Rule 10 - Existing Installations of Heating Boilers
Section 10-7 - Water gage glasses; location
Universal Citation: 675 IN Admin Code 10-7
Current through September 18, 2024
Authority: IC 22-13-2-8
Affected: IC 22-15-6
Sec. 7.
Each steam heating boiler shall have at least one (1) water gauge glass with the lowest visible part above the heating surfaces in the primary combustion chamber. When the heating surfaces above the low water line may be injured by contact with gases of high temperature, the water gauge shall be raised until the lowest visible part of the gauge glass is above such heating surface.
Transferred from the Boiler and Pressure Vessel Rules Board ( 680 IAC 2-10-7) to the Fire Prevention and Building Safety Commission ( 675 IAC 30-10-7) by P.L. 249-2019, SECTION 15, effective July 1, 2019.
Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.