Indiana Administrative Code
Title 327 - WATER POLLUTION CONTROL DIVISION
Article 8 - PUBLIC WATER SUPPLY
Rule 3.4 - Public Water System Wells
Section 3.4-15 - Discharge piping
Universal Citation: 327 IN Admin Code 3.4-15
Current through September 18, 2024
Authority: IC 13-14-8; IC 13-15-1-2; IC 13-15-2-1; IC 13-18-3-1; IC 13-18-4-1
Affected: IC 13-11-2; IC 13-13-5-1; IC 13-18-2
Sec. 15.
Discharge piping shall:
(1) meet the material requirements of 327 IAC 8-3.2-8;
(2) meet the installation requirements of 327 IAC 8-3.2-17;
(3) have control valves and other accessories located above the pumphouse floor when the discharge piping is located above grade; and
(4) be equipped with:
(A) check valve;
(B) shut off valve;
(C) pressure gauge;
(D) flow measuring equipment for individual
or collective flow measurement;
(E)
smooth nosed sample tap installed where positive pressure is maintained;
and
(F) threaded or flanged port
for maintenance and testing.
Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.