Rule 21-43.6 - Standard for the Storage and Handling of Anhydrous Ammonia
Current through Register Vol. 47, No. 6, September 18, 2024
The Compressed Gas Association's (CGA's) American National Standard Safety Requirements for the Storage and Handling of Anhydrous Ammonia (6th edition), commonly referred to as ANSI/CGA G-2.1 2014, is adopted by this reference as the official requirement for the storage and handling of anhydrous ammonia, with the following exceptions:
1. Strike subrule 3.1 in its entirety and insert in lieu thereof the following:
2. Insert a new subrule 5.1.3 to read as follows:
3. The following subrule 5.3.4 as set out in CGA G-2.1 2014, page 16, is included:
Minimum Separation Distances for Location of Ammonia Storage Containers
Minimum Distances (in feet or meters) from Each Container to: |
||||
Nominal Capacity of Container3) (Gallons or Cubic Meters) |
Mainline of Railroad4) |
Highway5) or Line of Adjoining Property which can be built upon |
Place of Public Assembly6) or Residential Occupancy7) |
Institutional Occupancy8) |
Over 500 to 2,000 gals9) |
100 ft |
25 ft |
150 ft |
250 ft |
Over 2,000 to 30,000 gals |
100 ft |
50 ft |
300 ft |
500 ft |
Over 30,000 to 100,000 gals |
100 ft |
50 ft |
450 ft |
750 ft |
Over 100,000 gals |
100 ft |
50 ft |
600 ft |
1000 ft |
Over 2 to 8 m3 |
30 m |
8 m |
45 m |
75 m |
Over 8 to 110 m3 |
30 m |
15 m |
90 m |
150 m |
Over 110 to 400 m3 |
30 m |
15 m |
140 m |
230 m |
Over 400 m3 |
30 m |
15 m |
180 m |
300 m |
4. Strike subrule 5.3.6 in its entirety and insert in lieu thereof the following:
5. Strike subrule 5.6.6 in its entirety and insert in lieu thereof the following:
6. Insert a new subrule 5.10.8.2 to read as follows:
Note: The internal back-pressure check valves or internal excess flow valves shall be installed in the facility piping prior to the positive shut-off valves. These valves shall be installed so that any break will occur on the side of the transfer hose. Protection from pull away while connected is the same as described in 5.10.8.1.
7. Add the following subrule 5.10.10:
Note: Ammonia vapor may be flared off when appropriate equipment is used to not allow ammonia vapor to escape unchecked into the atmosphere. This section does not apply to venting of a coupling between transfer hose and nurse tank or applicator or venting of vapor through 85 percent bleeder valve when loading a nurse tank or applicator.
8. Add the following subrule 5.10.10.1:
9. Add the following subrule 5.10.11:
Note: This section does not apply to nurse tanks or applicators with a working surface designed for loading purposes.
10. Add the following subrule 6.3.1.1:
11. Strike subrule 9.7.3 in its entirety and insert in lieu thereof the following:
12. Strike subrule 11.3.5 in its entirety and insert in lieu thereof the following:
13. Strike subrule 11.6.1 in its entirety and insert in lieu thereof the following:
14. Strike subrule 11.6.2 in its entirety and insert in lieu thereof the following:
15. Strike subrule 12.3.3 in its entirety and insert in lieu thereof the following:
16. Strike subrule 12.4.1 in its entirety and insert in lieu thereof the following:
This rule is intended to implement Iowa Code section 200.14.