Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 17 - ELECTRICAL CODES
Rule 1.8 - Indiana Electrical Code, 2009 Edition
Section 1.8-25 - Section 680.26(B)(1); conductive pool shells
Current through September 18, 2024
Authority: IC 22-13-2-2; IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7
Sec. 25.
(a) After the first sentence of 680.26(B)(1)(a), insert a new sentence to read as follows: Reinforcing steel shall not extend into soil beyond the concrete envelope.
(b) After 680.26(B)(1)(b), insert an exception to read as follows: Exception to (b): The equipotential bonding grid shall not be required to be installed under the bottom or vertically along the walls of vinyl lined polymer wall, fiberglass composite, or other pools constructed of nonconductive materials.
Agency cited as 675 IAC 17-1.8-28, which was renumbered by the Publisher as 675 IAC 17-1.8-25.