Current through Register Vol. 47, No. 6, September 18, 2024
A spa constructed or reconstructed after May 4, 2005, shall
comply with the following standards. Nothing in these rules is intended to
exempt spas and associated structures from any applicable federal, state or
local laws, rules or ordinances. Applicable requirements include, but are not
limited to, the handicapped access and energy requirements of the state
building code, the fire and life safety requirements of the state fire marshal,
the rules of the department of workforce development, and the rules of the
department of natural resources.
(1)
Construction permits.
a.
Permit required. No spa shall be constructed or reconstructed
without the owner or a designated representative of the owner first receiving a
permit from the department. Construction shall be completed within 24 months
from the date the construction permit is issued unless a written extension is
granted by the department.
b.
Permit application. The owner of a proposed or existing spa or
a designated representative of the owner shall apply for a construction permit
on forms provided by the department. The application shall be submitted to the
department at least 15 days prior to construction of a new spa or the
reconstruction of a spa.
c.
Plan submission. Three sets of plans and specifications shall
be submitted with the application. A nonrefundable plan review fee shall be
remitted with the application for each spa as required in 15.12(4).
d.
Notification of
completion. The owner of a newly constructed or reconstructed facility
or the owner's designated representative shall notify the department in writing
at least 15 business days prior to opening the spa.
(2)
Plans and
specifications.
a.
Plan
certification. Plans and specifications shall be sealed and certified
in accordance with the rules of the engineering and land surveying examining
board or the architectural examining board by an engineer or architect licensed
to practice in Iowa.
(1) This requirement may
be waived by the department if the project is the addition or replacement of a
chemical feed system, including a disinfection system, or a simple replacement
of a filter or pump or both.
(2) If
the requirement for engineering plans is waived, the owner of the spa assumes
full responsibility for ensuring that the construction or reconstruction
complies with these rules and with any other applicable federal, state and
local laws, rules, and ordinances.
b.
Content of plans. Plans
and specifications shall contain sufficient information to demonstrate to the
department that the proposed spa will meet the requirements of this chapter.
The information shall include, but may not be limited to:
(1) The name and address of the owner and the
name, address, and telephone number of the architect or engineer responsible
for the plans and specifications. If a contractor applies for a construction
permit, the name, address and telephone number of the contractor shall be
included.
(2) The location of the
project by street address or other legal description.
(3) A site plan showing the spa in relation
to buildings, streets, any swimming pool within the same general area, water
and sewer service, gas service, and electrical service.
(4) Detailed scale drawings of the spa and
its appurtenances, including a plan view and cross sections at a scale of 1/4
inch per foot or larger. The location of inlets, overflow system components,
main drains, deck and deck drainage, the location and size of spa piping, and
the spa steps and handrails shall be shown.
(5) A drawing(s) showing the location, plan,
and elevation of filters, pumps, chemical feeders, ventilation devices, and
heaters, and additional drawings or schematics showing operating levels,
backflow preventers, valves, piping, flow meters, pressure gauges,
thermometers, the make-up water connection, and the drainage system for the
disposal of filter backwash water.
(6) Plan and elevation drawings of bathhouse
facilities including dressing rooms; lockers; showers, toilets and other
plumbing fixtures; water supply and drain and vent systems; gas service; water
heating equipment; electrical fixtures; and ventilation systems, if
provided.
(7) Complete technical
specifications for the construction of the spa, for the spa equipment and for
the spa appurtenances.
c.
Deviation from plans. No deviation from the plans and
specifications or conditions of approval shall be made without prior approval
of the department.
(3)
General design.
a.
Materials. A spa shall be constructed of materials which are inert, stable,
nontoxic, watertight, and durable.
b. Water depth. The maximum water depth for a
general use spa shall not exceed 4 ft measured from the overflow level of the
spa. The maximum depth of any seat or sitting bench shall not exceed 2 ft
measured from the overflow level. A special-use spa may be deeper than 4 ft
with written approval from the department.
c. Structural loading. A spa shall be
designed and constructed to withstand anticipated structural loading for both
full and empty conditions.
d.
Distance from a swimming pool. A spa may be immediately adjacent to a swimming
pool, or a minimum of 4 ft from a Class B swimming pool or 6 ft from a Class A
swimming pool. The distance shall be measured from the outside edge of a ladder
support or handrail on the deck, a lifeguard stand, a swimming pool slide, or a
similar obstruction.
e. Water
supply. The water supplied to a spa shall be from a source meeting the
requirements of the department of natural resources for potable water.
