Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 653 - DESIGN, OPERATION AND MAINTENANCE CRITERIA
Subpart A - DESIGN REQUIREMENTS
Section 653.105 - Rate of Usage

Current through Register Vol. 48, No. 38, September 20, 2024

a) Average daily rate of usage shall be calculated using two times the average daily usage as determined in Section 653.104 and converted into an average rate over 24 hours in units of gallons per minute.

b) The maximum daily rate of usage shall be calculated using 1.5 times the average daily rate of usage.

c) The maximum hourly rate of usage shall be calculated using two times the maximum daily rate of usage.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.