Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 30 - INDIANA BOILER AND PRESSURE VESSEL RULES
Rule 5 - General Requirements
Section 5-6 - Safety appliances; removal or alteration
Current through September 18, 2024
Authority: IC 22-13-2-8
Affected: IC 22-15-6
Sec. 6.
(a) No person, except under the direction of an inspector, shall remove, or alter, any safety appliance prescribed by this article while a boiler or unfired pressure vessel is in operation, except for the purpose of making emergency repairs.
(b) If a safety appliance is repaired during an outage of a boiler or unfired pressure vessel, it must be reinstalled in accordance with the provisions of this article.
(c) The resetting of a safety appliance at a new pressure shall be done only with the approval of an inspector.
(d) No person shall in any manner load a safety valve to maintain a working pressure in excess of the MAWP of the boiler or unfired pressure vessel.
Transferred from the Boiler and Pressure Vessel Rules Board ( 680 IAC 2-5-6) to the Fire Prevention and Building Safety Commission ( 675 IAC 30-5-6) by P.L. 249-2019, SECTION 15, effective July 1, 2019.