
(including stresses from nearby vehicular traffic);
2. placed on a foundation or base capable of
providing support to the secondary containment systems and resistance to
pressure gradients above and below the system and capable of preventing failure
due to settlement, compression, or uplift;
3. provide with a leak detection system that
is designed and operated so that it will detect the failure of either the
primary and secondary containment structure or any release of hazardous waste
or accumulated liquid in the secondary containment system within 24 hours, or
at the earliest practicable time if the existing detection technology or site
conditions will not allow detection of a release within 24 hours;
4. sloped or otherwise designed or operated
to drain and remove liquids resulting from leaks, spills, or precipitation.
Spilled or leaked waste and accumulated precipitation must be removed from the
secondary containment system within 24 hours, or in as timely a manner as is
possible to prevent harm to human health or the environment, if removal of the
released waste or accumulated precipitation cannot be accomplished within 24
hours.
D. Secondary
containment for tanks must include one or more of the following devices:
1. a liner (external to the tank);
2. a vault;
3. a double-walled tank; or
4. an equivalent device as approved by the
administrative authority.
E. In addition to the requirements of
Subsections B-D of this Section, secondary containment systems must satisfy the
following requirements.
1. External liner
systems must be:
a. designed or operated to
contain 100 percent of the capacity of the largest tank within its
boundary;
b. designed or operated
to prevent run-on or infiltration of precipitation into the secondary
containment system unless the collection system has sufficient excess capacity
to contain run-on or infiltration. Such additional capacity must be sufficient
to contain precipitation from a 25-year, 24-hour rainfall event;
c. free of cracks or gaps;
d. designed and installed to completely
surround the tank and cover all surrounding earth likely to come into contact
with the waste if released from the tank(s);
e. impermeable to the extent that it will
prevent lateral as well as vertical migration of waste into the environment
(this is not intended to address releases to the air); and
f. if concrete is used as an external liner
system:
i. the liner system must be:
(a). provided with a coating or lining that
is compatible with the stored waste and meets the requirements of Subparagraph
E.1.d and e of this Section, except as specified in Clause E.1.f.ii and
Subsection J of this Section;
(b).
constructed with chemical-resistant water stops in place at all joints (if
any), in liner systems installed after June 20, 2010, and in liner systems
undergoing significant upgrade after June 20, 2010; and
(c). constructed with chemical-resistant
joint sealants at all joints and cracks (if any);
ii. the owner or operator of a tank equipped
with an uncoated/unlined concrete external liner system may demonstrate
compliance with Subclause E.1.f.i.(a) of this Section by submitting the
information described in Subsection J of this Section for review and obtaining
written approval by the Office of Environmental Services.
2. Vault systems must be:
a. designed or operated to contain 100
percent of the capacity of the largest tank within its boundary;
b. designed or operated to prevent run-on or
infiltration of precipitation into the secondary containment system unless the
collection system has sufficient excess capacity to contain run-on or
infiltration. Such additional capacity must be sufficient to contain
precipitation from a 25-year, 24-hour rainfall event;
c. constructed with chemical-resistant water
stops in place at all joints (if any);
d. constructed with chemical-resistant joint
sealants at all joints and cracks (if any), in vault systems installed after
June 20, 2010, and in vault systems undergoing significant upgrade after June
20, 2010;
e. provided with an
impermeable interior coating or lining that is compatible with the stored waste
and that will prevent migration of waste into the concrete;
f. provided with a means to protect against
the formation of and ignition of vapors within the vault, if the waste being
stored or treated:
i. meets any of the
definitions of ignitable waste under LAC 33:V.4903.B; or
ii. meets the definition of reactive waste
under LAC 33:V.4903.D, and may form an ignitable or explosive vapor;
and
g. provided with an
exterior moisture barrier or be otherwise designed or operated to prevent
migration of moisture into the vault if the vault is subject to hydraulic
pressure.
3.
Double-walled tanks must be:
a. designed as
an integral structure (i.e., an inner tank within an outer shell) so that any
release from the inner tank is contained by the outer shell;
b. protected, if constructed of metal, from
both corrosion of the primary tank interior and external surface of the outer
shell; and
c. provided with a
built-in, continuous leak detection system capable of detecting a release
within 24 hours or at the earliest practicable time, if the owner or operator
can demonstrate to the administrative authority and the administrative
authority concurs, that the existing leak detection technology or site
conditions will not allow detection of a release within 24 hours.
