Illinois Administrative Code
Title 8 - AGRICULTURE AND ANIMALS
Part 215 - ANHYDROUS AMMONIA, LOW PRESSURE NITROGEN SOLUTIONS, EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
Subpart A - ANHYDROUS AMMONIA, EQUIPMENT, CONTAINERS, AND STORAGE FACILITIES
Section 215.80 - Electrical Equipment and Wiring

Universal Citation: 8 IL Admin Code ยง 215.80

Current through Register Vol. 48, No. 12, March 22, 2024

a) Electrical equipment and wiring for use in ammonia installations shall be general purpose or weather resistant as appropriate.

b) Where concentrations of ammonia in air in excess of 16% by volume are likely to be encountered, electrical equipment and wiring shall be installed to comply with the requirements specified for use in hazardous locations, Class I, Group D, of ANSI/NFPA 70, National Electrical Code, Articles 500 and 501.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.