Indiana Administrative Code
Title 470 - DIVISION OF FAMILY RESOURCES
Article 3 - CHILD WELFARE SERVICES
Rule 4.7 - Child Care Centers; Licensing
Section 4.7-106 - Heat, light, ventilation, and air conditioning

Universal Citation: 470 IN Admin Code 4.7-106

Current through September 18, 2024

Authority: IC 12-13-5-3

Affected: IC 12-17.2-4

Sec. 106.

(a) Installation, testing, and maintenance of heating, ventilation, air conditioning, fire alarm, and sprinkler systems shall comply with the rules of the FPBSC under 675 IAC.

(b) When natural light is insufficient, it shall be supplemented by artificial light so that the following minimum levels of illumination are maintained:

(1) All food service areas shall have a minimum of seventy (70) foot-candles.

(2) All food storage areas, including refrigerators, shall have a minimum of twenty (20) foot-candles.

(3) Desks, table top work areas, reading areas, locked medication storage areas, and art rooms shall have a minimum of fifty (50) foot-candles.

(4) Gymnasiums, large muscle equipment areas, bathrooms, locker rooms, and diaper changing areas shall have a minimum of thirty (30) foot-candles.

(5) Hallways, corridors, stairwells, storage rooms, and food storage areas shall have a minimum of twenty (20) foot-candles.

(6) Rest and nap areas shall have a minimum of five (5) foot-candles in all areas.

(c) All light intensity measurements shall be at the level of work. If no work is done in a room or hallway, the measurement shall be at a height of thirty (30) inches above the floor.

(d) The child care center shall be ventilated.

(e) The center shall maintain a temperature of not less than sixty-eight (68) degrees Fahrenheit.

(f) All child care centers initially licensed after the effective date of this rule shall maintain a temperature not more than seventy-eight (78) degrees Fahrenheit.

(g) All outside doors and windows shall be screened with sixteen (16) gauge mesh screen when open.

(h) The center shall keep all screens in good repair and all unscreened windows and doors closed.

(i) The center shall make heating units, including water pipes and baseboard heaters, hotter than one hundred ten (110) degrees Fahrenheit inaccessible to children by barriers such as guards or other devices.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.