F. Ancillary equipment
must be provided with full secondary containment (e.g., trench, jacketing,
double-walled piping) that meets the requirements of Subsections B and C of
this Section, except for:
1. aboveground
piping (exclusive of flanges, joints, valves, and connections) that are
visually inspected for leaks on a daily basis;
2. welded flanges, welded joints, and welded
connections that are visually inspected for leaks on a daily basis;
3. sealless or magnetic coupling pumps and
sealless valves that are visually inspected for leaks on a daily basis;
and
4. pressurized aboveground
piping systems with automatic shut-off devices (e.g., excess flow check valves,
flow metering shutdown devices, loss of pressure actuated shut-off devices)
that are visually inspected for leaks on a daily basis.
G. The owner or operator may obtain a
variance from the requirements of this Section if the administrative authority
finds, as a result of a demonstration by the owner or operator, either that
alternative design and operating practices together with location
characteristics will prevent the migration of hazardous waste or hazardous
constituents into the groundwater or surface water at least as effectively as a
secondary containment during the active life of the tank system or that in the
event of a release that does migrate to groundwater or surface water, no
substantial present or potential hazard will be posed to human health or the
environment. New underground tank systems may not, per a demonstration in
accordance with this Subsection, be exempted from the secondary containment
requirements of this Section. Application for a variance as allowed in this
Subsection does not waive compliance with the requirements of this Chapter for
new tank systems.
1. In deciding whether to
grant a variance based on a demonstration of equivalent protection of
groundwater and surface water, the administrative authority will consider:
a. the nature and quantity of the
waste;
b. the proposed alternate
design and operation;
c. the
hydrogeologic setting of the facility, including the thickness of soils between
the tank system and groundwater; and
d. all other factors that would influence the
quality and mobility of the hazardous constituents and the potential for them
to migrate to groundwater or surface water.
2. In deciding whether to grant a variance,
based on a demonstration of no substantial present or potential hazard, the
administrative authority will consider:
a. the
potential adverse effects on groundwater, surface water, and land quality
taking into account:
i. the physical and
chemical characteristics of the waste in the tank system, including its
potential for migration;
ii. the
hydrogeological characteristics of the facility and surrounding land;
iii. the potential for health risks caused by
human exposure to waste constituents;
iv. the potential for damage to wildlife,
crops, vegetation, and physical structures caused by exposure to waste
constituents; and
v. the
persistence and permanence of the potential adverse effects;
b. the potential adverse effects
of a release on groundwater quality, taking into account:
i. the quantity and quality of groundwater
and the direction of groundwater flow;
ii. the proximity and withdrawal rates of
water in the area;
iii. the current
and future uses of groundwater in the area; and
iv. the existing quality of groundwater,
including other sources of contamination and their cumulative impact on the
groundwater quality;
c.
the potential adverse effects of a release on surface water quality, taking
into account:
i. the quantity and quality of
groundwater and the direction of groundwater flow;
ii. the patterns of rainfall in the
region;
iii. the proximity of the
tank system to surface waters;
iv.
the current and future uses of surface waters in the area and any water quality
standards established for those surface waters; and
v. the existing quality of surface water,
including other sources of contamination and the cumulative impact on surface
water quality; and
d.
the potential adverse effects of a release on the land surrounding the tank
system, taking into account:
i. the patterns
of rainfall in the region; and
ii.
the current and future uses of the surrounding land.
3. The owner or operator of a tank
system, for which a variance from secondary containment has been granted in
accordance with the requirements of Paragraph G.1 of this Section, at which a
release of a hazardous waste has occurred from the primary tank system but has
not migrated beyond the zone of engineering control (as established in the
variance), must:
a. comply with the
requirements of LAC 33:V.4441, except LAC 33:V.4441.D; and
b. decontaminate or remove contaminated soil
to the extent necessary to:
i. enable the
tank system, for which the variance was granted, to resume operation with the
capability for the detection of and response to releases at least equivalent to
the capability it had prior to the release; and
ii. prevent the migration of hazardous waste
or hazardous constituents to groundwater or surface water; or
c. if contaminated soil cannot be
removed or decontaminated in accordance with Subparagraph G.3.b of this
Section, comply with the requirements of LAC 33:V.1915.B.
