Current through Register Vol. 48, No. 52, December 27, 2024
a) Pumps. Petroleum
and hazardous substances shall be transferred from tanks by means of fixed
pumps designed and equipped to allow control of the flow and to prevent leakage
or accidental discharge. Systems that employ continuous air pressure on storage
tanks in connection with gauging or venting devices are prohibited.
b) Gravity Flow Prohibitions and Precautions
1) Devices that discharge by gravity are
prohibited and were to have been removed by January 1, 1986. The transfer of
waste motor oil to or from USTs is not subject to the requirements for transfer
by means of fixed pumps. Gravity transfer of waste motor oil is permitted.
Gravity devices at motor fuel dispensing facilities, bulk facilities, motor
vehicle repair shops and parking garages that are retained for their novelty or
historical interest may be retained at the facility, but shall be rendered
nonfunctional.
2) Where tanks are
at an elevation that produces a gravity head on the dispensing device, the tank
outlet shall be equipped with a device, such as a solenoid valve, positioned
downstream as close as possible to the tank, installed and adjusted so that
liquid cannot flow by gravity from the tank.
c) Siphon Bars. Siphon bars that are used to
transfer petroleum and hazardous substances between tanks by means of gravity
or negative atmospheric pressure shall be permitted subject to the following
requirements:
1) The height of the tops of all
tanks connected by the siphon bars shall be within 6 inches of each
other;
2) Piping shall meet the
requirements of Section
175.420; and
3) Release detection methods for tanks and
piping shall be of a type approved for tanks connected by siphon bars, in
accordance with Section
175.630.
d) Electrical Equipment and Requirements for
Pumps and Dispensers. All pumps and dispensing devices for petroleum and
hazardous substances and all connected electrical equipment shall be installed
in accordance with Section
175.425. Dispenser discharge
nozzles shall be constructed of nonferrous material or equipped with static
wire hose.
e) Dispensers. All
dispensers shall be required to comply with the following:
1) Under-dispenser Containment.
Under-dispenser containment is required pursuant to Section
175.410.
2) Labeling. All dispensing devices used for
drawing regulated substances from USTs shall be labeled in a conspicuous place
with the name of the product.
3)
Size Limits. With the exception of industrial or fleet facilities with no
connection to any UST from which regulated products are sold at retail,
dispensers shall not be connected, directly or indirectly, to any tank for
which the total of all compartments is over 30,000 gallons capacity.
4) Hoses and Reels. Hoses shall be secured to
protect them from damage. Mechanical retractable devices are required on
dispenser hoses in excess of 18 feet in length. Hose length on mechanical
retractors shall not exceed 50 feet without written approval of OSFM. Detection
of any of the following conditions indicates permanent damage and shall require
that the hose be replaced with the nozzle immediately bagged if any portion of
the hose or nozzle is actively leaking:
A)
hose cuts, abrasions or cracks in the hose cover that penetrates to the
reinforcement;
B) blisters or loose
cover;
C) soft spots in the hose,
particularly adjacent to the coupling;
D) indication of coupling slippage or
irregular coupling alignment; or
E)
flattened or kinked hose resulting in permanent deformation.
5) Third-party Listed Latch-open
Devices. When dispensing liquids into motor vehicle fuel tanks, dispenser
nozzles shall be either manually held open or may be held open by a latch-open
device that is an integral part of the listed nozzle assembly. An automatic
self-closing type nozzle with a latch hold open device must be installed as an
integral part of the listed nozzle assembly.
6) The dispensing nozzle must be an automatic
closing type that has been tested and is third party listed for its intended
use. Nozzles used to dispense diesel fuel at attended self-service and
unattended self-service motor fuel dispensing facilities shall have
large-diameter, "leaded" spouts to avoid dispensing diesel fuel into vehicles
with gasoline tanks.
