Sec. 4.

(a) Heating facilities shall be capable of and shall be operated to maintain a temperature during periods of student occupancy not less than the following:

(1) Sixty-eight (68) degrees Fahrenheit (F) in all:
(A) instructional rooms;

(B) offices;

(C) locker rooms; and

(D) cafeterias.

(2) Sixty-five (65) degrees Fahrenheit in activity rooms and shops.

(3) Sixty (60) degrees Fahrenheit in interior toilet rooms.

(b) Where provided air-conditioning systems shall be capable of providing and shall be operated to maintain a temperature not to exceed seventy-eight (78) degrees Fahrenheit and sixty-five percent (65%) relative humidity during periods of student occupancy.

Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.