Indiana Administrative Code
Title 327 - WATER POLLUTION CONTROL DIVISION
Article 8 - PUBLIC WATER SUPPLY
Rule 3.2 - Technical Standards for Water Mains
Section 3.2-17 - Installation
Current through September 18, 2024
Authority: IC 13-14-8; IC 13-14-9; IC 13-15-1-2; IC 13-15-2-1; IC 13-18-3-1; IC 13-18-4-1
Affected: IC 13-11-2; IC 13-13-5-1; IC 13-18-2
Sec. 17.
(a) All water mains and their accessories shall be installed and pressure and leak tested in accordance with the applicable provisions of one (1) of the following:
If an AWWA Standard is not available for the particular installation, the manufacturer's recommended installation procedure shall be followed.
(b) Continuous and uniform bedding shall be provided in the trench for all buried pipe. Backfill material shall be tamped in layers around the pipe and to a sufficient height above the pipe to adequately support and protect the pipe. All stones unable to pass through a U.S. Standard Sieve opening of two (2) inches that are found in the trench within six (6) inches of the outside edge of the pipe shall be removed.
(c) All necessary reaction blocking, tie rods, or joints designed to prevent movement for pipes and fittings (regardless of material type) at tees, bends, plugs, and hydrants shall be installed to prevent movement in conformance with AWWA Standard C600-99.
(d) Water mains shall be covered with earthen cover in accordance with the following:
Depth of Cover Requirements for Water Mains
County | Cover[1] (in) |
Adams | 60 |
Allen | 60 |
Bartholomew | 48 |
Benton | 60 |
Blackford | 60 |
Boone | 54 |
Brown | 48 |
Carroll | 60 |
Cass | 60 |
Clark | 36 |
Clay | 54 |
Clinton | 54 |
Crawford | 36 |
Daviess | 48 |
Dearborn | 48 |
Decatur | 48 |
Dekalb | 60 |
Delaware | 60 |
Dubois | 42 |
Elkhart | 60 |
Fayette | 54 |
Floyd | 36 |
Fountain | 60 |
Franklin | 48 |
Fulton | 60 |
Gibson | 42 |
Grant | 60 |
Greene | 54 |
Hamilton | 54 |
Hancock | 54 |
Harrison | 36 |
Hendricks | 54 |
Henry | 54 |
Howard | 60 |
Huntington | 60 |
Jackson | 48 |
Jasper | 60 |
Jay | 60 |
Jefferson | 42 |
Jennings | 48 |
Johnson | 54 |
Knox | 48 |
Kosciusko | 60 |
LaGrange | 60 |
Lake | 60 |
LaPorte | 60 |
Lawrence | 48 |
Madison | 60 |
Marion | 54 |
Marshall | 60 |
Martin | 48 |
Miami | 60 |
Monroe | 48 |
Montgomery | 60 |
Morgan | 48 |
Newton | 60 |
Noble | 60 |
Ohio | 42 |
Orange | 42 |
Owen | 54 |
Parke | 60 |
Perry | 36 |
Pike | 42 |
Porter | 60 |
Posey | 42 |
Pulaski | 60 |
Putnam | 54 |
Randolph | 54 |
Ripley | 48 |
Rush | 54 |
St. Joseph | 60 |
Scott | 36 |
Shelby | 54 |
Spencer | 36 |
Starke | 60 |
Steuben | 60 |
Sullivan | 54 |
Switzerland | 42 |
Tippecanoe | 60 |
Tipton | 60 |
Union | 48 |
Vanderburgh | 36 |
Vermillion | 60 |
Vigo | 60 |
Wabash | 60 |
Warren | 60 |
Warrick | 36 |
Washington | 36 |
Wayne | 54 |
Wells | 60 |
White | 60 |
Whitley | 60 |
[1] The cover dimension is measured from the top of pipe to the proposed finish grade.