Illinois Administrative Code
Title 41 - FIRE PROTECTION
Part 160 - STORAGE, TRANSPORTATION, SALE AND USE OF GASOLINE AND VOLATILE OILS: RULES AND REGULATIONS\ RELATING TO GENERAL STORAGE
Section 160.40 - Location of Tanks - Distance Between Aboveground Tanks

Universal Citation: 41 IL Admin Code ยง 160.40

Current through Register Vol. 48, No. 12, March 22, 2024

a) The minimum distance from tanks to adjacent tanks shall be as follows:

Tank Capacity

(Gallons)

Minimum Distance

(Feet)

24,000 or less.................................................

5

24,001 to 48,000............................................

10

48,001 to 75,000............................................

13

75,001 to 100,000..........................................

15

Over 100,000.................................................

One Tank Diameter

b) If tanks are of different capacities, the capacity of the larger tank shall govern its distance to adjacent tanks.

c) Existing tanks of under 24,000 gallons shall maintain a minimum distance of at least 3 feet.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.