Indiana Administrative Code
Title 170 - INDIANA UTILITY REGULATORY COMMISSION
Article 6 - WATER UTILITIES
Rule 3 - Central Station Hot Water Heating Utilities
Section 3-11 - Temperature standards
Current through March 20, 2024
Authority: IC 8-1-1-3; IC 8-1-2-4
Affected: IC 8-1-2-33; IC 8-1-2-34
Sec. 11.
Station Operating Schedule of Temperatures.
(a) The standard for heating service shall be determined by the average temperature of the flow and return water in the mains at the heating plant of the utility and shall not be less than that indicated in the following table showing the average temperatures of flow and return.
(b) The average temperature of station flow and return water shall be determined by dividing by two the sum of the temperature of the water in the flow main and the temperature of the water in the return main.
TABLE I
Table Showing Average Temperatures of Flow and Return Water
Day Schedule | Permissible Night Schedules | ||
Outside Temperature Degrees Fahrenheit | 6:00 a.m. to 6:00 p.m. | 6:00 p.m. to 9:30 p.m. 3:30 a.m. to 6:00 a.m. | 9:30 pm. to 3:30 a.m. |
70 | 80 | 85 | 70 |
65 | 92 | 98 | 82 |
60 | 102 | 107 | 92 |
55 | 111 | 116 | 101 |
50 | 121 | 126 | 111 |
45 | 129 | 134 | 119 |
40 | 137 | 142 | 128 |
35 | 144 | 148 | 136 |
30 | 151 | 154 | 145 |
25 | 158 | 160 | 154 |
20 | 164 | 165 | 162 |
15 | 170 | 170 | 170 |
10 | 175 | 175 | 175 |
5 | 180 | 180 | 180 |
zero | 184 | 184 | 184 |
-5 | 187 | 187 | 187 |
-10 | 190 | 190 | 190 |
-15 | 191 | 191 | 191 |
-20 | 192 | 192 | 192 |
NOTE.-See appendix [ 170 IAC 6-3-27 ] for schedule of station flow temperature.
TABLE II
Table Showing Temperature-Lowering Coefficients of Wind Movements
Outside Temperature | Temperature-Lowering Effect per Mile per Hour |
50° to 40° | .75 degrees |
40 to 30 | 1.00 degrees |
30 to 20 | 1.10 degrees |
20 to 10 | 1.20 degrees |
10 to 0 | 1.30 degrees |
0 to -10 | 1.40 degrees |
-10 to -20 | 1.50 degrees |
TABLE III
Table Showing Temperature-Lowering Effect of Wind
Outside Temperature | Light 5 to 10 m.p.h. | Wind Medium 10 to 15 m.p.h. | Strong 15 to 20 m.p.h. |
50° to 40° | 6° | 9° | 13° |
40 to 30 | 8 | 13 | 17 |
30 to 20 | 8 | 14 | 19 |
20 to 10 | 9 | 15 | 21 |
10 to 0 | 10 | 16 | 23 |
0 to -10 | 10 | 17 | 25 |
-10 to -20 | 11 | 19 | 26 |
NOTE.-The plant operator will vary these wind coefficients to suit local conditions.