(1) Water supplied to a spa shall be
discharged to the spa system through an air gap or a reduced-pressure principle
backflow device complying with the requirements of AWWA C-511-97,
"Reduced-Pressure Principle Backflow-Prevention Assembly."
(2) Each hose bib at a facility shall be
equipped with an atmospheric vacuum breaker or a hose connection backflow
preventer.
f. Sewer
separation required. No part of a spa recirculation system may be directly
connected to a sanitary sewer. An air break or an air gap shall be
provided.
g. Operations manual. The
owner shall require that a permanent manual for operation of a spa be provided.
The manual shall include, but may not be limited to:
(1) Instructions for routine operations at
the spa including, but not necessarily limited to:
1. Filter backwash or cleaning.
2. Maintaining the chemical supply for the
chemical feed systems.
3. Vacuuming
and cleaning the spa.
4. Spa water
testing procedures, including the frequency of testing.
5. Superchlorination.
6. Controller sensor maintenance and
calibration, including the recommended frequency of maintenance.
(2) For each centrifugal pump, a
pump performance curve plotted on an 81/2" x 11" or larger sheet.
(3) For each chemical feeder, the maximum
rated output listed in weight per time or volume per time units.
(4) Basic operating and maintenance
instructions for spa equipment that requires cleaning, adjustment, lubrication,
or parts replacement, with recommended maintenance frequencies or the
parameters that would indicate a need for maintenance.
h. A schematic drawing of the spa
recirculation system shall be posted in the spa filter room or shall be
included in the operations manual. Clear labeling of the spa piping with flow
direction and water status (unfiltered, treated, backwash) may be substituted
for the schematic drawing.
i. A
permanent file containing the operations and maintenance manuals for the
equipment installed at the spa shall be established. The file shall include a
source for parts or maintenance for the equipment at the spa. The file may be
located in a location other than the facility, but the file shall be readily
available to the facility management and maintenance staff.
(4)
Decks. A spa shall have
a deck around at least 50 percent of the spa perimeter. The deck shall be at
least 4 ft wide.
a.
Deck
materials. The deck shall be constructed of stable, nontoxic, and
durable materials.
b.
Deck
drainage. The deck shall drain away from the spa at a slope of at
least 1/8 inch/ft, but no more than 1/2 inch/ft to deck drains or to the
surrounding ground surface. The deck shall be constructed to eliminate standing
water.
c.
Deck
surface. The deck shall be provided with a slip-resistant, durable,
and cleanable surface.
d.
Deck covering. A deck covering may be used provided that:
(1) The covering allows drainage so that the
covering and the deck do not remain wet or retain moisture.
(2) The covering is inert and will not
support bacterial growth.
(3) The
covering provides a slip-resistant surface.
(4) The covering is durable and
cleanable.
e.
Steps or ramp required. When the top rim of a spa is more than 24
inches above the surrounding floor area, stairs or a ramp shall be provided to
the top of the spa. Stairs or a ramp shall be designed in accordance with the
state building code or the building code adopted by the jurisdiction in which
the spa is located.
(5)
Recirculation.
a.
Separate recirculation required. A spa shall have a
recirculation system separate from another spa or any swimming pool.
b.
Recirculation flow rate.
The recirculation system shall be capable of processing one spa volume of water
within 30 minutes. For spas with skimmers, the recirculation flow rate shall be
at least 3.8 gpm per lineal inch of skimmer weir or the flow rate required
above, whichever is greater.
c.
Recirculation pump. The recirculation pump(s) shall be listed
by NSF or by another listing agency approved by the department as complying
with the requirements of Standard 50 and shall comply with the following
requirements:
(1) The pump(s) shall supply the
recirculation flow rate required by 15.52(5)
"b" at a TDH of at
least that given in "1," "2" or "3" below, unless a lower TDH is shown by the
designer to be hydraulically appropriate. A valve for regulating the rate of
flow shall be provided in the recirculation pump discharge piping.
1. 40 feet for vacuum filters; or
2. 60 feet for pressure sand filters;
or
3. 70 feet for pressure
diatomaceous earth filters or cartridge filters.
(2) A separate pump or pumps shall be
provided for the spa agitation system.
