Illinois Administrative Code
Title 41 - FIRE PROTECTION
Part 160 - STORAGE, TRANSPORTATION, SALE AND USE OF GASOLINE AND VOLATILE OILS: RULES AND REGULATIONS\ RELATING TO GENERAL STORAGE
Section 160.150 - Piping - Underground

Current through Register Vol. 48, No. 12, March 22, 2024

a) Metallic piping shall not be surrounded or covered by cinders or other material of corrosive effect, but preferably should be laid in sand, and where carried in conduit, the openings of such conduit must be sealed to prevent escape of liquid except for vent pipes.

b) Pipe lines buried on railroad property shall be laid at a depth of not less than three feet; where they pass under tracks they shall be laid at least four feet below bottom of ties.

c) Piping buried in city streets or under roads shall be sealed in conduit. Joints of conduit shall be sealed to prevent leakage and pitch shall be toward tank yard, and a vent pipe shall be provided.

d) Metallic piping shall be coated with asphaltum or other corrosion resisting material.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.