Rule 11 - Existing Installations of Unfired Pressure Vessels (prior to July 1, 1953)
Section 11-4 - Safety appliances

Universal Citation: 675 IN Admin Code 11-4
Current through September 18, 2024

Authority: IC 22-13-2-8

Affected: IC 22-15-6

Sec. 4.

Each unfired pressure vessel shall be protected by such safety and relief valves and interlocking, indicating, and controlling safety devices as will ensure its safe operation. These valves and devices shall be so constructed, located, and installed that they cannot readily be rendered inoperative. The relieving capacity of safety valves shall be such as to prevent a rise of pressure in the vessel in excess of that permitted by applicable provisions of the API-ASME code or the ASME B&PVC, taking into account the effect of static head. Safety valve discharges shall be carried to a point where damage to property or injury to personnel is minimized.

Transferred from the Boiler and Pressure Vessel Rules Board ( 680 IAC 2-11-4) to the Fire Prevention and Building Safety Commission ( 675 IAC 30-11-4) by P.L. 249-2019, SECTION 15, effective July 1, 2019.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.