Current through Register Vol. 50, No. 9, September 20, 2024
A. The
provisions of this Section apply to the control of air pollutant emissions from
tanks for which LAC 33:V.1751.B references the use of this Section for such air
emission control.
B. The owner or
operator shall control air pollutant emissions from each tank subject to this
Section in accordance with the following requirements, as applicable:
1. for a tank that manages hazardous waste
that meets all of the conditions specified in Subparagraphs B.1.a-c of this
Section, the owner or operator shall control air pollutant emissions from the
tank in accordance with the Tank Level 1 controls specified in Subsection C of
this Section or the Tank Level 2 controls specified in Subsection D of this
Section:
a. the hazardous waste in the tank
has a maximum organic vapor pressure that is less than the maximum organic
vapor pressure limit for the tank's design capacity category as follows:
i. for a tank design capacity equal to or
greater than 151 m3, the maximum organic vapor
pressure limit for the tank is 5.2 kPa;
ii. for a tank design capacity equal to or
greater than 75 m3, but less than 151
m3, the maximum organic vapor pressure limit for the
tank is 27.6 kPa;
iii. for a tank
design capacity less than 75 m3, the maximum organic
vapor pressure limit for the tank is 76.6 kPa;
b. the hazardous waste in the tank is not
heated by the owner or operator to a temperature that is greater than the
temperature at which the maximum organic vapor pressure of the hazardous waste
is determined for the purpose of complying with Subparagraph B.1.a of this
Section; and
c. the hazardous waste
in the tank is not treated by the owner or operator using a waste stabilization
process, as defined in LAC 33:V.4721; and
2. for a tank that manages hazardous waste
that does not meet all of the conditions specified in Subparagraphs B.1.a-c of
this Section, the owner or operator shall control air pollutant emissions from
the tank by using Tank Level 2 controls in accordance with the requirements of
Subsection D of this Section. Examples of tanks required to use Tank Level 2
controls include a tank used for a waste stabilization process and a tank for
which the hazardous waste in the tank has a maximum organic vapor pressure that
is equal to or greater than the maximum organic vapor pressure limit for the
tank's design capacity category as specified in Subparagraph B.1.a of this
Section.
C. Owners and
operators controlling air pollutant emissions from a tank using Tank Level 1
controls shall meet the requirements specified in Paragraphs C.1-4 of this
Section.
1. The owner or operator shall
determine the maximum organic vapor pressure for a hazardous waste to be
managed in the tank using Tank Level 1 controls before the first time the
hazardous waste is placed in the tank. The maximum organic vapor pressure shall
be determined using the procedures specified in LAC 33:V.1753.C. Thereafter,
the owner or operator shall perform a new determination whenever changes to the
hazardous waste managed in the tank could potentially cause the maximum organic
vapor pressure to increase to a level that is equal to or greater than the
maximum organic vapor pressure limit for the tank design capacity category
specified in Subparagraph B.1.a of this Section, as applicable to the
tank.
2. The tank shall be equipped
with a fixed roof designed to meet the following specifications.
a. The fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the hazardous waste in the tank. The fixed roof may be a separate cover
installed on the tank (e.g., a removable cover mounted on an open-top tank) or
may be an integral part of the tank structural design (e.g., a horizontal
cylindrical tank equipped with a hatch).
b. The fixed roof shall be installed in a
manner such that there are no visible cracks, holes, gaps, or other open spaces
between roof section joints or between the interface of the roof edge and the
tank wall.
c. Each opening in the
fixed roof, and any manifold system associated with the fixed roof, shall be
either:
i. equipped with a closure device
designed to operate such that when the closure device is secured in the closed
position there are no visible cracks, holes, gaps, or other open spaces in the
closure device or between the perimeter of the opening and the closure device;
or
ii. connected by a closed-vent
system that is vented to a control device. The control device shall remove or
destroy organics in the vent stream, and shall be operating whenever hazardous
waste is managed in the tank, except as follows:
(a). during periods when it is necessary to
provide access to the tank for performing the activities of Subclause
C.2.c.ii.(b) of this Section, venting of the vapor headspace underneath the
fixed roof to the control device is not required, opening of closure devices is
allowed, and removal of the fixed roof is allowed. Following completion of the
activity, the owner or operator shall promptly secure the closure device in the
closed position or reinstall the cover, as applicable, and resume operation of
the control device; or
(b). during
periods of routine inspection, maintenance, or other activities needed for
normal operations, and for removal of accumulated sludge or other residues from
the bottom of the tank.
d. The fixed roof and
its closure devices shall be made of suitable materials that will minimize
exposure of the hazardous waste to the atmosphere, to the extent practical, and
will maintain the integrity of the fixed roof and closure devices throughout
their intended service life. Factors to be considered when selecting the
materials for and designing the fixed roof and closure devices shall include
organic vapor permeability; the effects of any contact with the hazardous waste
or its vapors managed in the tank; the effects of outdoor exposure to wind,
moisture, and sunlight; and the operating practices used for the tank on which
the fixed roof is installed.
