Authority: IC 13-14-8; IC 13-14-9; IC 13-15-1-2; IC
13-15-2-1; IC 13-18-3-1; IC 13-18-4-1
Sec. 8.
(a) All
piping, accessories, and other materials in a water main shall conform to 327
IAC 8-1, contain less than eight percent (8%) by mass lead, and conform to the
following applicable standards:
(1) For
ductile-iron and fittings, the following standards apply:
(A) C104/A21.4-03 American National Standard
for Cement-Mortar Lining for Ductile-Iron Pipe and Fittings for
Water.
(B) C105/A21.5-99 American
National Standard for Polyethylene Encasement for Ductile-Iron Pipe
Systems.
(C) C110/A21.10-03
American National Standard for Ductile-Iron and Gray-Iron Fittings for
Water.
(D) C111/A21.11-00 American
National Standard for Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and
Fittings.
(E) C115/A21.15-99
American National Standard for Flanged Ductile-Iron Pipe with Ductile-Iron or
Gray-Iron Threaded Flanges.
(F)
C150/A21.50-02 Thickness Design of Ductile-Iron Pipe.
(G) C151/A21.51-02 American National Standard
for Ductile-Iron Pipe, Centrifugally Cast, for Water. (H) C153/A21.53-00
American National Standard for Ductile-Iron Compact Fittings for Water
Service.
(2) For steel
pipe, the following standards apply:
(A)
C200-97 AWWA Standard for Steel Water Pipe-6 In. (150 mm) and Larger.
(B) C203-02 AWWA Standard for Coal-Tar
Protective Coatings and Linings for Steel Water Pipelines-Enamel and Tape-Hot
Applied.
(C) C205-00 AWWA Standard
for Cement-Mortar Protective Lining and Coating for Steel Water Pipe-4 In. (100
mm) and Larger-Shop Applied.
(D)
C206-97 AWWA Standard for Field Welding of Steel Water Pipe.
(E) C207-01 AWWA Standard for Steel Pipe
Flanges for Waterworks Service-Sizes 4 In. through 144 In. (100 mm through
3,600 mm).
(F) C208-01 AWWA
Standard for Dimensions for Fabricated Steel Water Pipe Fittings.
(G) C209-00 AWWA Standard for Cold-Applied
Tape Coatings for the Exterior of Special Sections, Connections, and Fittings
for Steel Water Pipelines.
(H)
C210-03 Liquid-Epoxy Coating Systems for the Interior and Exterior of Steel
Water Pipelines.
(I) C213-01 AWWA
Standard for Fusion-Bonded Epoxy Coating for the Interior and Exterior of Steel
Water Pipelines.
(J) C214-00 AWWA
Standard for Tape Coating Systems for the Exterior of Steel Water
Pipelines.
(K) C215-04 Extruded
Polyolefin Coatings for the Exterior of Steel Water Pipelines.
(L) C216-00 AWWA Standard for Heat-Shrinkable
Cross-Linked Polyolefin Coatings for the Exterior of Special Sections,
Connections, and Fittings for Steel Water Pipelines.
(M) C217-04 Cold-Applied Petrolatum and
Petroleum Wax Tape Coatings for the Exterior of Connections and Fittings for
Steel Water Pipelines.
(N) C218-02
AWWA Standard for Coating the Exterior of Aboveground Steel Water Pipelines and
Fittings.
(O) C219-01 AWWA Standard
for Bolted, Sleeve-Type Couplings for Plain-End Pipe.
(P) C220-98 AWWA Standard for Stainless-Steel
Pipe, 4 In. (100 mm) and Larger.
(3) For concrete pipe, the following
standards apply:
(A) C300-04 Reinforced
Concrete Pressure Pipe, Steel-Cylinder Type.
(B) C301-99 AWWA Standard for Prestressed
Concrete Pressure Pipe, Steel-Cylinder Type.
(C) C302-04 Reinforced Concrete Pressure
Pipe, Noncylinder Type.
(D) C303-02
Concrete Pressure Pipe, Bar-Wrapped, Steel-Cylinder Type.
(E) C304-99 AWWA Standard for Design of
Prestressed Concrete Cylinder Pipe.
(4) For asbestos-cement pipe, the following
standards apply:
(A) C400-03 Asbestos-Cement
Pressure Pipe, 4 In. through 16 In. (100 mm through 400 mm), for Water
Distribution Systems.
