Illinois Administrative Code
Title 77 - PUBLIC HEALTH
Part 295 - ASSISTED LIVING AND SHARED HOUSING ESTABLISHMENT CODE
Subpart I - PHYSICAL PLANT AND ENVIRONMENTAL REQUIREMENTS
Section 295.9005 - Units

Current through Register Vol. 48, No. 12, March 22, 2024

a) Each unit in the establishment shall include, at a minimum, the following:

1) A lockable door. The key to the unit is to be kept by the resident. The establishment shall keep a key to all lockable doors, to be used only in the case of an emergency situation. The door lock shall be capable of being disabled if required by the resident's service plan.

2) A telephone jack.

3) An emergency communication response system in place 24 hours each day by which a resident can notify building management, an emergency response vendor, or others able to respond to his or her need for assistance. (Section 10 of the Act)

b) To provide natural light and to provide safe egress in an emergency situation, a unit shall have:

1) A window to the outside; or

2) A door made of glass to the outside.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.