Illinois Administrative Code
Title 35 - ENVIRONMENTAL PROTECTION
Part 653 - DESIGN, OPERATION AND MAINTENANCE CRITERIA
Subpart A - DESIGN REQUIREMENTS
Section 653.103 - Wells

Current through Register Vol. 48, No. 38, September 20, 2024

a) Construction shall conform to the Standards and the current American Water Works Association (AWWA) Standard for Deep Wells, A100. Well construction shall also comply with all state, county and municipal regulations and statutes.

b) Water from creviced limestone formations having less than 50 feet of soil cover shall be treated to meet the standards of 35 Ill. Adm. Code 604.

c) Grouting shall be provided in accordance with the Standards for a depth of ten feet from:

1) the original ground surface where fill has been added; or

2) existing ground surface where soil has been removed.

d) A lead, elastomeric or other equivalent seal shall be provided between the pump base and pump pedestal for above-base discharge pumps.

Disclaimer: These regulations may not be the most recent version. Illinois may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.