Kentucky Administrative Regulations
Title 807 - ENERGY AND ENVIRONMENT CABINET PUBLIC SERVICE COMMISSION
Chapter 5 - Utilities
Section 807 KAR 5:066 - Water
Current through Register Vol. 50, No. 6, December 1, 2023
RELATES TO: KRS Chapter 278
NECESSITY, FUNCTION, AND CONFORMITY: KRS 278.280(2) provides that the Public Service Commission (hereinafter referred to as "commission") shall prescribe rules for the performance of any service or the furnishing of any commodity by the utility. This administrative regulation establishes general rules which apply to water utilities.
Section 1. Definitions.
Section 2. Information Available to Customers. A utility shall provide the following information to any customer upon request:
Section 3. Quality of Water.
Section 4. Continuity of Service.
Section 5. Pressures.
Section 6. Water Supply Measurement.
Section 7. Standards of Construction. Design and construction of the utility's facilities shall conform to good standard engineering practice. Plans and specifications for water supplies shall be prepared by an engineer registered in Kentucky, with the submitted plans bearing the engineer's seal. The utility's facilities shall be designed, constructed and operated so as to provide adequate and safe service to its customers and shall conform to requirements of the Natural Resources Cabinet with reference to sanitation and potability of water.
Section 8. Distribution Mains.
Section 9. Service Lines.
Section 10. Construction Requirements.
Circulating |
Noncirculating |
|
1 inch nominal size |
150 feet |
100 feet |
1 1/2 inch nominal size |
300 feet |
200 feet |
2 inch nominal size |
500 feet |
250 feet |
In the case of rural water lines, if hydraulic studies indicate they can comply with Section 5(1) of this administrative regulation and can provide adequate flow of water to serve the peak requirements of customers, the above maximum extension lengths may be extended with approval of the commission.
Section 11. Extension of Service.
Section 12. Service Connections.
Section 13. Measurement of Service.
Section 14. Meter Test Facilities and Equipment.
Section 15. Accuracy Requirements of Water Meters.
TEST REQUIREMENTS FOR NEW, REBUILT, AND REPAIRED COLD WATER METERS* |
|||||||||||||
Maximum Rate (All Meters) |
Intermediate Rates (All Meters) |
Minimum Rate (New and Rebuilt) |
Minimum (Repaired ) |
||||||||||
Size in. |
Flow Rate gpm |
Test Quantity |
Accuracy Limits % |
Flow Rate gpm |
Test Quantity |
Accuracy Limits % |
Flow Rate gpm |
Test Quantity |
Accuracy Limits Percent |
Accuracy Limits % (min.) |
|||
gal |
ft3 |
gal |
ft3 |
gal |
ft3 |
||||||||
Displacement Meters |
|||||||||||||
5/8 |
15 |
100 |
10 |
98.5-101.5 |
2 |
10 |
1 |
98.5-101.5 |
1/4 |
10 |
1 |
95-101 |
90 |
5/8 x 3/4 |
15 |
100 |
10 |
98.5-101.5 |
2 |
10 |
1 |
98.5-101.5 |
1/4 |
10 |
1 |
95-101 |