7) Prohibition
on Unapproved Hold-open Devices. Temporary, portable or removable hold-open
devices, including, but not limited to, plastic hooks, wires, wood blocks, gas
caps and similar devices, shall not be used on dispenser nozzles. No person
shall market, expose for sale, sell or distribute by any means whatsoever, in
the State of Illinois, any temporary, portable or readily removable device
designed or intended to be used for the purpose of holding open flammable or
combustible liquid dispensing nozzles during dispensing operations at motor
fuel dispensing facilities.
8)
Requirements for a Secondary Means of Control. Any dispensing devices from
which the flow of product is normally stopped by means other than by the
closure of the nozzle valve shall further comply with either of the following:
A) The system shall be provided with
equipment with a feature that causes or requires the closing of the nozzle
valve before product flow may be resumed or before the nozzle can be replaced
in its normal position in the dispenser; or
B) The nozzle valve latch-open device shall
be removed.
9) Flow
Shutoff
A) Hose nozzle valves shall be of the
type that will close automatically, independent of the latch-open device, upon
loss of pressure in the dispensing system. The latch-open device may only be
engaged when the dispensing system is under pressure.
B) All dispensing devices shall be equipped
with 2 methods of controlling the flow of fuel:
i) deactivation of the dispenser;
and
ii) closing of the hand nozzle
or some other secondary means to shut off flow.
C) The nozzle must be designed and maintained
to cease the flow of product if the nozzle falls to the ground from the fill
pipe of the motor vehicle being fueled.
D) A listed emergency breakaway device
designed to retain liquid on both sides of the breakaway point shall be
installed on each hose. If hoses are attached to a hose-retrieving mechanism,
the listed emergency breakaway device shall be installed between the point of
attachment of the hose-retrieving mechanism to the hose and the hose nozzle
valve.
E) A control shall be
provided that will permit the pump to operate only when a dispensing nozzle is
removed from its bracket or normal position with respect to the dispensing
device, and the switch on the dispensing device is manually activated. This
control shall also stop the pump when all nozzles have been returned, either to
their brackets or normal nondispensing position.
10) Rebuilt Hose Nozzles. Rebuilt hose
nozzles may be used if they are listed for that purpose.
11) Spout Anchor Springs. Nozzles must be
equipped with devices (e.g., wire or a spout anchor spring) designed to retain
the nozzle spout in the vehicle fill pipe while refueling. These devices must
be part of the listed nozzle assembly. The spout anchor spring shall be of the
type recommended by the manufacturer of the hose nozzle valve and be installed
and maintained in accordance with the manufacturer's recommendations.
12) Shear Valve. Pressurized piping systems
require a listed rigidly anchored emergency shutoff (shear) valve installed per
manufacturer's specifications in each supply line at the base of each
individual dispenser. The valve shall incorporate a fusible link or other
thermally activated device, designed to close automatically in the event of
severe impact or fire exposure.
A) In addition
to being rigidly anchored to structural supports, each shear valve shall also
be:
i) Installed so as to align with the
dispenser piping to avoid stresses on the connection between the shear valve
and the dispenser supply piping;
ii) Installed so that the shearpoint of the
valve is within 1/2 inch plus or minus of grade, with grade being the mounting
plane of the dispenser base; and
iii) Installed so that the link arms can
freely operate and the valve close without interference.
B) After October 13, 2018, any product piping
manifolded beneath a dispenser must be manifolded so that each line connecting
to dispenser supply piping is on its own separate shear valve.
i) Manifolding of piping under a dispenser
shall not be done above a shear valve.
ii) Piping beneath a dispenser that was
manifolded above a shear valve prior to October 13, 2018 may remain in that
configuration until the piping is upgraded, provided that any single poppet
shear valve beneath the dispenser is replaced with a double poppet shear valve.
This shear valve replacement, if indicated, shall be completed by October 13,
2019. On or after May 2, 2023, manifolded piping above a shear valve must be
removed upon dispenser replacement.
13) Collision Protection for Dispensers. All
fuel dispensers shall be mounted or protected against collision damage by means
of islands, posts or an equivalent means.
14) Secure Mounting of Dispensers. Dispensing
devices shall be bolted to their mounting surface in accordance with the
manufacturer's instructions.