3. Whenever a hazardous waste is
in the tank, the fixed roof shall be installed with each closure device secured
in the closed position except as follows.
a.
Opening of closure devices or removal of the fixed roof is allowed at the
following times:
i. to provide access to the
tank for performing routine inspection, maintenance, or other activities needed
for normal operations. Examples of such activities include those times when a
worker needs to open a port to sample the liquid in the tank or when a worker
needs to open a hatch to maintain or repair equipment. Following completion of
the activity the owner or operator shall promptly secure the closure device in
the closed position or reinstall the cover, as applicable, to the
tank;
ii. to remove accumulated
sludge or other residues from the bottom of the tank.
b. Opening of a spring-loaded pressure-vacuum
relief valve, conservation vent, or similar type of pressure relief device that
vents to the atmosphere is allowed during normal operations for the purpose of
maintaining the tank internal pressure in accordance with the tank design
specifications. The device shall be designed to operate with no detectable
organic emissions when the device is secured in the closed position. The
settings at which the device opens shall be established such that the device
remains in the closed position whenever the tank internal pressure is within
the internal pressure operating range determined by the owner or operator based
on the tank manufacturer recommendations, applicable regulations, fire
protection and prevention codes, standard engineering codes and practices, or
other requirements for the safe handling of flammable, ignitable, explosive,
reactive, or hazardous materials. Examples of normal operating conditions that
may require these devices to open are during those times when the tank internal
pressure exceeds the internal pressure operating range for the tank as a result
of loading operations or diurnal ambient temperature fluctuations.
c. Opening of a safety device, as defined in
LAC 33:V.4721, is allowed at any time conditions require doing so to avoid an
unsafe condition.
4. The
owner or operator shall inspect the air emission control equipment in
accordance with the following requirements:
a. the fixed roof and its closure devices
shall be visually inspected by the owner or operator to check for defects that
could result in air pollutant emissions. Defects include, but are not limited
to, visible cracks, holes, or gaps in the roof sections or between the roof and
the tank wall; broken, cracked, or otherwise damaged seals or gaskets on
closure devices; and broken or missing hatches, access covers, caps, or other
closure devices;
b. the owner or
operator shall perform an initial inspection of the fixed roof and its closure
devices on or before the date that the tank becomes subject to this Section.
Thereafter, the owner or operator shall perform the inspections at least once
every year, except under the special conditions provided for in Subsection L of
this Section;
c. in the event that
a defect is detected, the owner or operator shall repair the defect in
accordance with the requirements of Subsection K of this Section; and
d. the owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in LAC
33:V.1765.B.
D. Owners and operators controlling air
pollutant emissions from a tank using Tank Level 2 controls shall use one of
the following tanks:
1. a fixed-roof tank
equipped with an internal floating roof in accordance with the requirements
specified in Subsection E of this Section;
2. a tank equipped with an external floating
roof in accordance with the requirements specified in Subsection F of this
Section;
3. a tank vented through a
closed-vent system to a control device in accordance with the requirements
specified in Subsection G of this Section;
4. a pressure tank designed and operated in
accordance with the requirements specified in Subsection H of this Section;
or
5. a tank located inside an
enclosure that is vented through a closed-vent system to an enclosed combustion
control device in accordance with the requirements specified in Subsection I of
this Section.
E. The
owner or operator who controls air pollutant emissions from a tank using a
fixed roof with an internal floating roof shall meet the requirements specified
in Paragraphs E.1-3 of this Section.
1. The
tank shall be equipped with a fixed roof and an internal floating roof in
accordance with the following requirements.
a. The internal floating roof shall be
designed to float on the liquid surface except when the floating roof must be
supported by the leg supports.
b.