90 |
3/4 |
25 |
100 |
10 |
98.5-101.5 |
3 |
10 |
1 |
98.5-101.5 |
1/2 |
10 |
1 |
95-101 |
90 |
1 |
40 |
100 |
10 |
98.5-101.5 |
4 |
10 |
1 |
98.5-101.5 |
3/4 |
10 |
1 |
95-101 |
90 |
1 1/2 |
50 |
100 |
10 |
98.5-101.5 |
8 |
100 |
10 |
98.5-101.5 |
11/2 |
100 |
10 |
95-101 |
90 |
2 |
100 |
100 |
10 |
98.5-101.5 |
15 |
100 |
10 |
98.5-101.5 |
2 |
100 |
10 |
95-101 |
90 |
3 |
150 |
500 |
50 |
98.5-101.5 |
20 |
100 |
10 |
98.5-101.5 |
4 |
100 |
10 |
95-101 |
90 |
4 |
200 |
500 |
50 |
98.5-101.5 |
40 |
100 |
10 |
98.5-101.5 |
7 |
100 |
10 |
95-101 |
90 |
6 |
500 |
1000 |
100 |
98.5-101.5 |
60 |
100 |
10 |
98.5-101.5 |
12 |
100 |
10 |
95-101 |
90 |
Multijet Meters |
|||||||||||||
5/8 |
15 |
100 |
10 |
98.5-101.5 |
1 |
10 |
1 |
98.5-101.5 |
1/4 |
10 |
1 |
97-103 |
90 |
5/8 x 3/4 |
15 |
100 |
10 |
98.5-101.5 |
1 |
10 |
1 |
98.5-101.5 |
1/4 |
10 |
1 |
97-103 |
90 |
3/4 |
25 |
100 |
10 |
98.5-101.5 |
2 |
10 |
1 |
98.5-101.5 |
1/2 |
10 |
1 |
97-103 |
90 |
1 |
35 |
100 |
10 |
98.5-101.5 |
3 |
10 |
1 |
98.5-101.5 |
3/4 |
10 |
1 |
97-103 |
90 |
1 1/2 |
70 |
100 |
10 |
98.5-101.5 |
5 |
100 |
10 |
98.5-101.5 |
11/2 |
100 |
10 |
97-103 |
90 |
2 |
100 |
100 |
10 |
98.5-101.5 |
8 |
100 |
10 |
98.5-101.5 |
2 |
100 |
10 |
97-103 |
90 |
Class I Turbine Meters |
|||||||||||||
1 1/2 |
80 |
200 |
20 |
98-102 |
Not Required |
12 |
100 |
10 |
98-102 |
- |
|||
2 |
120 |
300 |
30 |
98-102 |
16 |
100 |
10 |
98-102 |
- |
||||
3 |
250 |
500 |
50 |
98-102 |
24 |
100 |
10 |
98-102 |
- |
||||
4 |
400 |
1000 |
100 |
98-102 |
40 |
100 |
10 |
98-102 |
- |
||||
6 |
1000 |
2000 |
200 |
98-102 |
80 |
1000 |
100 |
98-102 |
- |
||||
8 |
1500 |
3000 |
300 |
98-102 |
140 |
1000 |
100 |
98-102 |
- |
||||
10 |
2200 |
5000 |
500 |
98-102 |
225 |
1000 |
100 |
98-102 |
- |
||||
12 |
3300 |
7000 |
700 |
98-102 |
400 |
1000 |
100 |
98-102 |
- |
||||
Class II Turbine Meters |
|||||||||||||
2 |
120 |
300 |
30 |
98.5-101.5 |
Not Required |
4 |
100 |
10 |
98.5-101.5 |
- |
|||
3 |
275 |
600 |
60 |
98.5-101.5 |
8 |
100 |
10 |
98.5-101.5 |
- |
||||
4 |
500 |
1000 |
100 |
98.5-101.5 |
15 |
100 |
10 |
98.5-101.5 |
- |
||||
6 |
1100 |
2500 |
250 |
98.5-101.5 |
30 |
1000 |
100 |
98.5-101.5 |
- |
||||
8 |
1800 |
4000 |
400 |
98.5-101.5 |
50 |
1000 |
100 |
98.5-101.5 |
- |
||||
10 |
3000 |
6000 |
600 |
98.5-101.5 |
75 |
1000 |
100 |
98.5-101.5 |
- |
||||
12 |
4000 |
8000 |
800 |
98.5-101.5 |
120 |
1000 |
100 |
98.5-101.5 |
- |
||||
Propeller Meters |
|||||||||||||
2 |
100 |
200 |
20 |
98-102 |
35 |
100 |
10 |
98-102 |
30 |
100 |
10 |
95 |
90 |
3 |
150 |
300 |
30 |
98-102 |
40 |
100 |
10 |
98-102 |
35 |
100 |
10 |
95 |
90 |
4 |
200 |
500 |
60 |
98-102 |
50 |
100 |
10 |
98-102 |
45 |
100 |
10 |
95 |
90 |
5 |
400 |
100 0 |
100 |
98-102 |
75 |
200 |
20 |
98-102 |
70 |
200 |
20 |
95 |
90 |
6 |
500 |
1000 |
100 |
98-102 |
90 |
300 |
30 |
98-102 |
85 |
300 |
