Indiana Administrative Code
Title 326 - AIR POLLUTION CONTROL DIVISION
Article 7 - SULFUR DIOXIDE RULES
Rule 4.1 - Lake County Sulfur Dioxide Emission Limitations
Section 4.1-3 - BP Products North America Inc. sulfur dioxide emission limitations
Universal Citation: 326 IN Admin Code 4.1-3
Current through March 20, 2024
Authority: IC 13-14-8; IC 13-17-3-4; IC 13-17-3-11
Affected: IC 13-15; IC 13-17
Sec. 3.
(a) BP Products North America Inc., Source Identification Number 00003, shall comply with the sulfur dioxide emission limits in pounds per million British thermal units (MMBtu), pounds per hour, and other requirements as follows:
Emissions Unit Description | Emission Limit lbs/MMBtu | Emission Limit lbs/hour |
(1) No. 1 Power Station Boilers 3, 4, 5, 6, and 7: | ||
(A) Boilers 3 and 4 | 0.033 each | 17.49 total |
(B) Boilers 5, 6, and 7 | 0.033 each | 26.24 total |
(2) No. 3 Power Station Boilers 1, 2, 3, 4, and 6 | 0.033 each | 18.98 each |
(3) No. 11 Pipe Still: | ||
(A) H-1X Heater | 0.033 | 8.25 |
(B) H-2 Vacuum Heater | 0.033 | 1.49 |
(C) H-3 Vacuum Heater | 0.033 | 1.82 |
(D) H-101, 102, 103, and 104 Coker Preheaters | 0.033 each | 6.60 total |
(E) H-200 Crude Charge | 0.033 | 8.23 |
(F) H-300 Furnace | 0.033 | 5.94 |
(4) No. 12 Pipe Still: |
(A) H-1A, H-1B Preheaters, and H-2 Vacuum Heater | 0.033 each | 21.78 total |
(B) H-1CN and H-1CS Crude Preheaters | 0.033 each | 7.92 total |
(C) H-1CX | 0.033 | 13.53 |
(5) No. 2 Isomerization H-1 Feed Heater Furnace | 0.034 | 6.46 |
(6) No. 3 Ultraformer: | ||
(A) H-1 Feed Heater Furnace | 0.033 | 7.92 |
(B) H-2 Feed Heater Furnace | 0.034 | 6.29 |
(C) F-7 Furnace | 0.035 | 0.81 |
(7) No. 4 Ultraformer: | ||
(A) F-1 Ultraformer Furnace, F-8A and F-8B Reboilers | 0.033 each | 13.00 total |
(B) F-2 Preheat Furnace | 0.033 | 9.44 |
(C) F-3 No. 1 Reheat Furnace | 0.033 | 7.99 |
(D) F-4, F-5, and F-6 Reheat Furnaces | 0.033 each | 9.41 total |
(E) F-7 Furnace | 0.033 | 1.72 |
(8) Aromatic Recovery Unit F-200A and F-200B Furnace | 0.035 each | 17.47 total |
(9) Blending Oil Desulfurization Furnace F-401 | 0.034 | 1.19 |
(10) Catalytic Refining Unit: | ||
(A) F-101 Feed Preheater | 0.04 | 2.88 |
(B) F-102a Stripper Reboiler | 0.04 | 2.40 |
(11) FCU 500 | 750.00 | |
(12) FCU 600 | 437.50 | |
(13) Wastewater Sludge Fluid Bed Incinerator | 1.78 | |
(14) Catalytic Feed Hydrotreating Unit: | ||
(A) F-801 A/B Preheater Furnace | 0.035 | 2.33 |
(B) F-801 C Preheater Furnace | 0.035 | 2.1 |
(15) Beavon-Stretford Tail Gas Unit | 53.10 total reduced sulfur | |
(16) Sodium Bisulfite Tail Gas Unit | 9.0 | |
(17) Sulfur Recovery Unit Incinerator | 0.033 | 1.25 |
(18) F-1 Asphalt Heater | 0.033 | 0.43 |
(19) F-2 Steiglitz Park Residual Heater | 0.033 | 0.90 |
(20) Distillate Desulfurization Unit Heaters WB-301 and WB-302 | 0.033 each | 4.24 total |
(21) Hydrogen Unit B-1 | 0.033 | 12.09 |
(b) BP Products North America Inc. shall:
(1)
maintain daily records of:
(A) fuel type,
average sulfur content, and average fuel gravity for each emissions unit
specified in this section with sulfur dioxide emission limitations less than or
equal to four-hundredths (0.04) pound per MMBtu;
(B) calculated coke burn and sulfur content
of the coke for the FCU 500 and FCU 600;
(C) total reduced sulfur concentration,
hydrogen sulfide concentration, and calculated stack gas flow rate for the
Beavon-Stretford Tail Gas Unit; and
(D) sulfur dioxide concentration and stack
gas flow rate for the Sodium Bisulfite Tail Gas Unit; and
(2) submit a report to the department within
thirty (30) days after the end of each calendar quarter containing the average
daily sulfur dioxide emission rate in pounds per hour sulfur dioxide for the
emissions units specified in this section, except for the Beavon-Stretford Tail
Gas Unit, that is to be reported as pounds per hour total reduced sulfur
calculated as sulfur dioxide.
Disclaimer: These regulations may not be the most recent version. Indiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.