Section 1.8-25 - Section 680.26(B)(1); conductive pool shells

Universal Citation: 675 IN Admin Code 1.8-25

Current through September 18, 2024

Authority: IC 22-13-2-2; IC 22-13-2-13

Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7

Sec. 25.

(a) After the first sentence of 680.26(B)(1)(a), insert a new sentence to read as follows: Reinforcing steel shall not extend into soil beyond the concrete envelope.

(b) After 680.26(B)(1)(b), insert an exception to read as follows: Exception to (b): The equipotential bonding grid shall not be required to be installed under the bottom or vertically along the walls of vinyl lined polymer wall, fiberglass composite, or other pools constructed of nonconductive materials.

Agency cited as 675 IAC 17-1.8-28, which was renumbered by the Publisher as 675 IAC 17-1.8-25.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.