Kansas Administrative Regulations
Agency 5 - DEPARTMENT OF AGRICULTURE-DIVISION OF WATER RESOURCES
Article 40 - DESIGN OF EARTH DAMS
Section 5-40-53 - Drawdown pipes

Universal Citation: KS Admin Regs 5-40-53

Current through Register Vol. 43, No. 12, March 20, 2024

(a) Except as specified in subsection (b), each dam shall be equipped with a drawdown pipe that meets the requirements for a pipe as specified in K.A.R. 5-40-50. A valve or gate shall be installed in the pipe so that the controls are accessible and damage from freezing is prevented. Drawdown pipes may be incorporated into the primary spillway.

(b) The installation of a drawdown pipe shall not be required for a low-impact dam if the chief engineer determines that both of the following criteria are met:

(1) The failure to install a drawdown pipe will not prejudicially and unreasonably affect the public interest and the public safety.

(2) The drawdown pipe is not necessary to administer water rights.

(c) Each drawdown pipe shall have the capacity to evacuate 90 percent of the volume of the permanent pool in 14 or fewer days assuming no inflow into the reservoir, but in no case shall the drawdown pipe have an internal diameter of less than four inches. The inlet of the drawdown pipe shall be constructed to reduce the likelihood of plugging.

Disclaimer: These regulations may not be the most recent version. Kansas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.