Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 17 - ELECTRICAL CODES
Rule 1.8 - Indiana Electrical Code, 2009 Edition
Section 1.8-27 - Section 680.26(B)(2)(b); alternate means
Current through September 18, 2024
Authority: IC 22-13-2-2; IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7
Sec. 27.
(a) Delete the text of 680.26(B)(2)(b) and substitute to read as follows: Alternate means. Where structural reinforcing steel is not available or is encapsulated in a nonconductive compound, a copper grid shall be installed within concrete or under other surfaces in accordance with 680.26(B)(1)(b).
(b) After 680.26(B)(2)(b), insert an exception to read as follows: Exception to (b): The equipotential bonding grid shall not be required to be installed under pool decks of nonconductive materials.
Agency cited as 675 IAC 17-1.8-30, which was renumbered by the Publisher as 675 IAC 17-1.8-27.