Section 1.6-11 - Chapter 11; refrigeration

Universal Citation: 675 IN Admin Code 1.6-11

Current through September 18, 2024

Authority: IC 22-13-2-2

Affected: IC 22-12-7; IC 22-13; IC 22-14; IC 36-8-17

Sec. 11.

(a) Delete Section 1101.10 in its entirety without substitution.

(b) Amend Section 1105.6.3 by inserting after "multispeed fans shall be allowed to be", the words "30 air changes per hour".

(c) Amend Section 1106.5 to read as follows: Remote controls. Where flammable refrigerants are used, remote control of the mechanical equipment and appliances located in the machinery room shall comply with Sections 1106.5.1 and 1106.5.2 shall be provided at an approved location immediately outside the machinery room and adjacent to its principal entrance.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.