(3) For sand filter systems, the pump and
filter system shall be designed so that each filter can be backwashed at a rate
of at least 15 gpm/ft2 of filter area.
(4) If a pump is located at an elevation
higher than the spa water surface, it shall be self-priming or the piping shall
be arranged to prevent the loss of pump prime when the pump is
stopped.
(5) Where a vacuum filter
is used, a vacuum limit control shall be provided on the pump suction line. The
vacuum limit switch shall be set for a maximum vacuum of 18 in Hg.
(6) A compound vacuum-pressure gauge shall be
installed on the pump suction line as close to the pump as practical. A vacuum
gauge may be used for pumps with suction lift. A pressure gauge shall be
installed on the pump discharge line as close to the pump as practical. Gauges
shall be of such a size and located so that they may be easily read by the
operator.
(7) On pressure filter
systems, a hair and lint strainer shall be installed on the suction side of the
recirculation pump. The hair and lint strainer basket shall be readily
accessible for cleaning, changing, or inspection. A spare strainer basket shall
be provided. This requirement may be waived for systems using vertical turbine
pumps or pumps designed for solids handling.
d.
Spa water heater.
(1) A heating coil, pipe or steam hose shall
not be installed in a spa.
(2)
Gas-fired spa water heaters shall comply with the requirements of ANSI/AGA
Z21.56-2001, ANSI/AGA Z21.56a-2004, and ANSI/AGA Z21.26b-2004.
(3) Electric spa water heaters shall comply
with the requirements of UL 1261 and shall bear the UL mark.
(4) A spa water heater with an input of
greater than 400,000 BTU/hour (117 kilowatts) shall have a water heating vessel
constructed in accordance with ASME Boiler Code, Section 8. The data plate of
the heater shall bear the ASME mark.
(5) A thermometer shall be installed in the
piping to measure the temperature of the water returning to the spa. The
thermometer shall be located so that it may be read easily by an
operator.
(6) Combustion air shall
be provided for fuel-burning water heaters as required by the state plumbing
code, 641-Chapter 25, Iowa Administrative Code, or as required by local
ordinance.
(7) Fuel-burning water
heaters shall be vented as required by the state plumbing code, 641-Chapter 25,
Iowa Administrative Code, or as required by local ordinance.
(8) Fuel-burning water heaters shall be
equipped with a pressure relief valve sized for the energy capacity of the
heater.
e.
Flow
meters.
(1) Each spa recirculation
system shall be provided with a permanently installed flow meter to measure the
recirculation flow rate.
(2) A flow
meter shall be accurate within 5 percent of the actual flow rate between
± 20 percent of the recirculation flow rate specified in
15.52(5)"b" or the nominal recirculation flow rate specified
by the designer.
(3) A flow meter
shall be installed on a straight length of pipe with sufficient clearance from
valves, elbows or other sources of turbulence to attain the accuracy required
by 15.52(5)"e" (2). The flow meter shall be installed so that
it may be easily read by the facility staff, or a remote readout of the flow
rate shall be installed where it may be easily read by the staff. The designer
may be required to provide documentation that the installation meets the
requirements of subparagraph (2).
(6)
Filtration. A filter
shall be listed by NSF or by another listing agency approved by the department
as complying with the requirements of Standard 50 and shall comply with the
following requirements:
a. Pressure gauges.
Each pressure filter shall have a pressure gauge on the inlet side. Gauges
shall be of such a size and located so that they may be read easily by the
operator. A differential pressure gauge which gives the difference in pressure
between the inlet and outlet of the filter may be used in place of a pressure
gauge.
b. Air relief valves. An air
relief valve shall be provided for each pressure filter.
c. Backwash water visible. Backwash water
from a pressure filter shall discharge through an observable free fall, or a
sight glass shall be installed in the backwash discharge line.
d. Backwash water discharge. Backwash water
shall be discharged indirectly to a sanitary sewer or another point of
discharge approved by the department of natural resources.
e. Rapid sand filter.
(1) The filtration rate shall not exceed 3
gpm/ft2 of filter area.
(2) The backwash rate shall be at least 15
gpm/ft2 of filter area.
f. High-rate sand filter.
(1) The filtration rate shall not exceed 15
gpm/ft2 of filter area.
(2) The backwash rate shall be at least 15
gpm/ft2 of filter area.
