Current through Register Vol. 48, No. 38, September 20, 2024
a) OSFM hereby
adopts the nationally-recognized standards, codes and guides listed as
incorporated standards in subsection (b), subject to OSFM modifications listed
in subsection (c). Standards incorporated by reference in this Part do not
include any later editions or amendments, unless explicitly stated otherwise in
this Part.
b) Incorporated
Standards
National Fire Protection Association
Batterymarch Park
Quincy MA 02269
NFPA 101, Life Safety Code (2015) (adopted in its entirety,
subject to the OSFM modifications in subsection (c)).
NFPA 101, Life Safety Code (2000) (only to the extent cited in
subsections (c)(1), (c)(2) and (c)(6)).
NFPA 101A, Guide on Alternative Approaches to Life Safety
(2016).
NFPA 101A, Guide on Alternative Approaches to Life Safety
(2001) (only to the extent cited in subsection (c)(1)).
NFPA 914, Code for Fire Protection of Historic Structures
(2010) (only to the extent cited in Section
100.8) .
NFPA 80, Standard for Fire Doors and Other Opening Protectives
(2013) (only to the extent cited in subsection (c)(10)(I)).
NFPA 1, Fire Code (2015) (only to the extent cited in
subsection (c)(11)).
c)
Modifications to the Life Safety Code
1) High
Rise Buildings
All existing high rise buildings, as defined in NFPA 101, Life
Safety Code (all applicable Sections), shall comply with the sprinkler
requirements prescribed in the 2000 edition of NFPA 101, Life Safety Code,
effective January 1, 2002. Use of a Fire Safety Evaluation System (FSES) for
compliance with this Section must adhere to NFPA 101A, Guide on Alternative
Approaches to Life Safety (2001).
2) Assembly Occupancies
All existing assembly occupancies, as defined in NFPA 101
(Chapter 13), shall comply with the sprinkler requirements prescribed in the
2000 edition of NFPA 101, Life Safety Code, effective January 1, 2002.
3) Day Care Occupancies
A) Child Care Facilities (see the Child Care
Act of 1969 [ 225 ILCS101 ])
i) For purposes
of determining the occupancy subclassification of a day care facility, the
current version of the following Department of Children and Family Services
rules will be applied: 89 Ill. Adm. Code 406, 407 and 408. This is applicable
to licensed and nonlicensed facilities.
ii) Child-to-staff ratios in day care
facilities shall comply with 89 Ill. Adm. Code 406, 407 and 408 and with the
Child Care Act of 1969 [ 225 ILCS 10 ]. Any conflicting provisions of NFPA 101,
Life Safety Code are inapplicable to day care facilities.
iii) In day care homes in which clients
occupy a level below the level of exit discharge, means of escape shall be
provided in accordance with either the applicable requirements of NFPA 101,
Life Safety Code (2015) or with one of the following:
*If a means of escape discharging directly to the outside at
the basement level is not provided, requiring occupants to traverse another
level of the home to exit, the path of escape through the level of exit
discharge shall be separated from the remainder of that level of the home by
construction providing a minimum fire resistance rating of 1-hour; or
*The home shall be equipped with smoke alarms permanently
powered by the building's electrical system and wired so that the actuation of
one smoke alarm will actuate all the smoke alarms in the dwelling. At least one
such smoke alarm shall be located on each level of the occupancy (excluding
unoccupied attics and crawl spaces), and the path of escape through the level
of exit discharge (from the basement door to the exterior door of the home)
must be protected by automatic fire sprinklers. Listed residential sprinklers
shall be used and the installation shall be made in accordance with 41 Ill.
Adm. Code 109 and codes and standards referenced in that Part.
B)Windows for Rescue in Existing
Day Care Centers Windows for rescue required by NFPA 101, Life Safety Code
(2015), Section 17.2.11.1, are not required for existing day care
centers.
C)Day Care Homes - New and
Existing
Day care homes shall be defined as new and existing based on
the date the original home construction was completed and available for
residency.
D)Smoke
Detection in Corridors Outside Day Care Homes Located Within a Building of
Another Occupancy
A smoke alarm system installed as prescribed in this subsection
(c)(3)(D) shall be permitted to be used in day care homes located within a
building of another occupancy in lieu of a smoke detection system connected to
a fire alarm system as required by NFPA 101, Life Safety Code (2015), Sections
16.6.3.4.2 and 17.6.3.4.2:
i)Smoke
alarms connected to the building's electric shall be installed in accordance
with proper coverage standards in the corridor serving the day care home.
ii)Smoke alarms connected to the
building's electric shall be installed in accordance with proper coverage
standards within the day care home (see NFPA 101, Life Safety Code (2015)),
Section 16.6.3.4 for new day care homes and Section 17.6.3.4 for existing day
care homes) as well as within 15 ft of all sleeping rooms. NFPA 101, Life
Safety Code (2015), Section 17.6.3.4.4 shall not be permitted to be used.
iii)All smoke alarms regulated by
subsections (c)(3)(D)(i) and (ii) will be arranged so that operation of any
smoke alarm shall cause all smoke alarms within the corridor and the day care
home to sound.