The internal floating roof shall be equipped with a continuous seal between the
wall of the tank and the floating roof edge that meets either of the following
requirements:
i. a single continuous seal
that is either a liquid-mounted seal or a metallic shoe seal, as defined in LAC
33:V.4721; or
ii. two continuous
seals mounted one above the other. The lower seal may be a vapor-mounted
seal.
c. The internal
floating roof shall meet the following specifications:
i. each opening in a noncontact internal
floating roof, except for automatic bleeder vents (vacuum breaker vents) and
the rim space vents, is to provide a projection below the liquid
surface;
ii. each opening in the
internal floating roof shall be equipped with a gasketed cover or a gasketed
lid except for leg sleeves, automatic bleeder vents, rim space vents, column
wells, ladder wells, sample wells, and stub drains;
iii. each penetration of the internal
floating roof for the purpose of sampling shall have a slit fabric cover that
covers at least 90 percent of the opening;
iv. each automatic bleeder vent and rim space
vent shall be gasketed;
v. each
penetration of the internal floating roof that allows for passage of a ladder
shall have a gasketed sliding cover; and
vi. each penetration of the internal floating
roof that allows for passage of a column supporting the fixed roof shall have a
flexible fabric sleeve seal or a gasketed sliding cover.
2. The owner or operator shall
operate the tank in accordance with the following requirements:
a. when the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling shall be
continuous and shall be completed as soon as practical;
b. automatic bleeder vents are to be set
closed at all times when the roof is floating, except when the roof is being
floated off or is being landed on the leg supports; and
c. prior to filling the tank, each cover,
access hatch, gauge float well, or lid on any opening in the internal floating
roof shall be bolted or fastened closed (i.e., no visible gaps). Rim space
vents are to be set to open only when the internal floating roof is not
floating or when the pressure beneath the rim exceeds the manufacturer's
recommended setting.
3.
The owner or operator shall inspect the internal floating roof in accordance
with the procedures specified as follows:
a.
the floating roof and its closure devices shall be visually inspected by the
owner or operator to check for defects that could result in air pollutant
emissions. Defects include, but are not limited to, the internal floating roof
is not floating on the surface of the liquid inside the tank; liquid has
accumulated on top of the internal floating roof; any portion of the roof seals
have detached from the roof rim; holes, tears, or other openings are visible in
the seal fabric; the gaskets no longer close off the hazardous waste surface
from the atmosphere; or the slotted membrane has more than 10 percent open
area;
b. the owner or operator
shall inspect the internal floating roof components as follows, except as
provided in Subparagraph E.3.c of this Section:
i. visually inspect the internal floating
roof components through openings on the fixed-roof (e.g., manholes and roof
hatches) at least once every 12 months after initial fill; and
ii. visually inspect the internal floating
roof, primary seal, secondary seal (if one is in service), gaskets, slotted
membranes, and sleeve seals (if any) each time the tank is emptied and degassed
and at least every 10 years;
c. as an alternative to performing the
inspections specified in Subparagraph E.3.b of this Section for an internal
floating roof equipped with two continuous seals mounted one above the other,
the owner or operator may visually inspect the internal floating roof, primary
and secondary seals, gaskets, slotted membranes, and sleeve seals (if any) each
time the tank is emptied and degassed and at least every five years;
d. prior to each inspection required by
Subparagraph E.3.b or c of this Section, the owner or operator shall notify the
Office of Environmental Services in advance of each inspection to provide the
administrative authority with the opportunity to have an observer present
during the inspection. The owner or operator shall notify the administrative
authority of the date and location of the inspection as follows:
i. prior to each visual inspection of an
internal floating roof in a tank that has been emptied and degassed, written
notification shall be prepared and sent by the owner or operator so that it is
received by the administrative authority at least 30 calendar days before
refilling the tank except when an inspection is not planned as provided for in
Clause E.3.d.ii of this Section;
ii. when a visual inspection is not planned
and the owner or operator could not have known about the inspection 30 calendar
days before refilling the tank, the owner or operator shall notify the Office
of Environmental Services as soon as possible, but no later than seven calendar
days before refilling of the tank. This notification may be made by telephone
and immediately followed by a written explanation for why the inspection is
unplanned. Alternatively, written notification, including the explanation for
the unplanned inspection, may be sent so that it is received by the
administrative authority at least seven calendar days before refilling the
tank;
e. in the event
that a defect is detected, the owner or operator shall repair the defect in
accordance with the requirements of Subsection K of this Section; and
f. the owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in LAC
33:V.1765.B.
