Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 24 - SUPPLEMENTARY FIRE SAFETY RULES
Rule 1 - Migrant Day Care Nursery Fire Safety Code
Section 1-7 - Egress requirements
Current through September 18, 2024
Authority: IC 12-17.2-2-9
Affected: IC 16-19-3-4; IC 22-13-2-2
Sec. 7.
(a) A minimum of two (2) exits, other than elevators, are required when the number of occupants in any exempted center or portion thereof, used by children ages 0-2, is at least seven (7), and for children ages 3-6 is at least sixteen (16). Exits shall be located a distance apart, equal to but not less than one-half (1/2) of the length of the maximum overall diagonal dimension of the area to be served, measured in a straight line between exits. This distance may be decreased to one-third (1/3) if the building is equipped throughout with a supervised sprinkler system. See Table 8-A [sic., Table 7-A].
(b) Exit doors shall meet the following requirements:
(c) Exit signs shall meet the following requirements:
(d) The means of egress from the exempted center shall be provided with a light having an intensity of a one (1) foot candle at floor level, at all times, during hours of operation.