Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 31 - INDIANA AMUSEMENT DEVICE CODE
Rule 5 - Technical Requirements
Section 5-19 - Number of exits

Universal Citation: 675 IN Admin Code 5-19

Current through September 18, 2024

Authority: IC 22-13-2-8

Affected: IC 22-15-2-7; IC 22-15-7

Sec. 19.

(a) All totally enclosed amusement device structures shall have at least two (2) exits located at or near opposite sides of the structure.

(b) If the capacity of the totally enclosed amusement device structure exceeds six hundred (600) persons, exits shall be provided on three (3) sides. If the capacity exceeds one thousand (1,000) persons, the exits shall be located on four (4) sides. Exits shall be uniformly distributed as nearly as possible, and the line of travel from any point to an exit shall not exceed one hundred fifty (150) feet.

NOTE: Transferred from the Regulated Amusement Device Safety Board (685 IAC 1-5-19) to the Fire Prevention and Building Safety Commission (675 IAC 31-5-19) by P.L. 249-2019, SECTION 16, effective July 1, 2019.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.