30 |
95 |
90 |
8 |
600 |
2000 |
200 |
98-102 |
100 |
300 |
30 |
98-102 |
90 |
300 |
30 |
95 |
90 |
10 |
900 |
3000 |
300 |
98-102 |
125 |
300 |
30 |
98-102 |
110 |
300 |
30 |
95 |
90 |
12 |
1000 |
5000 |
500 |
98-102 |
150 |
400 |
50 |
98-102 |
140 |
400 |
50 |
95 |
90 |
14 |
1100 |
5000 |
500 |
98-102 |
250 |
1000 |
100 |
98-102 |
225 |
1000 |
100 |
95 |
90 |
16 |
1400 |
5000 |
600 |
98-102 |
350 |
1000 |
100 |
98-102 |
315 |
1000 |
100 |
95 |
90 |
18 |
1600 |
5000 |
600 |
98-102 |
450 |
2000 |
200 |
98-102 |
405 |
2000 |
200 |
95 |
90 |
20 |
2000 |
10000 |
1000 |
98-102 |
550 |
2000 |
200 |
98-102 |
495 |
2000 |
200 |
95 |
90 |
24 |
3000 |
10000 |
1000 |
98-102 |
800 |
5000 |
500 |
98-102 |
720 |
5000 |
500 |
95 |
90 |
30 |
4500 |
20000 |
2000 |
98-102 |
1200 |
5000 |
500 |
98-102 |
1080 |
5000 |
500 |
95 |
90 |
36 |
6000 |
20000 |
2000 |
98-102 |
1500 |
5000 |
500 |
98-102 |
1350 |
5000 |
500 |
95 |
90 |
Compound Meters |
|||||||||||||
2 |
100 |
100 |
10 |
97-103 |
sec. |
100 |
10 |
90-103 |
- |
||||
3 |
150 |
500 |
50 |
97-103 |
100 |
10 |
90-103 |
- |
|||||
4 |
200 |
500 |
50 |
97-103 |
100 |
10 |
90-103 |
- |
|||||
6 |
500 |
1000 |
100 |
97-103 |
100 |
10 |
90-103 |
- |
|||||
8 |
600 |
2000 |
200 |
97-103 |
200 |
20 |
90-103 |
- |
|||||
10 |
900 |
2000 |
200 |
97-103 |
1000 |
100 |
90-103 |
- |
|||||
Fire-Service Type |
|||||||||||||
3 |
100 |
500 |
50 |
97-103 |
sec. |
sec . |
Not Less |
- |
|||||
4 |
200 |
500 |
100 |
97-103 |
than 85% |
- |
|||||||
6 |
500 |
3000 |
200 |
97-103 |
- |
||||||||
8 |
600 |
3000 |
300 |
97-103 |
- |
||||||||
10 |
900 |
5000 |
500 |
97-103 |
- |
* - A rebuilt meter is one that has had the measuring element replaced with a factory-made new unit.
A repaired meter is one that has had the old measuring element cleaned and refurbished in a utility repair shop.
sec. - Quantity should be one or more full revolution of the test hand but not less than two (2) min running.
Section 16. Periodic Tests.
Size of Meter Inches |
Interval Between Tests Years |
5/8 |
10 |
5/8 x 3/4 |
10 |
3/4 |
10 |
1 |
10 |
1 1/4 |
4 |
1 1/2 |
4 |
2 |
4 |
3 |
2 |
4 and larger |
1 |
Section 17. Water Shortage Response Plans. Each utility which files a water shortage response plan with the Natural Resources Cabinet shall simultaneously file a copy of the plan with the commission. Any utility which has already filed a plan with the Natural Resources Cabinet shall file the plan with the commission within sixty (60) days of the effective date of this administrative regulation.
Section 18. Deviations from Administrative Regulation. In special cases, for good cause shown, the commission may permit deviations from this administrative regulation.
8 Ky.R. 828; eff. 4-7-1982; 18 Ky.R. 1968; 3388; eff. 6-7-1992; TAm eff. 8-9-2007; TAm 1-30-2013; Crt eff. 3-27-2019.
STATUTORY AUTHORITY: KRS 278.280(2)