Illinois Administrative Code
Title 41 - FIRE PROTECTION
Part 150 - RACE TRACK RULES FOR FIRE SAFETY
Section 150.60 - General Occupancy Requirements
Universal Citation: 41 IL Admin Code ยง 150.60
Current through Register Vol. 48, No. 38, September 20, 2024
a) Heating and Cooking Equipment
1) Heating and cooking equipment shall be
listed by Underwriters Laboratories, Inc. or the American Gas Association.
Installation of the equipment and related fuel storage and piping facilities
shall be in accordance with recognized standards and good practices as found in
the following standards: NFPA Standard No. 54-1974, National Fuel Gas Code;
NFPA Standard No. 58-1974, Storage and Handling of Liquefied Petroleum Gases
and NFPA Standard No. 70-1975, National Electrical Code.
2) Cylinders or tanks of compressed fuel
gases shall not be permitted in grandstands or in buildings except as provided
in NFPA Standard 58-1974 (Storage and Handling of Liquefied Petroleum
Gases).
3) Sleeping rooms shall be
heated by steam, hot water, warm air, electricity or approved individual
gas-fired heating units.
4) Steam
and hot water boilers and furnaces shall be located in a separate building or
enclosure with fire resistive floors, walls, ceilings and doors. Enclosures
around high pressure boilers (operating at over 15 per square inch (psi) gauge
pressure) shall have two-hour fire resistance with openings protected by 11/2
hour fire doors; enclosures around low pressure boilers (operating below 15 per
square inch (psi) gauge pressure for steam and 30 per square inch (psi) gauge
pressure for hot water) and furnaces shall have 3/4-hour fire resistance with
openings protected by 3/4-hour fire doors.
5) Ranges, deep fat fryers and grills shall
have a hood and exhaust ventilation system to the outside as outlined in NFPA
Standard No. 96-1973, Vapor Removal from Commercial Cooking
Equipment.
6) Hood and Vent
Systems: All hood and vent systems over cooking equipment shall be protected by
a listed automatic fire extinguishing system installed according to NFPA
Standard No. 96-1973, Vapor Removal from Cooking Equipment. Actuation of the
system shall transmit an alarm to a constantly attended location.
b) Electrical System
1) New electrical systems shall be installed
by qualified electricians in accordance with NFPA Standard No. 70-1975, the
National Electrical Code. Existing electrical systems installed in accordance
with the requirements of the National Electrical Code in effect at the time of
installation will not be required to be replaced provided they are properly
maintained, and provided that electrical systems shall be updated to conform to
NFPA Standard No. 70-1975 as buildings are updated to conform to NFPA Standard
No. 70-1975 as buildings are updated in accordance with Section 3.3 of these
rules (41 Ill. Adm. Code Section
150.30(c)
) .
2) Plug receptacles in electrical systems in
barns are permitted provided that the receptacles are at least 4 ft. above
floor level (centered between stalls) and of grounded type. In addition,
electrical equipment (unless double insulated) shall be of the 3 wire
(grounded) type.
3) Electrical
systems in sleeping rooms shall be provided with at least one double plug
receptacle having two standard outlets.
c) Flammable Liquids
1) Flammable liquids shall be stored and
handled in accordance with recognized standards and good practices as found in
NFPA Standard No. 30-1973, Flammable and Combustible Liquids Code.
2) No flammable liquids shall be stored in
the grandstand structure. Beverage containers of one gallon or less shall be
exempt.
3) Bulk supplies of
flammable liquids over 55 gallons shall be stored in buried tanks.
4) Bulk supplies of flammable liquids in
containers of 55 gallons or less shall be stored outside of and at least 50
feet from all buildings. Outside storage under this section shall be limited to
550 gallons in aggregate stored in any one location. Storage areas shall be
enclosed by either a masonry wall or non-combustible fence not less than six
(6) feet in height with entrance kept locked when not in use.
5) Listed safety cans shall be used for
handling flammable liquids in less than drum quantities. (Paints, insecticides,
and veterinary medicines in original containers of 5 gallons or less shall be
exempt from this requirement)
d) Hay Storage
1) Facilities for the storage of hay or straw
may be located either within or detached from the barn structure. Hay Storage
shall not be permitted in barn lofts.
2) Hay storage rooms located within the barn
shall be:
A) Separated from the rest of the
stalls and sleeping rooms by walls extending to roof deck having at least
one-hour fire resistance rating with doorways protected by self-closing
3/4-hour fire door.
B) Provided
with smoke relief venting of at least 1 sq. ft. for each 25 sq. ft. of hay
storage area unless the area is sprinklered.
3) Detached hay storage buildings having an
area of less than 200 sq. ft., shall be located at least 10 ft. from Class A or
B barns, and 20 ft. from Class C barns, provided, however, that detached hay
storage buildings with exterior walls of masonry, masonry veneer, or one-hour
fire resistive protected construction and having an area of less than 200 sq.
ft. shall be located at least 10 ft. from buildings with combustible exterior
walls. Hay storage buildings having an area greater than 200 sq. ft. shall
comply with the spacing provisions of Section 5.24 (41 Ill. Adm. Code Section
150.50(b)(4)(A)
) .
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.