(3) If more than one filter tank is served by
a pump, the designer shall demonstrate that backwash flow rate to each filter
tank meets the requirements of subparagraph (2), or an isolation valve shall be
installed at each filter tank to permit each filter to be backwashed
individually.
g. Vacuum
sand filter.
(1) The filtration rate shall not
exceed 15 gpm/ft2 of filter area.
(2) The backwash rate shall be at least 15
gpm/ft2 of filter area.
(3) An equalization screen shall be provided
to evenly distribute the filter influent over the surface of the filter
sand.
(4) Each filter system shall
have an automatic air-purging cycle.
h. Sand filter media shall comply with the
filter manufacturer's specifications.
i. Diatomaceous earth filters.
(1) The filtration rate shall not be greater
than 1.5 gpm/ft2 of effective filter area except
that a maximum filtration rate of 2.0 gpm/ft2 may be
allowed where continuous body feed is provided.
(2) Diatomaceous earth filter systems shall
have piping to allow recycling of the filter effluent during precoat.
(3) Waste diatomaceous earth shall be
discharged to a sanitary sewer or other point of discharge approved by the
department of natural resources. The discharge may be subject to the
requirements of the local waste water utility.
j. Cartridge filters.
(1) The filtration rate shall not exceed 0.38
gpm/ft2.
(2) A duplicate set of cartridges shall be
provided.
k. Other filter
systems may be used if approved by the department.
(7)
Piping.
a.
Piping standards. Spa
piping shall conform to applicable nationally recognized standards and shall be
specified for use within the limitations of the manufacturer's specifications.
Spa piping shall comply with the applicable requirements of NSF/ANSI Standard
61, "Drinking Water System Components-Health Effects." Plastic pipe shall
comply with the requirements of NSF/ANSI Standard 14, "Plastic Piping
Components and Related Materials," for potable water pipe.
b.
Pipe sizing. Spa
recirculation piping shall be sized so that water velocities do not exceed 6
ft/sec for suction flow and 10 ft/sec for pressure flow.
c.
Skimmer pipe capacity.
The piping for the skimmer system shall be designed to convey 100 percent of
the recirculation flow rate.
d.
Main drain pipe capacity. The main drain piping shall be
designed to convey 100 percent of the recirculation flow rate. If the spa
agitation system uses the same suction piping as the recirculation system, the
piping shall be designed for the combined flow within the requirements of
paragraph "b" above.
e.
Separate piping required.
The piping from the spa agitation system pump to the spa shall be separate from
the recirculation system piping.
(8)
Inlets.
a. Wall inlets shall be provided for a
spa.
b. The inlets shall be
adequate in design, number, location, and spacing to ensure effective
distribution of treated water and the maintenance of a uniform disinfectant
residual throughout the spa. At least two recirculation inlets shall be
provided.
(1) Inlets shall be located at least
6 inches below the design water surface.
(2) Inlets shall be directional flow-type
inlets. Each inlet shall have a fitting with an opening of 1 inch diameter or
less.
c. Each agitation
system opening shall have a fitting with an opening of 1 inch diameter or
less.
(9)
Skimmers. A recessed automatic surface skimmer shall be listed
by NSF or by another listing agency approved by the department as complying
with the requirements of Standard 50, except that an equalizer is not required
for a skimmer installed in a spa equipped with an automatic water level
maintenance device.
a. Skimmers required. A
spa shall have at least one skimmer for each 100 ft2
of surface area or fraction thereof.
b. Flow-through skimmers. Each skimmer shall
be designed for a flow-through rate of at least 3.8 gpm per lineal inch of
weir. The combined capacity of all skimmers in a spa shall not be less than the
total recirculation rate.
c.
Skimmer weirs. Skimmers shall have weirs that adjust automatically to
variations in water level of at least 4 inches.
d. Flow control. Skimmers shall be equipped
with a device to control flow through the skimmer.
e. Equalizers. If a spa is not equipped with
an automatic water level maintenance device, each skimmer shall have an
operational equalizer. The equalizer opening in the spa shall be covered with a
fitting listed by a listing agency approved by the department as meeting the
requirements of the ASME standard.
f. The skimmer(s) shall not be connected to
the agitation system.
(10)
Main drain system. Each
spa shall have a convenient means of draining the water from the spa for
service. Spa main drains may be on the sidewall of a spa near the spa bottom.
a. Suction outlets. If a spa pump is directly
connected to a main drain or another fully submerged outlet, the pump shall be
connected to two or more fully submerged outlets or to a single fully submerged
outlet that is unblockable. The recirculation system and the agitation system
may use the same fully submerged outlet(s).