4. Safety
devices, as defined in LAC 33:V.4721, may be installed and operated as
necessary on any tank complying with the requirements of Subsection E of this
Section.
F. The owner or
operator who controls air pollutant emissions from a tank using an external
floating roof shall meet the requirements specified in Paragraphs F.1-3 of this
Section.
1. The owner or operator shall
design the external floating roof in accordance with the following
requirements:
a. the external floating roof
shall be designed to float on the liquid surface except when the floating roof
must be supported by the leg supports;
b. the floating roof shall be equipped with
two continuous seals, one above the other, between the wall of the tank and the
roof edge. The lower seal is referred to as the primary seal, and the upper
seal is referred to as the secondary seal:
i.
the primary seal shall be a liquid-mounted seal or a metallic shoe seal, as
defined in LAC 33:V.4721. The total area of the gaps between the tank wall and
the primary seal shall not exceed 212 square centimeters
(cm2) per meter of tank diameter, and the width of
any portion of these gaps shall not exceed 3.8 centimeters (cm). If a metallic
shoe seal is used for the primary seal, the metallic shoe seal shall be
designed so that one end extends into the liquid in the tank and the other end
extends a vertical distance of at least 61 centimeters above the liquid
surface; and
ii. the secondary seal
shall be mounted above the primary seal and cover the annular space between the
floating roof and the wall of the tank. The total area of the gaps between the
tank wall and the secondary seal shall not exceed 21.2 square centimeters
(cm2) per meter of tank diameter, and the width of
any portion of these gaps shall not exceed 1.3 centimeters (cm); and
c. the external floating roof
shall meet the following specifications:
i.
except for automatic bleeder vents (vacuum breaker vents) and rim space vents,
each opening in a noncontact external floating roof shall provide a projection
below the liquid surface;
ii.
except for automatic bleeder vents, rim space vents, roof drains, and leg
sleeves, each opening in the roof shall be equipped with a gasketed cover,
seal, or lid;
iii. each access
hatch and each gauge float well shall be equipped with a cover designed to be
bolted or fastened when the cover is secured in the closed position;
iv. each automatic bleeder vent and each rim
space vent shall be equipped with a gasket;
v. each roof drain that empties into the
liquid managed in the tank shall be equipped with a slotted membrane fabric
cover that covers at least 90 percent of the area of the opening;
vi. each unslotted and slotted guide pole
well shall be equipped with a gasketed sliding cover or a flexible fabric
sleeve seal;
vii. each unslotted
guide pole shall be equipped with a gasketed cap on the end of the
pole;
viii. each slotted guide pole
shall be equipped with a gasketed float or other device which closes off the
liquid surface from the atmosphere; and
ix. each gauge hatch and each sample well
shall be equipped with a gasketed cover.
2. The owner or operator shall operate the
tank in accordance with the following requirements:
a. when the floating roof is resting on the
leg supports, the process of filling, emptying, or refilling shall be
continuous and shall be completed as soon as practical;
b. except for automatic bleeder vents, rim
space vents, roof drains, and leg sleeves, each opening in the roof shall be
secured and maintained in a closed position at all times except when the
closure device must be open for access;
c. covers on each access hatch and each gauge
float well shall be bolted or fastened when secured in the closed
position;
d. automatic bleeder
vents shall be set closed at all times when the roof is floating, except when
the roof is being floated off or is being landed on the leg supports;
e. rim space vents shall be set to open only
at those times that the roof is being floated off the roof leg supports or when
the pressure beneath the rim seal exceeds the manufacturer's recommended
setting;
f. the cap on the end of
each unslotted guide pole shall be secured in the closed position at all times
except when measuring the level or collecting samples of the liquid in the
tank;
g. the cover on each gauge
hatch or sample well shall be secured in the closed position at all times
except when the hatch or well must be opened for access; and
h. both the primary seal and the secondary
seal shall completely cover the annular space between the external floating
roof and the wall of the tank in a continuous fashion except during
inspections.