4. The owner or operator of a tank system,
for which a variance from secondary containment had been granted in accordance
with the requirements of Paragraph G.1 of this Section, at which a release of
hazardous waste has occurred from the primary tank system and has migrated
beyond the zone of engineering control (as established in the variance), must:
a. comply with the requirements of LAC
33:V.4441.B-D; and
b. prevent the
migration of hazardous waste or hazardous constituents to groundwater or
surface water, if possible, and decontaminate or remove contaminated soil. If
contaminated soil cannot be decontaminated or removed, or if groundwater has
been contaminated, the owner or operator must comply with the requirements of
LAC 33:V.4442;
c. if repairing,
replacing, or reinstalling the tank system, provide secondary containment in
accordance with the requirements of Subsections A-F of this Section or reapply
for a variance from secondary containment and meet the requirements for new
tank systems in LAC 33:V.4435 if the tank system is replaced. The owner or
operator must comply with these requirements even if contaminated soil can be
decontaminated or removed, and groundwater or surface water has not been
contaminated.
H. The following procedures must be followed
in order to request a variance from secondary containment.
1. The Office of Environmental Services must
be notified in writing by the owner or operator that he intends to conduct and
submit a demonstration for a variance from secondary containment as allowed in
Subsection G of this Section according to the following schedule:
a. for existing tank systems, at least 24
months prior to the date that secondary containment must be provided in
accordance with Subsection A of this Section; and
b. for new tank systems, at least 30 days
prior to entering into a contract for installation of the tank
system.
2. As part of
the notification, the owner or operator must also submit to the Office of
Environmental Services a description of the steps necessary to conduct the
demonstration and a timetable for completing each of the steps. The
demonstration must address each of the factors listed in Paragraph G.1 or 2 of
this Section.
3. The demonstration
for a variance must be completed and submitted to the Office of Environmental
Services within 180 days after notifying the administrative authority of intent
to conduct the demonstration.
4.
The administrative authority will inform the public, through a newspaper
notice, of the availability of the demonstration for a variance. The notice
shall be placed in a daily or weekly major local newspaper of general
circulation and shall provide at least 30 days from the date of the notice for
the public to review and comment on the demonstration for a variance. The
administrative authority also will hold a public hearing, in response to a
request or at his own discretion, whenever such a hearing might clarify one or
more issues concerning the demonstration for a variance. Public notice of the
hearing will be given at least 30 days prior to the date of the hearing and may
be given at the same time as notice of the opportunity for the public to review
and comment on the demonstration. These two notices may be combined.
5. The administrative authority will approve
or disapprove the request for a variance within 90 days of receipt of the
demonstration from the owner or operator and will notify in writing the owner
or operator and each person who submitted written comments or requested notice
of the variance decision. If the demonstration for a variance is incomplete or
does not include sufficient information, the 90-day time period will begin when
the administrative authority receives a complete demonstration, including all
information necessary to make a final determination. If the public comment
period in Paragraph H.4 of this Section is extended, the 90-day time period
will be similarly extended.
I. All tank systems, until such time as
secondary containment meeting the requirements of this Section is provided,
must comply with the following.
1. For
non-enterable underground tanks, a leak test that meets the requirements of LAC
33:V.4433 must be conducted at least annually.
2. For other than non-enterable underground
tanks and for all ancillary equipment, an annual leak test, as described in
Paragraph I.1 of this Section, or an internal inspection or other tank
integrity examination by an independent, qualified professional engineer that
addresses cracks, leaks, corrosion, and erosion must be conducted at least
annually. The owner or operator must remove the stored waste from the tank, if
necessary, to allow the condition of all internal tank surfaces to be
assessed.
3. The owner or operator
must maintain on file at the facility a record of the results of the
assessments conducted in accordance with Paragraphs I.1-2 of this
Section.
4. If a tank system or
component is found to be leaking or unfit-for-use as a result of the leak test
or assessment in Paragraphs I.1-2 of this Section, the owner or operator must
comply with the requirements of LAC 33:V.4441.