4) One- and Two-Family Dwellings
NFPA 101, Life Safety Code (2015), Chapter 24 (One- and
Two-Family Dwellings) is adopted as recommended guidelines only, except when
referenced as being required for compliance with this Part.
5) Communicating Spaces
Corridors shall not be required to be separated from
communicating spaces as required in NFPA 101, Life Safety Code (2015), Section
8.6.6, in new or existing occupancies, provided all of the following criteria
are met:
A) The arrangement complies
with all other requirements of Section 8.6.6(4), including, if applicable,
8.6.6(4)(b);
B) The building is
protected throughout by an approved automatic sprinkler system; and
C) Two means of egress are provided to
occupants of the building on each floor that is served by the communicating
opening that do not require the use of the stairway located within the
communicating space, as defined in NFPA 101, Section 8.6.6.
6) Mixed Occupancies
All existing mixed occupancies, as defined by NFPA 101, Life
Safety Code, shall, at minimum, continue to comply with the requirements of
Section 6.1.14 of NFPA 101, Life Safety Code (2000), effective January 1, 2002,
but shall also be permitted to comply with the requirements of Section 6.1.14
of NFPA 101, Life Safety Code (2015).
7)Determination of "Story" in Occupancies
The criteria for what a "story level" is, as found in NFPA 101,
Life Safety Code (2015), Section 16.1.1.8
and 17.1.1.8
are permitted to be used for all occupancies found in NFPA 101, Life Safety
Code (2015).
8)Use of NFPA
101A for Apartment Building Occupancies
NFPA 101A, Guide on Alternative Approaches to Life Safety
(2016), Sections 7.6 and 7.7, may be used to demonstrate equivalent protection
in apartment buildings, regardless of whether they contain board and care
occupancies or house board and care clients receiving personal care
services.
9)Means of Egress
Design to Travel to Direct Exits and Travel to Windows for Rescue in
Educational Occupancies and Day Care Centers Travel to exits or to windows for
rescue shall be permitted as follows in educational occupancies and day care
centers:
A)Travel directly from one room
through adjoining rooms to reach an exit without entering a corridor may be
permitted as long as the travel distance does not exceed 150 ft and doors
located between the rooms are not locked or obstructed and other requirements
found in NFPA 101, Life Safety Code (2015) are met.
B)Travel directly from one room through
adjoining rooms without entering a corridor to reach a window for rescue may be
permitted as long as the travel distance does not exceed 75 ft and doors
located between the rooms are not locked or obstructed and other requirements
found in NFPA 101, Life Safety Code (2015) are met.
C)Travel may be considered to be within a
single room if two or more rooms are connected using openings that are at least
60 inches in clear width without any doors.
10)Door Locking to Prevent Unwanted Entry
Occupancies shall be permitted to provide locking to prevent unwanted entry as
long as all of the following requirements are met:
A)The locking means is approved and complies
with NFPA 101, Life Safety Code (2015);
B)The locking means can be engaged without
opening the door;
C)The unlocking
and unlatching from the occupied side of the door can be accomplished without
the use of a key or tool;
D)For
existing occupancies only, the unlocking and unlatching requires not more than
two releasing operations. For new occupancies, unlocking and unlatching
requires no more than one releasing operation;
E)The unlocking and unlatching means are
mounted at a height not exceeding 48 inches above the finished floor;
F)Locks, if remotely engaged, can be unlocked
from the occupied side;
G)The door
is capable of being unlocked and opened from outside the room by staff with the
necessary key or other credential;
H)The locking means does not modify the door
closer, panic hardware, or fire exit hardware;
I)Modifications to fire door assemblies,
including door hardware, shall be in accordance with NFPA 80, Standard for Fire
Doors and Other Opening Protectives (2013);
J)The emergency response plan addresses the
use of the locking and unlocking means from within and outside the room;
K)Staff is drilled in the
engagement and release of the locking means, from within and outside the room,
as part of the emergency response plan; and
L)If doors are replaced, the new door shall
comply with unlocking and unlatching that does not require more than one
releasing operation.
11)Use of Combustible Vegetation in Buildings
Combustible vegetation within buildings shall comply with NFPA 1, Fire Code
(2015), Section 10.13.
12)Windows
for Rescue and Windows Used as a Secondary Means of Escape Where windows for
rescue are required or where they are used as a secondary means of escape, the
bottom sill of the window shall be not more than 44 inches above the floor as
required by NFPA 101, Life Safety Code (2015), or a permanently fixed stair or
ramp shall be installed at the window to allow occupants to be within 44 inches
of the bottom window sill when standing atop the stair or ramp. The stair or
ramp shall be at least the width of the window or a minimum of 36 inches in
width, whichever is larger.
13)Size and Access to Secondary Means of
Escape If a window is used as a secondary means of escape as permitted by NFPA
101, Life Safety Code (2015) and the size is not in accordance with NFPA 101,
Life Safety Code (2015), the owner or operator of the facility using this
window as a secondary means of escape must demonstrate to an on-site
representative of OSFM that all occupants (staff and clients) can escape
through the window to the exterior of the facility in 3 minutes or less.
d)The materials
incorporated by this Section are on file with OSFM at the following locations:
1035 Stevenson Drive
Springfield IL 62703-4259
James R. Thompson Center
100 W. Randolph Street, Ste. 4-600
Chicago IL 60601