3. The
owner or operator shall inspect the external floating roof in accordance with
the procedures specified as follows.
a. The
owner or operator shall measure the external floating roof seal gaps in
accordance with the following requirements:
i.
the owner or operator shall perform measurements of gaps between the tank wall
and the primary seal within 60 calendar days after initial operation of the
tank following installation of the floating roof and, thereafter, at least once
every five years;
ii. the owner or
operator shall perform measurements of gaps between the tank wall and the
secondary seal within 60 calendar days after initial operation of the tank
following installation of the floating roof and, thereafter, at least once
every year;
iii. if a tank ceases
to hold hazardous waste for a period of one year or more, subsequent
introduction of hazardous waste into the tank shall be considered an initial
operation for the purposes of Clauses F.3.a.i and ii of this Section;
iv. the owner or operator shall determine the
total surface area of gaps in the primary seal and in the secondary seal
individually using the following procedure:
(a). the seal gap measurements shall be
performed at one or more floating roof levels when the roof is floating off the
roof supports;
(b). seal gaps, if
any, shall be measured around the entire perimeter of the floating roof in each
place where a 0.32-centimeter (cm) diameter uniform probe passes freely
(without forcing or binding against the seal) between the seal and the wall of
the tank and measure the circumferential distance of each such
location;
(c). for a seal gap
measured under Paragraph F.3 of this Section, the gap surface area shall be
determined by using probes of various widths to measure accurately the actual
distance from the tank wall to the seal and multiplying each such width by its
respective circumferential distance;
(d). the total gap area shall be calculated
by adding the gap surface areas determined for each identified gap location for
the primary seal and the secondary seal individually, and then dividing the sum
for each seal type by the nominal diameter of the tank. These total gap areas
for the primary seal and secondary seal are then compared to the respective
standards for the seal type as specified in Subparagraph F.1.b of this
Section;
v. in the event
that the seal gap measurements do not conform to the specifications in
Subparagraph F.1.b of this Section, the owner or operator shall repair the
defect in accordance with the requirements of Subsection K of this Section;
and
vi. the owner or operator shall
maintain a record of the inspection in accordance with the requirements
specified in LAC 33:V.1765.B.
b. The owner or operator shall visually
inspect the external floating roof in accordance with the following
requirements:
i. the floating roof and its
closure devices shall be visually inspected by the owner or operator to check
for defects that could result in air pollutant emissions. Defects include, but
are not limited to, holes, tears, or other openings in the rim seal or seal
fabric of the floating roof; a rim seal detached from the floating roof; all or
a portion of the floating roof deck being submerged below the surface of the
liquid in the tank; broken, cracked, or otherwise damaged seals or gaskets on
closure devices; and broken or missing hatches, access covers, caps, or other
closure devices;
ii. the owner or
operator shall perform an initial inspection of the external floating roof and
its closure devices on or before the date that the tank becomes subject to this
Section. Thereafter, the owner or operator shall perform the inspections at
least once every year except for the special conditions provided for in
Subsection L of this Section;
iii.
in the event that a defect is detected, the owner or operator shall repair the
defect in accordance with the requirements of Subsection K of this Section;
and
iv. the owner or operator shall
maintain a record of the inspection in accordance with the requirements
specified in LAC 33:V.1765.B.
c. Prior to each inspection required by
Subparagraph F.3.a or F.3.b of this Section, the owner or operator shall notify
the Office of Environmental Services in advance of each inspection to provide
the administrative authority with the opportunity to have an observer present
during the inspection. The owner or operator shall notify the administrative
authority of the date and location of the inspection as follows:
i. prior to each inspection to measure
external floating roof seal gaps as required under Subparagraph F.3.a of this
Section, written notification shall be prepared and sent by the owner or
operator so that it is received by the administrative authority at least 30
calendar days before the date the measurements are scheduled to be
performed;
ii. prior to each visual
inspection of an external floating roof in a tank that has been emptied and
degassed, written notification shall be prepared and sent by the owner or
operator so that it is received by the administrative authority at least 30
calendar days before refilling the tank, except when an inspection is not
planned as provided for in Clause F.3.c.iii of this Section; and
iii. when a visual inspection is not planned
and the owner or operator could not have known about the inspection 30 calendar
days before refilling the tank, the owner or operator shall notify the
administrative authority as soon as possible, but no later than seven calendar
days before refilling of the tank. This notification may be made by telephone
and immediately followed by a written explanation stating why the inspection is
unplanned. Alternatively, written notification, including the explanation for
the unplanned inspection, may be sent so that it is received by the
administrative authority at least seven calendar days before refilling the
tank.
4.
Safety devices, as defined in LAC 33:V.4721, may be installed and operated as
necessary on any tank complying with the requirements of Subsection F of this
Section.
G. The owner or
operator who controls air pollutant emissions from a tank by venting the tank
to a control device shall meet the requirements specified in Paragraphs G.1-3
of this Section.
