Section 160.80 - Venting of Tanks - Normal Vents

Universal Citation: 41 IL Admin Code ยง 160.80

Current through Register Vol. 48, No. 38, September 20, 2024

a) Each tank over 100 gallons in capacity shall have vent openings, or pressure vacuum vents in accordance with NFPA 30 (1981).

b) Vent openings shall in no case be less than one and one-fourth inches in diameter, and where a power pump is used in filling the tanks, and a tight connection is made to the fill pipe, the vent shall not be smaller than the fill pipe.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.