(1) Two fully submerged outlets that are
directly connected to one or more pumps in the same outlet system shall be at
least 3 ft apart on center or on different spa surfaces. If three or more fully
submerged outlets that are all directly connected to one or more pumps in the
same outlet system are installed, the distance between the outlets farthest
apart shall be at least 3 ft on center or the outlets shall be installed on
different spa surfaces.
(2) If
there is only one fully submerged outlet in an outlet system, the flow rating
of the outlet cover/grate, sump and the associated piping shall be at least 100
percent of the maximum system flow rate. If two or more fully submerged outlets
are installed in an outlet system, the combined flow rating of the
cover/grates, the sumps and the associated piping shall be at least 200 percent
of the maximum system flow rate. Multiple outlets in an outlet system shall be
plumbed in parallel.
The maximum system flow rate for the recirculation system is
the flow rate specified in 15.52(5)"b" or the design flow
rate, whichever is greater. The maximum system flow rate for the agitation
system is the specified design flow rate. If a flow rate is not specified, the
maximum system flow rate shall be the flow capacity of the pump(s) at 50 feet
TDH, based on the manufacturer's published pump curves.
b. Control valve. If a main drain
is connected to the recirculation system, there shall be a control valve to
adjust the flow between the main drain and the overflow system.
c. Main drain covers. Each main drain or
other fully submerged outlet shall be covered with a cover/grate that is listed
as complying with the requirements of the ASME standard by a listing agency
approved by the department. A listed cover/grate shall be used in accordance
with its listing.
(1) The flow rating for the
cover/grate(s) shall comply with 15.52(10)"a" (2).
(2) The mark of a listing agency acceptable
to the department shall be permanently marked on the top surface of each
manufactured cover/grate.
(3) Field
fabricated cover/grates shall be certified for compliance to the ASME standard
by a professional engineer licensed in Iowa. A certificate of compliance shall
be provided to the spa owner and to the department.
(4) The fully submerged outlet cover/grate
shall be designed to be securely fastened to the spa so that the cover/grate is
not removable without tools.
d. For outlet systems with manufactured
sumps, the sumps shall be listed by a listing agency acceptable to the
department for compliance with the ASME standard. Field fabricated sumps shall
be designed in accordance with the ASME standard and shall be certified by an
engineer licensed in Iowa.
(11)
Disinfection and pH
control.
a. Controller required. A
spa recirculation system shall be equipped with an automatic controller for
maintenance of the disinfectant level and pH in the spa water. The control
output of the controller to the chemical feed systems shall be based on the
continuous measurement of the ORP and the pH of the water in the spa
recirculation system.
b. No
disinfection system designed to use di-chlor or tri-chlor shall be installed
for an indoor spa after May 4, 2005.
c. Disinfection system. A continuous feed
disinfectant system shall be provided. The disinfectant feed system shall have
the capacity to supply at least 10 mg/L chlorine or bromine based on the
recirculation flow rate required in 15.52(5)"b."
d. Disinfection feeder listing. A
disinfectant feeder shall be listed by NSF or by another listing agency
approved by the department as complying with the requirements of Standard
50.
e. Gas chlorine shall not be
used as a disinfectant for a spa.
f. Solution feed. Where a metering pump is
used to feed a solution of disinfectant, the disinfectant solution container
shall have a capacity of at least one day's supply at the rate specified in
15.52(11)"c."
g.
Erosion chlorine feeders. The storage capacity of an erosion feeder shall be at
least one day's supply of disinfectant at the rate specified in
15.52(11)"c."
h.
pH chemical system. Each spa shall have a metering pump for the addition of a
pH control chemical to the spa recirculation system, or a carbon dioxide
(CO2) gas feed system. A metering pump shall be listed
by NSF or another listing agency approved by the department as complying with
the requirements of Standard 50.
i.
Chemical feed stop. The chemical feed systems shall be designed so that
chemical feed is automatically and positively stopped when the recirculation
flow is interrupted.
j. Test
equipment. Test equipment complying with the following requirements shall be
provided.
(1) The test equipment shall provide
for the direct measurement of free chlorine and combined chlorine from 0 to 10
ppm in increments of 0.2 ppm or less over the full range, or total bromine from
0 to 20 ppm in increments of 0.5 ppm over the full range.
