Section 653.805 - Fire Protection Systems
Universal Citation: 35 IL Admin Code ยง 653.805
Current through Register Vol. 48, No. 38, September 20, 2024
A reduced pressure principle backflow preventers shall be installed to protect the community water supply against backflow and backsiphonage when:
a) the fire safety system contains antifreeze, fire retardant or other chemicals;
b) water is pumped into the fire safety system from another source; or
c) water flows into the fire safety system by gravity from a non-potable source; or
d) there is a connection whereby water can be pumped into the fire safety system from any other source.
Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.