Rule 10 - Existing Installations of Heating Boilers
Section 10-11 - Stop valves and check valves

Universal Citation: 675 IN Admin Code 10-11

Current through March 20, 2024

Authority: IC 22-13-2-8

Affected: IC 22-15-6

Sec. 11.

(a) If a heating boiler may be closed off from the heating system by closing a steam stop valve, there shall be a check valve in the condensate return line between the boiler and the system.

(b) If any part of a heating system may be closed off from the remainder of the system by closing a steam stop valve, there shall be a check valve in the condensate return pipe from that part of the system.

Transferred from the Boiler and Pressure Vessel Rules Board ( 680 IAC 2-10-11 ) to the Fire Prevention and Building Safety Commission ( 675 IAC 30-10-11 ) by P.L. 249-2019, SECTION 15, effective July 1, 2019.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.