Illinois Administrative Code
Title 83 - PUBLIC UTILITIES
Part 501 - STANDARDS OF SERVICE FOR GAS UTILITIES AND ALTERNATIVE GAS SUPPLIERS
Subpart B - NATURAL GAS MEASUREMENT REQUIREMENTS
Section 501.120 - Meter and Equipment Handling Requirements

Current through Register Vol. 48, No. 38, September 20, 2024

a) A utility shall store all meters not in service in a secure, weather-protected environment and stack the meters in an upright position or in a manner recommended by the manufacturer. The weather-protected environment requirement does not apply to utility vehicles used to transport meters.

b) A utility shall provide a secure means of transporting a meter prior to its installation and after its removal from service.

c) A utility shall cap the inlet and outlet connections of a meter when the meter is not in service. Meter caps are not necessary when a meter is located within a utility's proving room or meter soaking room or after the meter has been tested and is waiting for repair.

d) A utility shall protect all auxiliary and tertiary equipment prior to installation and after removal from service.

e) If a utility drops or in any way damages a meter or auxiliary or tertiary equipment prior to installation, the utility shall not place that equipment into service until the utility establishes the proper operation and accuracy of the equipment.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.