Section 5-5 - Hydrostatic leak tests; alternative tests

Universal Citation: 675 IN Admin Code 5-5

Current through September 18, 2024

Authority: IC 22-13-2-8

Affected: IC 22-15-6

Sec. 5.

(a) The pressure of a hydrostatic leak test, when performed on a boiler or unfired pressure vessel of riveted or welded construction, except a locomotive boiler, shall not exceed the original hydrostatic test pressure. The pressure of a hydrostatic leak test performed on a locomotive boiler shall not exceed one and one-fourth (1 1/4) times the MAWP. During the hydrostatic leak test, the safety valve or valves shall be removed, or each valve disk shall be held down by means of a testing clamp and not by applying additional load to the spring with the compression screw. The minimum water temperature used to perform a hydrostatic leak test shall meet the requirements of the applicable construction or repair code; however, the maximum water temperature shall not exceed one hundred twenty (120) degrees Fahrenheit.

(b) If the inspector and the owner or user so agree, other examinations or tests in accordance with the ASME B&PVC or Part 3 of the NBIC may be substituted for the leak test required by this section.

Transferred from the Boiler and Pressure Vessel Rules Board ( 680 IAC 2-5-5) to the Fire Prevention and Building Safety Commission ( 675 IAC 30-5-5) by P.L. 249-2019, SECTION 15, effective July 1, 2019.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.