(B) C401-03
The Selection of Asbestos-Cement Pressure Pipe, 4 In. through 16 In. (100 mm
through 400 mm), for Water Distribution Systems.
(C) C402-00 AWWA Standard for Asbestos-Cement
Transmission Pipe, 18 In. through 42 In. (450 mm through 1,050 mm), for Water
Supply Service.
(D) C403-00 AWWA
Standard for the Selection of Asbestos-Cement Transmission Pipe, Sizes 18 In.
through 42 In. (450 mm through 1,050 mm), for Water Supply Service.
(5) For valves and hydrants, the
following standards apply:
(A) C500-02
Metal-Seated Gate Valves for Water Supply Service.
(B) C502-94 AWWA Standard for Dry-Barrel Fire
Hydrants (includes addendum C502a-95).
(C) C503-97 AWWA Standard for Wet-Barrel Fire
Hydrants.
(D) C504-00 AWWA Standard
for Rubber-Seated Butterfly Valves.
(E) C507-99 AWWA Standard for Ball Valves, 6
In. through 48 In. (150 mm through 1,200 mm).
(F) C508-01 AWWA Standard for Swing-Check
Valves for Waterworks Service, 2 In. through 24 In. (50 mm through 600 mm)
NPS.
(G) C509-01 AWWA Standard for
Resilient-Seated Gate Valves for Water Supply Service.
(H) C510-97 AWWA Standard for Double Check
Valve Backflow-Prevention Assembly.
(I) C511-97 AWWA Standard for
Reduced-Pressure Principle Backflow-Prevention Assembly.
(J) C512-04 Air-Release, Air/Vacuum, and
Combination Air Valves for Waterworks Service.
(K) C540-02 Power-Actuating Devices for
Valves and Slide Gates for Waterworks Service.
(L) C550-01 AWWA Standard for Protective
Epoxy Interior Coatings for Valves and Hydrants.
(M) C560-00 AWWA Standard for Cast-Iron Slide
Gate.
(6) For plastic
pipe, the following standards apply:
(A)
C900-97 AWWA Standard for Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated
Fittings, 4 In. through 12 In. (100 mm through 300 mm), for Water
Distribution.
(B) C901-96 AWWA
Standard for Polyethylene (PE) Pressure Pipe and Tubing, 1/2 In. (13 mm)
through 3 In. (76 mm), for Water Service.
(C) C905-97 AWWA Standard for Polyvinyl
Chloride (PVC) Pressure Pipe and Fabricated Fittings, 14 In. through 36 In (350
mm through 1,200 mm), for Water Transmission and Distribution.
(D) C906-99 AWWA Standard for Polyethylene
(PE) Pressure Pipe and Fittings, 4 In. (100 mm) through 63 In. (1,575 mm), for
Water Distribution and Transmission.
(E) C907-91 AWWA Standard for Polyvinyl
Chloride (PVC) Pressure Fittings for Water, 4 In. through 8 In. (100 mm through
200 mm).
(F) American Society for
Testing and Materials (ASTM) D2239-03 Standard Specifications for Polyethylene
(PE) Plastic Pipe (SIDR-PN) Based on Controlled Inside Diameter.
(G) ASTM D2241-04b Standard Specification for
Polyvinyl Chloride (PVC) Pressure-Rated Pipe (SDR Series).
(H) ASTM D3350-04 Standard Specification for
Polyethylene Plastic Pipe and Fittings Materials.
(b) All water mains installed in areas of
ground water contamination, consisting of solvent, petroleum, or other volatile
or semivolatile organic compounds, shall be constructed with nonpermeable
piping and accessories.
(c) Piping
and accessories previously used exclusively for water mains may be reused if
the piping or accessories:
(1) comply with the
requirements of subsection (a); and
(2) have been restored to their original
condition.
(d) All
connections between pipes shall have mechanical joints or slip-on joints with
rubber gaskets with the exception of:
(1)
steel pipe that may be welded;
(2)
polyethylene (PE) pipes that may be thermojointed by a person who is a
manufacturer's certified thermojointer; or
(3) piping described in section 10(d) of this
rule.
(e) Water mains
constructed with PVC and installed under existing or proposed roadways and
railroads shall be cased in conformance with AWWA Standard C900-97 or AWWA
Standard C905-97.
(f) Water mains
that are cased shall conform to AWWA Standard C600-99.
(g) Water mains constructed with nonmetallic
materials must be equipped with tracing wire or other metallic identification
equipment.