Kansas Administrative Regulations
Agency 49 - DEPARTMENT OF LABOR
Article 51 - HIGH PRESSURE BOILERS
Section 49-51-9 - Steam gauges

Universal Citation: KS Admin Regs 49-51-9

Current through Register Vol. 43, No. 12, March 20, 2024

(a) Each steam boiler shall have a steam gauge with dial range not less than 1 1/2 or more than 3 1/2 times the maximum allowable working pressure connected to the steam space or to the steam connection to the water column. The steam gauge shall be connected to a siphon or equivalent device of sufficient capacity to keep the gauge tube filled with water. The steam gauge shall be arranged so that the gauge cannot be shut off from the boiler except by a cock placed near the gauge. The cock shall be provided with a tee or lever handle arranged to be parallel to the pipe in which it is located when the cock is open.

(b) When a steam gauge connection longer than eight feet becomes necessary, a shut-off valve may be used near the boiler if the valve is the outside-screw-and-yoke type and is locked open. The line shall be of ample size with provision for free blowing.

(c) Each boiler shall be provided with a 1/2-inch nipple and globe valve connected to the steam space for the exclusive purpose of attaching a test gauge when the boiler is in service so that the accuracy of the boiler steam gauge may be ascertained.

Disclaimer: These regulations may not be the most recent version. Kansas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.