1. The tank shall be covered
by a fixed roof and vented directly through a closed-vent system to a control
device in accordance with the following requirements:
a. the fixed roof and its closure devices
shall be designed to form a continuous barrier over the entire surface area of
the liquid in the tank;
b. each
opening in the fixed roof not vented to the control device shall be equipped
with a closure device. If the pressure in the vapor headspace underneath the
fixed roof is less than atmospheric pressure when the control device is
operating, the closure devices shall be designed to operate such that when the
closure device is secured in the closed position there are no visible cracks,
holes, gaps, or other open spaces in the closure device or between the
perimeter of the cover opening and the closure device. If the pressure in the
vapor headspace underneath the fixed roof is equal to or greater than
atmospheric pressure when the control device is operating, the closure device
shall be designed to operate with no detectable organic emissions;
c. the fixed roof and its closure devices
shall be made of suitable materials that will minimize exposure of the
hazardous waste to the atmosphere, to the extent practical, and will maintain
the integrity of the fixed roof and closure devices throughout their intended
service life. Factors to be considered when selecting the materials for and
designing the fixed roof and closure devices shall include organic vapor
permeability; the effects of any contact with the liquid and its vapor managed
in the tank; the effects of outdoor exposure to wind, moisture, and sunlight;
and the operating practices used for the tank on which the fixed roof is
installed; and
d. the closed-vent
system and control device shall be designed and operated in accordance with the
requirements of LAC 33:V.1761.
2. Whenever a hazardous waste is in the tank,
the fixed roof shall be installed with each closure device secured in the
closed position and the vapor headspace underneath the fixed roof vented to the
control device except as follows.
a. Venting
to the control device is not required, and opening of closure devices or
removal of the fixed roof is allowed at the following times:
i. to provide access to the tank for
performing routine inspection, maintenance, or other activities needed for
normal operations. Examples of such activities include those times when a
worker needs to open a port to sample liquid in the tank or when a worker needs
to open a hatch to maintain or repair equipment. Following completion of the
activity, the owner or operator shall promptly secure the closure device in the
closed position or reinstall the cover, as applicable, to the tank;
and
ii. to remove accumulated
sludge or other residues from the bottom of a tank.
b. Opening of a safety device, as defined in
LAC 33:V.4721, is allowed at any time conditions require doing so to avoid an
unsafe condition.
3. The
owner or operator shall inspect and monitor the air emission control equipment
in accordance with the following procedures:
a. the fixed roof and its closure devices
shall be visually inspected by the owner or operator to check for defects that
could result in air pollutant emissions. Defects include, but are not limited
to, visible cracks, holes, or gaps in the roof sections or between the roof and
the tank wall; broken, cracked, or otherwise damaged seals or gaskets on
closure devices; and broken or missing hatches, access covers, caps, or other
closure devices;
b. the closed-vent
system and control device shall be inspected and monitored by the owner or
operator in accordance with the procedures specified in LAC
33:V.1761;
c. the owner or operator
shall perform an initial inspection of the air emission control equipment on or
before the date that the tank becomes subject to this Section. Thereafter, the
owner or operator shall perform the inspections at least once every year,
except for the special conditions provided for in Subsection L of this
Section;
d. in the event that a
defect is detected, the owner or operator shall repair the defect in accordance
with the requirements of Subsection K of this Section; and
e. the owner or operator shall maintain a
record of the inspection in accordance with the requirements specified in LAC
33:V.1765.B.
H. The owner or operator who controls air
pollutant emissions by using a pressure tank shall meet the following
requirements:
1. the tank shall be designed
not to vent to the atmosphere as a result of compression of the vapor headspace
in the tank during filling of the tank to its design capacity;
2. all tank openings shall be equipped with
closure devices designed to operate with no detectable organic emissions as
determined using the procedure specified in LAC 33:V.1753.D; and
3. whenever a hazardous waste is in the tank,
the tank shall be operated as a closed system that does not vent to the
atmosphere except under either of the following conditions as specified in
Subparagraphs H.3.a and b of this Section:
a.
at those times when opening of a safety device, as defined in LAC 33:V.1703, is
required to avoid an unsafe condition; or
b. at those times when purging of inerts from
the tank is required and the purge stream is routed to a closed-vent system and
control device designed and operated in accordance with the requirements of LAC
33:V.1761.
I.