(2) The test equipment shall provide for the
measurement of spa water pH from 7.0 to 8.0 with at least five increments in
that range.
(3) The test equipment
shall provide for the measurement of total alkalinity and calcium hardness with
increments of 10 ppm or less.
(4)
The test equipment shall provide for the measurement of cyanuric acid from 30
to 100 ppm. This requirement may be waived for a facility that does not use
cyanuric acid or a stabilized chlorine disinfectant.
(12)
Safety.
a.
Spa entry. A spa shall
have at least one stairway, ramp, ladder, or set of recessed steps designating
a point of entry and exit for every 50 ft of perimeter or fraction thereof.
(1) Stair steps leading into a spa shall be
at least 12 inches wide, the tread depth shall be no less than 10 inches, and
the riser height shall be no more than 12 inches. If a bench or seat is used as
a part of the stair, the first riser height from the bottom of the spa to the
seat or bench shall be no more than 14 inches. Except for the first riser, the
riser height shall be uniform.
1. Stair steps
shall be provided with a slip-resistant surface.
2. The stair steps shall be provided with two
handrails or grab rails, one on each side of the steps.
(2) Ladders.
1. Ladders shall be provided with a handrail
which extends from below the water surface to the top surface of the deck on
each side of the ladder.
2. Ladders
shall be of a color contrasting with the spa walls.
(3) Recessed steps.
1. Recessed steps shall have a tread depth of
at least 5 inches, a tread width of at least 12 inches, and a uniform rise of
no more than 12 inches.
2. Recessed
steps shall be provided with a handrail or with deck-level grab rails on each
side of the recessed steps.
3.
Recessed steps shall drain to the spa.
(4) Handrails and grab rails.
1. Ladders, handrails, and grab rails shall
be designed to be securely anchored and so that tools are required for their
removal.
2. Ladders, handrails, and
grab rails shall be of corrosion-resistant materials, or provided with
corrosion-resistant coatings. They shall have no exposed sharp
edges.
b.
Agitation system control. The agitation system start control
shall be installed out of the reach of persons in the spa. The "on" cycle for
the agitation system shall be no more than ten minutes.
c.
Electrical. New
construction or reconstruction shall comply with the requirements of the
National Electrical Code, 70-2005, as published by the National Fire Protection
Association, Batterymarch Park, Quincy, MA 02269.
d.
Lighting. Artificial
lighting shall be provided at indoor spas and at outdoor spas which are to be
used after sunset, in accordance with the following:
(1) Underwater lighting of at least 60 lamp
lumens/ft2 or 0.5
watts/ft2 of water surface area and area lighting of
at least 10 lumens/ft2 or 0.6
watts/ft2 of deck area.
(2) If underwater lights are not provided,
overhead lighting of at least 30 lumens/ft2 or 2.0
watts/ft2 of spa water surface area shall be
provided.
e.
Spa
enclosure.
(1) A spa shall be
enclosed by a fence, wall, building, or combination thereof not less than 4 ft
high. The spa enclosure shall be constructed of durable materials. A spa may be
in the same room or enclosure as another spa or a swimming pool.
(2) A fence, wall, or other means of
enclosure shall have no openings that would allow the passage of a 4-inch
sphere, and shall not be easily climbable by toddlers. The distance between the
ground and the top of the lowest horizontal support accessible from the outside
of the facility, or between the two lowest horizontal supports accessible from
outside the facility, shall be at least 45 inches. A horizontal support is
considered accessible if it is on the exterior of the fence relative to the
spa, or if the gap between the vertical members of the fence is greater than
13/4 inches.
(3) At least one gate
or door with an opening of at least 36 inches in width shall be provided for
emergency purposes. When closed, gates and doors shall comply with the
requirements of (2) above. Gates and doors shall be lockable. Except where
lifeguard or structured program supervision is provided whenever the spa is
open, gates and doors shall be self-closing and self-latching.
(4) For indoor spas, if there are sleeping
rooms, apartments, condominiums, or permanent recreation areas used by children
which open directly into the spa area, the spa shall be enclosed by a barrier
at least 3 ft high. No opening in the barrier shall permit the passage of a
4-inch sphere. There shall be at least one 36-inch-wide gate or door through
the barrier. Gates and doors shall be lockable. Except where lifeguard
supervision is provided whenever the spa is open, gates or doors shall be
self-closing and self-latching.