Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 30 - INDIANA BOILER AND PRESSURE VESSEL RULES
Rule 10 - Existing Installations of Heating Boilers
Section 10-10 - Thermometers for hot water heating boilers; location and connection
Authority: IC 22-13-2-8
Affected: IC 22-15-6
Sec. 10.
Each hot water heating boiler shall have a thermometer so located and connected that it shall be easily readable when observing the water pressure or altitude. The thermometer shall be so located that it shall at all times indicate the temperature in degrees Fahrenheit of the water in the boiler, at or near the outlet. The pressure or altitude gauges and thermometer may be separate devices, or a combination device.
Transferred from the Boiler and Pressure Vessel Rules Board ( 680 IAC 2-10-10) to the Fire Prevention and Building Safety Commission ( 675 IAC 30-10-10) by P.L. 249-2019, SECTION 15, effective July 1, 2019.