The owner or operator who controls air pollutant emissions by using an
enclosure vented through a closed-vent system to an enclosed combustion control
device shall meet the requirements specified in Paragraphs I.1-4 of this
Section:
1. the tank shall be located inside
an enclosure. The enclosure shall be designed and operated in accordance with
the criteria for a permanent total enclosure as specified in Procedure
T-Criteria for and Verification of a Permanent or Temporary
Total Enclosure under
40
CFR 52.741, Appendix B. The enclosure may
have permanent or temporary openings to allow worker access; passage of
material into or out of the enclosure by conveyor, vehicles, or other
mechanical means; entry of permanent mechanical or electrical equipment; or
direct airflow into the enclosure. The owner or operator shall perform the
verification procedure for the enclosure as specified in Section 5.0 to
Procedure T-Criteria for and Verification of a
Permanent or Temporary Total Enclosure initially when the enclosure is
first installed and, thereafter, annually;
2. the enclosure shall be vented through a
closed-vent system to an enclosed combustion control device that is designed
and operated in accordance with the standards for either a vapor incinerator,
boiler, or process heater specified in LAC 33:V.1761;
3. safety devices, as defined in LAC
33:V.4721, may be installed and operated as necessary on any enclosure,
closed-vent system, or control device used to comply with the requirements of
Paragraphs I.1 and 2 of this Section; and
4. the owner or operator shall inspect and
monitor the closed-vent system and control device as specified in LAC
33:V.1761.
J. The owner
or operator shall transfer hazardous waste to a tank subject to this Section in
accordance with the following requirements:
1. transfer of hazardous waste, except as
provided in Paragraph J.2 of this Section, to the tank from another tank
subject to this Section or from a surface impoundment subject to LAC 33:V.1757
shall be conducted using continuous hard-piping or another closed system that
does not allow exposure of the hazardous waste to the atmosphere. For the
purpose of complying with this provision, an individual drain system is
considered to be a closed system when it meets the requirements of 40 CFR Part
63, Subpart RR-National Emission Standards for Individual Drain Systems;
and
2. the requirements of
Paragraph J.1 of this Section do not apply when transferring a hazardous waste
to the tank under any of the following conditions:
a. the hazardous waste meets the average VO
concentration conditions specified in LAC 33:V.1751.C.1 at the point of waste
origination;
b. the hazardous waste
has been treated by an organic destruction or removal process to meet the
requirements in LAC 33:V.1751.C.2; or
c. the hazardous waste meets the requirements
of LAC 33:V.1751.C.4.
K. The owner or operator shall repair each
defect detected during an inspection performed in accordance with the
requirements of Paragraph C.4, E.3, F.3, or G.3 of this Section as follows:
1. the owner or operator shall make first
efforts at repair of the defect no later than five calendar days after
detection, and repair shall be completed as soon as possible, but no later than
45 calendar days after detection, except as provided in Paragraph K.2 of this
Section; and
2. repair of a defect
may be delayed beyond 45 calendar days if the owner or operator determines that
repair of the defect requires emptying or temporary removal from service of the
tank and no alternative tank capacity is available at the site to accept the
hazardous waste normally managed in the tank. In this case, the owner or
operator shall repair the defect the next time the process or unit that is
generating the hazardous waste managed in the tank stops operation. Repair of
the defect shall be completed before the process or unit resumes
operation.
L. Following
the initial inspection and monitoring of the cover as required by the
applicable provisions of this Subchapter, subsequent inspection and monitoring
may be performed at intervals longer than one year under the following special
conditions:
1. in the case when inspecting or
monitoring the cover would expose a worker to dangerous, hazardous, or other
unsafe conditions, then the owner or operator may designate a cover as an
"unsafe to inspect and monitor cover" and comply with all of the following
requirements:
a. prepare a written
explanation for the cover stating the reasons why the cover is unsafe to
visually inspect or to monitor, if required; and
b. develop and implement a written plan and
schedule to inspect and monitor the cover, using the procedures specified in
the applicable Section of this Subchapter, as frequently as practicable during
those times when a worker can safely access the cover; and
2. in the case when a tank is buried
partially or entirely underground, an owner or operator is required to inspect
and monitor, as required by the applicable provisions of this Section, only
those portions of the tank cover and those connections to the tank (e.g., fill
ports, access hatches, gauge wells, etc.) that are located on or above the
ground surface.
AUTHORITY NOTE:
Promulgated in accordance with
R.S.
30:2180 et
seq.