Kansas Administrative Regulations
Agency 49 - DEPARTMENT OF LABOR
Article 51 - HIGH PRESSURE BOILERS
Section 49-51-8 - Water level indicators

Universal Citation: KS Admin Regs 49-51-8

Current through Register Vol. 43, No. 12, March 20, 2024

(a) No outlet connections, except for any damper regulator, feedwater regulator, low water fuel cutout, drain, gauge, or other apparatus that does not permit the escape of an appreciable amount of steam or water from it, shall be placed on the piping that connects the water column to the boiler. The water column shall be provided with a valved drain of at least 3/4 inch pipe size. The discharge shall be piped to a safe location.

(b) For all installations in which the water gauge glass or glasses are more than 30 feet above the boiler operating floor, remote water level indicating or recording gauges shall be installed at eye height above the operating floor.

Disclaimer: These regulations may not be the most recent version. Kansas may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.