Title 675 - FIRE PREVENTION AND BUILDING SAFETY COMMISSION
Article 17 - ELECTRICAL CODES
Rule 1.8 - Indiana Electrical Code, 2009 Edition
Section 1.8-12 - Section 250.104(B); other metal piping
Universal Citation: 675 IN Admin Code 1.8-12
Current through September 18, 2024
Authority: IC 22-13-2-2; IC 22-13-2-13
Affected: IC 22-12; IC 22-13; IC 22-14; IC 22-15; IC 36-7
Sec. 12.
(a) Change the next to last sentence of Section 250.104(B) to read as follows: The equipment grounding conductor for the circuit that is likely to energize the piping shall be permitted to serve as the bonding means if connected using a fixed wiring method.
(b) Add a new sentence at the end of Section 250.104(B) to read as follows: All metal gas piping upstream from the equipment shutoff valve(s) shall be electrically continuous.
Agency cited as 675 IAC 17-1.8-13, which was renumbered by the Publisher as 675 IAC 17-1.8-12.
Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.