Kansas Administrative Regulations
Agency 5 - DEPARTMENT OF AGRICULTURE-DIVISION OF WATER RESOURCES
Article 1 - DEFINITIONS
Section 5-1-9 - Criteria to determine when a water flow-meter is out of compliance

Universal Citation: KS Admin Regs 5-1-9

Current through Register Vol. 43, No. 12, March 20, 2024

(a) A water flowmeter shall be considered to be out of compliance if any of the following criteria is met:

(1) The water flowmeter registers less than 94 percent or more than 106 percent of the actual volume of water passing the water flowmeter. If necessary, this determination may be made by a field test conducted by, or approved by, the chief engineer.

(2) The seal placed on the totalizer by the manufacturer or the manufacturer's authorized representative has been broken, or the totalizer value has been reset or altered without the authorization of the manufacturer, an authorized representative of the manufacturer, or the chief engineer.

(3) A seal placed on the water flowmeter or totalizer by the chief engineer has been broken.

(4) The water flowmeter register is not visible or is unreadable for any reason.

(5) There is not full pipe flow through the water flow-meter.

(6) Flow-straightening vanes have not been properly designed, manufactured, and installed.

(7) The water flowmeter is not calibrated for the nominal size of the pipe in which the flowmeter is installed.

(8) The water flowmeter is not installed in accordance with the manufacturer's installation specifications. However, five diameters of straight pipe above the water flow-meter sensor and two diameters below the water flow-meter sensor shall be the minimum spacing, regardless of the manufacturer's installation specifications.

(9) A water flowmeter is installed at a location at which the flowmeter does not measure all of the water diverted from the source of supply.

(b) A water flowmeter installed in the diversion works or a distribution system for a water right authorized for municipal use shall not be subject to the requirements of paragraphs (a)(2) and (3) if an accurate record of water use can be determined by readings from at least one alternate water flowmeter in the same diversion works or distribution system.

Disclaimer: These regulations may not be the most recent version. Kansas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.