Indiana Administrative Code
Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 17 - ELECTRICAL CODES
Rule 1.8 - Indiana Electrical Code, 2009 Edition
Section 1.8-13 - Section 300.3; conductors
Universal Citation: 675 IN Admin Code 1.8-13
Current through September 18, 2024
Authority: IC 22-13-2-2; IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7
Sec. 13.
Add Section 300.3(D), entitled "Separation from corrugated stainless steel tubing", and add text to read as follows: All wiring methods shall be isolated from corrugated stainless steel tubing by a space separation of at least 2 inches except where the bonding connection is made.
Agency cited as 675 IAC 17-1.8-14, which was renumbered by the Publisher as 675 IAC 17-1.8-13.
Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.