Rule 1.6 - 2014 Indiana Mechanical Code
Section 1.6-7 - Chapter 6; duct systems

Universal Citation: 675 IN Admin Code 1.6-7

Current through September 18, 2024

Authority: IC 22-13-2-2

Affected: IC 22-12-7; IC 22-13; IC 22-14; IC 36-8-17

Sec. 7.

(a) Amend Section 602.2.1.4 by deleting the text in its entirety and inserting the following: 602.2.1.4 Combustible electrical equipment. Combustible electrical equipment exposed within a plenum shall have a peak rate of heat release not greater than 100 kilo watts, a peak optical density not greater than 0.50 and an average optical density not greater than 0.15 when tested in accordance with Ul 2043. Combustible electrical equipment shall be listed and labeled.

(b) Delete Section 602.2.1.4.1 in its entirety.

(c) Delete Section 602.2.1.4.2 in its entirety.

(d) Amend Section 607.5.4 by deleting the text of Exception 2 and inserting the following: Exception 2. Smoke dampers shall not be required in duct penetrations of smoke barriers in fully ducted heating, ventilating, and air conditioning systems in smoke compartments protected throughout with quick response sprinklers.

(e) Amend Section 607.5.5, after the word "fire", by deleting "and smoke" without substitution.

(f) Amend Section 607.5.5 by deleting Exception 2 without substitution.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.