J. Unlined/Uncoated Concrete Liner
Systems-Demonstration of Sufficiency Process
1. Submittals to the Office of Environmental
Services intended to secure its approval of uncoated/ unlined concrete liner
systems, as provided for in Clause E.1.f.ii of this Section, must contain
documentation regarding the information described below.
a. The owner or operator must provide
detailed information on the uncoated/unlined external liner, including, but not
limited to:
i. the design and installation
specifications for any concrete joints, including water stops;
ii. the characteristics of any joint sealant
used, including its compatibility with the waste stored in the tank system;
and
iii. the characteristics of the
concrete mix used, the design and construction specifications of the concrete
liner and secondary containment system, and any American Concrete Institute or
other applicable standards used.
b. The owner or operator must also provide
the following information:
i. the physical and
chemical characteristics of the waste in the tank system, including its
potential for migration and its compatibility with the unlined/uncoated
concrete external liner system;
ii.
the persistence and permanence of the potential adverse effects from a release
of the waste constituents to the environment;
iii. the risk to human health and the
environment posed by a potential release of the waste constituents contained in
the tank to the soil or groundwater;
iv. any factors that specifically influence
the potential mobility of the waste contained in the tank and its potential to
migrate through the unlined/uncoated concrete external liner system to the
environment;
v. any additional
protections afforded by the design and construction of the tank system; such as
tank liners, lined piping, welded flanges, double bottoms, and/or elevation of
the tank above the unlined/uncoated concrete external liner; and
vi. any other information requested by the
administrative authority.
2. The submittal may also contain other
documentation demonstrating that an unlined/uncoated concrete external liner
system is appropriate, such as documentation regarding the following:
a. any natural or man-made hydrogeological
characteristic of the facility and surrounding land that affords a barrier to
the migration of waste into the environment;
b. any applicable regulation or permit
requirement, or standard, such as, for example:
i. any schedule of more frequent than normal
internal inspection of the tank pursuant to appropriate standards (e.g.
American Petroleum Institute (API), American Society of Mechanical Engineers
(ASME), etc.);
ii. any schedule of
more frequent than normal external inspection of the tank pursuant to
appropriate standards (e.g. API, ASME, etc.);
iii. any certification by a registered
professional engineer regarding the permeability of the concrete that comprises
the concrete liner system; and
c. the cost of installing and maintaining an
impermeable coating or lining versus the potential benefits to be derived
therefrom.
3. In
deciding whether to approve the use of an unlined/uncoated concrete external
liner system in lieu of the requirements of Subclause E.1.f.i.(a) of this
Section:
a. the administrative authority
shall consider each submittal on its own merits;
b. the stringency of the administrative
authority's requirements may vary depending on the tank's contents (e.g., the
concentration or type of material involved); and
c. the administrative authority shall approve
the use of an unlined/uncoated concrete external liner system if it reasonably
determines that the unlined/uncoated concrete external liner system:
i. will prevent lateral and vertical
migration of waste into the environment; or
ii. is otherwise appropriate based on the
potential risk to human health and the environment.
4. Within 30 days after receipt of
an administratively complete submittal pursuant to this Subsection, the
department shall provide written acknowledgment to the owner or operator that
the submittal is under consideration. Subclause E.1.f.i.(a) of this Section
shall not apply to the concrete external liner system while the administrative
authority considers the owner's or operator's submittal. The administrative
authority shall notify the owner or operator in writing of the administrative
authority's approval or disapproval of the proposed use of an unlined/uncoated
concrete external liner system. If the administrative authority does not
approve the use of an unlined/uncoated concrete external liner system, it shall
give the owner or operator a reasonable period of time to provide an
appropriate coating or lining for the concrete external liner system, or
another acceptable means of secondary containment.
5. If the use of an unlined/uncoated concrete
external liner system is approved:
a. the
owner or operator shall maintain on-site:
i.
the written approval received from the administrative authority, or a legible
copy thereof; and
ii. documentation
sufficient to establish that any conditions upon which that approval was based
are being fulfilled; and
b. the owner or operator shall provide
written notification to the Office of Environmental Services of any change in
the tank system, the service of the tank system, the concrete external liner
system, the waste stored in the tank(s), or the information submitted by the
owner or operator pursuant to Paragraph 1 or 2 of this Subsection that could
result in a significant increase in the risk to human health or the environment
posed by a potential release of the waste constituents contained in the
tank(s). Such notice shall be provided within 15 days of the owner's or
operator's discovery of any such change. The department thereafter may require
the submittal of additional information by the owner or operator, and/or revoke
the approval for the owner's or operator's continued use of the
unlined/uncoated concrete external liner system.
AUTHORITY NOTE:
Promulgated in accordance with
R.S.
30:2180 et
seq.