15)
Under-dispenser containments shall be factory manufactured and shall comply
with the design requirements of Section
175.410(i).
f) Location of Pumps and
Dispensers
1) Unless otherwise allowed under
this Section or permitted at the time of installation, dispensers and pumps
shall be located outside of buildings. Dispenser hoses shall not be able to
reach to within 5 feet from any building or window or other building opening,
such as a basement, cellar, pit, ventilated soffit or any air intake or exhaust
of any building, and must be located to avoid pocketing of vapor or liquid.
Dispensers installed after October 1, 1985 shall not be located below grade. A
transfer pump is not considered a dispenser and may be located inside a
pumphouse or industrial building. Bulk-load outs are not considered dispensing
and shall comply with NFPA 30 (see 41 Ill. Adm. Code
174.310).
2) However, buildings used exclusively for
fleet dispensing of motor fuels may house dispensers and dispensing equipment
for combustible liquids (Class II and III) so long as the buildings and
equipment are in compliance with NFPA 30A, NFPA 101, and NFPA 70, incorporated
by reference in 41 Ill. Adm. Code
174.210. Such facilities shall
also comply with all applicable OSFM administrative rules.
3) Indoor dispensing shall otherwise be
allowed only if approved by OSFM in writing prior to November 29, 1993 and if
the following requirements are met:
A) For
dispensing units existing prior to September 15, 1978:
i) be separated from other areas by 2 hour
fire resistive construction;
ii) be
provided with a mechanical or gravity ventilation system electrically
interlocked with the dispensing units so that the dispensing units cannot be
operated, unless the ventilation fan motors are energized and operating. The
system shall be upgraded to meet NFPA 30A not later than September 1, 2011;
and
iii) have all openings beneath
dispenser enclosures sealed to prevent the flow of leaking fuel to lower
building spaces.
B) For
dispensers existing as of October 1, 1985 and located within repair and parking
garages:
i) be not below grade;
ii) be separated from motor vehicle repair
areas, pits and basements by 2 hour fire resistive construction;
iii) be protected against physical damage
from vehicles by mounting the dispensing unit on a concrete island or by
equivalent means;
iv) be located in
a position where the dispensers and pumps cannot be struck by an out-of-control
vehicle descending a ramp or other slope;
v) be provided with an approved mechanical or
gravity ventilation system, that shall be upgraded to meet NFPA 30A by not
later than September 1, 2011; and
vi) be provided with a clearly identified
emergency stop, readily accessible in case of fire or physical damage to any
dispensing units to shut off the power to dispensing units and submersible
pumps.
C) Existing
dispensing units located below grade in repair and parking garages as of
October 1, 1985 shall have independent mechanical ventilation systems and the
entire dispensing area shall be protected by an automatic sprinkler system
conforming to the requirements of NFPA 13, incorporated by reference in 41 Ill.
Adm. Code 174.210. The sprinkler system shall be interconnected to an alarm
system conforming to NFPA 72, incorporated by reference in 41 Ill. Adm. Code
174.210, and the sprinkler system shall be a wet system except in unheated
areas. Facilities in existence as of September 1, 2011 shall have the option of
complying with the Edition of NFPA 72 incorporated by reference in 41 Ill. Adm.
Code 174.210 or the NFPA alarm and
sprinkler system requirements in effect at the time of their installation.
i) The ventilation systems shall be
electrically interlocked with the gasoline dispensing units so that the
dispensing units cannot be operated unless the ventilation fan motors are
energized and operating, and shall be upgraded to meet NFPA 30A by not later
than September 1, 2011.
ii)
Existing dispensing units located below grade within buildings shall also
comply with subsection (f)(3)(B), as applicable.
4) Curb pumps or pumps located in
any portion of a public street are prohibited, except that devices at motor
fuel dispensing facilities, bulk facilities, vehicle repair garages and parking
garages that are retained for their novelty or historical interest may be
retained at the facility if rendered nonfunctional.
5) Dispensing devices at a motor fuel
dispensing facility shall be located 10 feet or more from any property lines or
buildings, so that all parts of the vehicle being served will be on the
premises of the facility or garage.